Plan Review Details - Permit 21031242
Plan Review Stops For Permit 21031242
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-06 Cont ID  
Sent By ccarvaja Date 2021-08-06 Time 11:20 Rev Time 0.00
Received By ccarvaja Date 2021-07-23 Time 11:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-07 Cont ID  
Sent By lcrespo Date 2021-04-07 Time 11:25 Rev Time 0.00
Received By lcrespo Date 2021-03-30 Time 10:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-07-27 Cont ID  
Sent By lcrespo Date 2021-07-27 Time 09:32 Rev Time 0.00
Received By lcrespo Date 2021-07-27 Time 09:32 Sent To  
Notes
2021-07-27 09:36:0307/27/21 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By lcrespo Date 2021-04-07 Time 11:24 Rev Time 0.00
Received By lcrespo Date 2021-04-07 Time 11:24 Sent To  
Notes
2021-04-07 11:31:0104/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. PLEASE SUBMIT DOCUMENTATION THAT THE PROPOSED DEVICE
 IS LEAD-FREE, WHICH CONTAINS NOT MORE THAN 0.25-PERCENT
 LEAD.
  
 2. PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS, AND
 FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING
 OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL
 HAVE A WEIGHTED AVERAGE LEAD CONTENT 0.25 PERCENT OR
 LESS PER THE 2020 FBC SEC. P 605.2.1 LEAD CONTENT OF
 DRINKING WATER PIPE AND FITTINGS.
  
 3. THE DOCUMENT SUBMITTED IS NOT THE CORRECT ONE. YOUR
 OFFICE HAS BEEN CONTACTED BEFORE ON THE SAME MATTER, SO
 PLEASE MAKE A NOT-AS-IT BEASUSE THAT WILL PREVENT DELAY
 IN FUTURE BACKFLOW REVIEWS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status P Date 2021-08-06 Cont ID  
Sent By ccarvaja Date 2021-08-06 Time 11:20 Rev Time 0.00
Received By ccarvaja Date 2021-08-06 Time 11:21 Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By lcrespo Date 2021-04-07 Time 11:25 Rev Time 0.00
Received By lcrespo Date 2021-04-07 Time 11:25 Sent To  
Notes
***NONE***