Plan Review Details - Permit 21031423
Plan Review Stops For Permit 21031423
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-23 Cont ID  
Sent By rmcdouga Date 2021-04-23 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2021-04-23 Time 15:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By rmcdouga Date 2021-04-15 Time 14:15 Rev Time 0.00
Received By rmcdouga Date 2021-04-15 Time 11:45 Sent To  
Notes
2021-04-15 14:37:44PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT PRODUCT APPROVAL FOR THE STRUCTURAL MULLIONS.
 FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001.
 PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA
 NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM
 DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING
 MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL MULLIONS
 AND EXTERIOR DOOR TYPES. ONLY ONE SET IS REQUIRED TO BE
 UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 2) THE PRODUCT APPROVALS FOR THE FIXED WINDOWS (NOA NO.
 17-1218.12) AND THE GLAZED DOORS (NOA NO. 16-0617.03)
 HAVE NOT BEEN CONFIRMED TO COMPLY WITH THE 2020 FBC
 SEVENTH EDITION. SUBMIT CURRENT PRODUCT APPROVALS. FBC
 107.3.4
  
 3) IN THE WINDOW AND DOOR SCHEDULE, THE HORIZONTAL
 ROLLING WINDOWS DESIGN PRESSURES ARE + OR - 65 PSF. THE
 REQUIRED PRESSURES IN THE SCHEDULE ARE +49.8 PSF AND -
 66.6 PSF. THE REQUIRED NEGATIVE PRESSURE -66.6 PSF CAN
 NOT BE MORE THAN THE DESIGN PRESSURE -65 PSF. FBC-R301
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-23 Cont ID  
Sent By rmcdouga Date 2021-04-23 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2021-04-22 Time 09:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-15 Cont ID  
Sent By rmcdouga Date 2021-04-15 Time 14:15 Rev Time 0.00
Received By rmcdouga Date 2021-04-02 Time 13:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-04-15 Cont ID  
Sent By rmcdouga Date 2021-04-15 Time 14:15 Rev Time 0.00
Received By rmcdouga Date 2021-04-15 Time 11:45 Sent To  
Notes
***NONE***