Plan Review Details - Permit 21031225
Plan Review Stops For Permit 21031225
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-09-17 Cont ID  
Sent By rmcphers Date 2021-09-17 Time 14:02 Rev Time 0.00
Received By rmcphers Date 2021-09-17 Time 14:02 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-06 Cont ID  
Sent By rmcphers Date 2021-04-06 Time 11:07 Rev Time 0.00
Received By rmcphers Date 2021-04-06 Time 11:07 Sent To  
Notes
2021-04-06 11:09:19PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-17 Cont ID  
Sent By rmcphers Date 2021-09-17 Time 14:03 Rev Time 0.00
Received By rmcphers Date 2021-09-17 Time 14:03 Sent To  
Notes
2021-09-17 14:20:56COMMERCIAL ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ROOF SLOPE TO COMPLY WITH FBC
 1507.10.1 SLOPE.
 BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF NOT LESS
 THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) FOR DRAINAGE, EXCEPT FOR COAL-TAR
 BUILT-UP ROOFS THAT SHALL HAVE A DESIGN SLOPE OF NOT
 LESS THAN ONE-EIGHTH UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (1-PERCENT SLOPE).
  
 2) DOORS MARKED (E) = A 32" DOOR DOES NOT PROVIDE THE
 CORRECT OPENING WIDTH FBC ACCESSIBILITY 404.2.3 CLEAR
 WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
 FBC ACCESSIBILITY 203.9 EMPLOYEE WORK AREAS.
 SPACES AND ELEMENTS WITHIN EMPLOYEE WORK AREAS SHALL
 ONLY BE REQUIRED TO COMPLY WITH 206.2.8, 207.1, AND
 215.3 AND SHALL BE DESIGNED AND CONSTRUCTED SO THAT
 INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER, AND
 EXIT THE EMPLOYEE WORK AREA.
  
 3) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS
 AND ROOFING SYSTEMS.
  
 4) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE
 LISTED BY PERMIT NUMBER ON THE DRAWINGS.
  
 5) PLEASE SHOW THE WIND DESIGN CRITERIA USED (WIND
 SPEED, RISK CATEGORY, EXPOSURE ETC.) PER FBC 1603.1.4
  
 6) PLEASE SHOW ACCESSIBLE PARKING AND ACCESS AISLE
 DIMENSIONS TO COMPLY WITH FBC ACCESSIBILITY 502
  
 7) PLEASE SHOW THE ACCESSIBLE RESTROOM DETAILS PER FBC
 ACCESSIBILITY CHAPTER 6 - SHOW GRAB BAR HEIGHTS,
 LENGTHS AND LOCATIONS, SHOW MIRROR HEIGHT TO THE
 REFLECTING SURFACE, SHOW PAPER DISPENSER HEIGHTS AND
 DISTANCE FROM WATER CLOSETS ETC..
  
 8) JOB COST NEEDS TO BE SHOWN ON THE REVISED BUILDING
 PERMIT APPLICATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-06 Cont ID  
Sent By rmcphers Date 2021-04-06 Time 11:09 Rev Time 0.00
Received By rmcphers Date 2021-04-06 Time 11:09 Sent To  
Notes
2021-04-06 11:27:22COMMERCIAL ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ROOF SLOPE TO COMPLY WITH FBC
 1507.10.1
 2) CANNOT SET ROOF TOP EQUIPMENT ON EMBEDDED 4X4'S -
 PLEASE SHOW MECHANICAL EQUIPMENT ON THE ROOF TO COMPLY
 WITH FBC 1510.10 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10.
 3) ADDING R30 BAT INSULATION IN 2X10 JOIST WILL NOT
 ALLOW FOR THE REQUIRED AIR GAP SEE FBC 1203.2
 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH
 SEPARATE SPACE BY VENTILATION OPENINGS PROTECTED
 AGAINST THE ENTRANCE OF RAIN AND SNOW. BLOCKING AND
 BRIDGING SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH
 THE MOVEMENT OF AIR. AN AIRSPACE OF NOT LESS THAN 1
 INCH (25 MM) SHALL BE PROVIDED BETWEEN THE INSULATION
 AND THE ROOF SHEATHING.
 4) SOFFIT SCREEN VENT FOR ENCLOSED RAFTER SPACES SHOULD
 BE CONTINUOUS TO COMPLY WITH FBC 1203.2 VENTILATION
 REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH
 SEPARATE SPACE BY VENTILATION OPENINGS PROTECTED
 AGAINST THE ENTRANCE OF RAIN AND SNOW. BLOCKING AND
 BRIDGING SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH
 THE MOVEMENT OF AIR.
 5) THE CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE
 REVISE THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN
 EFFECT (2020 FBC USING ASCE 7-16).
 6) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS
 AND ROOFING SYSTEMS.
 7) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE
 LISTED BY PERMIT NUMBER ON THE DRAWINGS.
 8) PLEASE SHOW THE WIND DESIGN CRITERIA USED PER FBC
 1603.1.4
 9) PLEASE SHOW THE STRAPPING FOR THE 2X10 JOIST TO THE
 2X8 BEAMS FBC 1604.8.1
 10) PLEASE ACKNOWLEDGE ON THE DRAWINGS THAT THE PARKING
 AREA WILL BE ON A SEPARATE PERMIT. WILL NEED TO SHOW
 ACCESSIBLE PARKING AND ACCESS AISLE TO COMPLY WITH FBC
 CHAPTER 5.
 11) PLEASE SHOW THE ACCESSIBLE RESTROOM DETAILS PER FBC
 ACCESSIBILITY CHAPTER 6 - SHOW GRAB BAR HEIGHTS,
 LENGTHS AND LOCATIONS, SHOW MIRROR HEIGHT TO THE
 REFLECTING SURFACE, SHOW PAPER DISPENSER HEIGHTS AND
 DISTANCE FROM WATER CLOSETS ETC..
 12) JOB COST SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - PLEASE REVISE THE BUILDING PERMIT
 APPLICATION SHOWING THE CORRECT JOB VALUE - FBC WPB
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-09-22 Cont ID  
Sent By jleahy Date 2021-09-22 Time 11:04 Rev Time 0.00
Received By jleahy Date 2021-09-22 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-31 Cont ID  
Sent By equinone Date 2021-03-31 Time 16:07 Rev Time 0.00
Received By equinone Date 2021-03-31 Time 16:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-24 Cont ID  
Sent By pleduc Date 2021-08-24 Time   Rev Time 0.00
Received By pleduc Date 2021-08-24 Time 10:42 Sent To  
Notes
2021-08-24 10:44:19FIRE PROVISO:
  
 FIRE INSPECTOR WILL VERIFY/CONFIMR INSTALLATION DURING
 FIRE INSPECTION FINAL.
  
  
 1) INSTALL AN EXIT SIGN OVER ONLY EXIT DOOR.
  
 PER NFPA 101, CH 38 NEW BUNISNESS OCCUPANCIES
  
 38.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 THERE ARE MULTIPLE DOORS IN THE AREA AND THE EXIT SHALL
 BE CLEARLY MARKED.
  
  
  
  
 2) PROVIDE AN FIRE EXTINGUISHER. MIN. 10LB ABC
  
 38.3.5 EXTINGUISHMENT REQUIREMENTS. PORTABLE FIRE
 EXTINGUISHERS
 SHALL BE PROVIDED IN EVERY BUSINESS OCCUPANCY IN
 ACCORDANCE WITH SECTION
 9.9.
  
  
 9.9* PORTABLE FIRE EXTINGUISHERS
 WHERE REQUIRED BY ANOTHER SECTION OF THIS CODE,
 PORTABLE FIRE EXTINGUISHERS
 SHALL BE SELECTED, INSTALLED, INSPECTED, AND MAINTAINED
 IN ACCORDANCE
 WITH NFPA 10.
  
 MIN. 10LB ABC IS REQUIRED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-25 Cont ID  
Sent By pleduc Date 2021-03-25 Time   Rev Time 0.00
Received By pleduc Date 2021-03-25 Time 11:45 Sent To  
Notes
2021-03-25 11:57:04FIRE PROVISO:
  
 FIRE INSPECTOR WILL VERIFY/CONFIMR INSTALLATION DURING
 FIRE INSPECTION FINAL.
  
  
 1) INSTALL AN EXIT SIGN OVER ONLY EXIT DOOR.
  
 PER NFPA 101, CH 38 NEW BUNISNESS OCCUPANCIES
  
 38.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 THERE ARE MULTIPLE DOORS IN THE AREA AND THE EXIT SHALL
 BE CLEARLY MARKED.
  
  
  
  
 2) PROVIDE AN FIRE EXTINGUISHER. MIN. 10LB ABC
  
 38.3.5 EXTINGUISHMENT REQUIREMENTS. PORTABLE FIRE
 EXTINGUISHERS
 SHALL BE PROVIDED IN EVERY BUSINESS OCCUPANCY IN
 ACCORDANCE WITH SECTION
 9.9.
  
  
 9.9* PORTABLE FIRE EXTINGUISHERS
 WHERE REQUIRED BY ANOTHER SECTION OF THIS CODE,
 PORTABLE FIRE EXTINGUISHERS
 SHALL BE SELECTED, INSTALLED, INSPECTED, AND MAINTAINED
 IN ACCORDANCE
 WITH NFPA 10.
  
 MIN. 10LB ABC IS REQUIRED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-22 Cont ID  
Sent By jleahy Date 2021-09-22 Time 11:04 Rev Time 0.00
Received By jleahy Date 2021-08-23 Time 06:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-04-08 Time   Rev Time 0.00
Received By cdecoeur Date 2021-03-24 Time 15:35 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-04-06 Cont ID  
Sent By rmcphers Date 2021-04-06 Time 12:55 Rev Time 0.00
Received By rmcphers Date 2021-04-06 Time 12:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-30 Cont ID  
Sent By medwards Date 2021-08-30 Time 07:13 Rev Time 0.00
Received By medwards Date 2021-08-30 Time 07:13 Sent To  
Notes
2021-08-30 07:13:491ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21031225
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 EACH USE OF SPACE IN THIS TENANT SPACE ACCORDING TO FBC
 M 403.3.1.1 AND TABLE 403.3.1.1 ON THE DRAWINGS.
  
 2) PLEASE SHOW HOW THE OUTDOOR AIR IS BEING SUPPLIED TO
 THIS AREA. FBC CHAPTER 4.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-05 Cont ID  
Sent By hmoser Date 2021-04-05 Time 15:24 Rev Time 0.00
Received By hmoser Date 2021-04-05 Time 14:05 Sent To  
Notes
2021-04-05 15:23:57PLAN DENIED
 1) HEAT LOAD REQUIRED SECTION C 403.2.1 FLORIDA ENERGY
 CODE 2020
 2) EQUIPMENT SCHEDULE REQUIRED ON PLAN SECTION 107 FBC
 3) SHOW LOCATION OF A/C CONDENSERS ON PLAN. SECTION 107
 FBC
 4) REFER TO SECTION 307.2.4.1 DUCTLESS MINI SPLIT
 SYSTEM TRAPS 2020 FBC (M)
 5) PROVIDE OUTDOOR AIR CALCULATION PER TABLE 403.3.1.1
 MINIMUM VENTILATION RATES
 2020FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-09-13 Cont ID  
Sent By ccole Date 2021-09-13 Time 11:53 Rev Time 0.00
Received By ccole Date 2021-09-13 Time 10:59 Sent To  
Notes
2021-09-13 11:55:502ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21031225
 9/13/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAPS FOR FURTHER CLARIFICATION.
  
 1) FAILED A, B, & C. NO PLUMBING DRAWINGS PROVIDED.
 SHEET A-1: PROVIDE PLUMBING PLANS FOR THE ALTERED
 TOILET ROOM IN COMPLIANCE WITH SECTIONS 107.2.1 AND
 107.3.5.3.1 WPB, AND FBC- 2020 PLUMBING. PROVIDE THE
 FOLLOWING LIST OF ITEMS:
  
 A) SANITARY DRAINAGE AND WATER RISER DRAWINGS.
  
 B) PLUMBING FLOOR PLAN LAYOUT DRAWING.
  
 C) PLUMBING FIXTURE SCHEDULE.
  
 3) FAILED ALL ITEMS BELOW EXCEPT C WHICH WAS REMOVED
 FROM THE COMMENT LIST. A-1: THE CURRENT TOILET ROOM
 DESIGN IS INCOMPLETE AND NOT IN COMPLIANCE WITH THE
 FBC- 2020 ACCESSIBILITY CODE. REFER TO SECTIONS 202.3,
 213.1, AND 213.3.1 FBC ACC AND PROVIDE ENLARGED TOILET
 ROOM DRAWINGS SHOWING COMPLIANCE WITH THE FOLLOWING
 ITEMS- FBC ACC:
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
  
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
  
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
  
 E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
  
 F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3.
  
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
  
 H) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION
 604.6.
  
 I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
  
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2.
  
 IT APPEARS THAT THE EXISTING WINDOWS BY THE RESTROOM
 WOULD HAVE TO BE REMOVED IN ORDER TO MEET COMPLIANCE
 WITH THE FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By ccole Date 2021-04-08 Time 12:51 Rev Time 0.00
Received By ccole Date 2021-04-08 Time 11:59 Sent To  
Notes
2021-04-08 12:52:111ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21031225
 4/8/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1: PROVIDE PLUMBING PLANS FOR THE ALTERED
 TOILET ROOM IN COMPLIANCE WITH SECTIONS 107.2.1 AND
 107.3.5.3.1 WPB, AND FBC- 2020 PLUMBING. PROVIDE THE
 FOLLOWING LIST OF ITEMS:
  
 A) SANITARY DRAINAGE AND WATER RISER DRAWINGS.
  
 B) PLUMBING FLOOR PLAN LAYOUT DRAWING.
  
 C) PLUMBING FIXTURE SCHEDULE.
  
 2) A-1: THE PROPOSED PROJECT SHALL BE IN COMPLIANCE
 WITH THE FBC-2020 EXISTING BUILDING CODE. PLEASE REFER
 TO SECTION 301.1 AND INDICATE WHICH COMPLIANCE METHOD
 WILL BE USED- PRESCRIPTIVE, WORK AREA, OR PERFORMANCE.
 A COMPLETE REVIEW CANNOT BE COMPLETED UNTIL A METHOD IS
 CHOSEN AND PLANS ARE REVISED IN ACCORDANCE WITH THE
 COMPLIANCE METHOD.
  
 3) A-1: THE CURRENT TOILET ROOM DESIGN IS INCOMPLETE
 AND NOT IN COMPLIANCE WITH THE FBC- 2020 ACCESSIBILITY
 CODE. REFER TO SECTIONS 202.3, 213.1, AND 213.3.1 FBC
 ACC AND PROVIDE ENLARGED TOILET ROOM DRAWINGS SHOWING
 COMPLIANCE WITH THE FOLLOWING ITEMS- FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
 F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 H) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION
 604.6.
 I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2.
  
 4) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-09-17 Cont ID  
Sent By rmcphers Date 2021-09-17 Time 14:21 Rev Time 0.00
Received By rmcphers Date 2021-09-17 Time 14:21 Sent To  
Notes
2021-09-17 14:21:41SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-04-06 Cont ID  
Sent By rmcphers Date 2021-04-06 Time 12:56 Rev Time 0.00
Received By rmcphers Date 2021-04-06 Time 12:56 Sent To  
Notes
2021-04-06 12:56:49SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-09-17 Cont ID  
Sent By rmcphers Date 2021-09-17 Time 14:22 Rev Time 0.00
Received By rmcphers Date 2021-09-17 Time 14:22 Sent To  
Notes
2021-09-17 14:26:13SIGNATURE REVIEW
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 DRAWINGS LABELED "002 A-1 ONE STORY OFFICE REMODLE.PDF
 V2 " DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-29 Cont ID  
Sent By medwards Date 2021-03-29 Time 05:58 Rev Time 0.00
Received By medwards Date 2021-03-29 Time 05:57 Sent To  
Notes
2021-03-29 05:59:17ORIGINAL SIGNED AND SEALED PAPER DRAWING ROUTED TO
 STORAGE. ME

Review Stop Z ZONING
Rev No 2 Status F Date 2021-08-31 Cont ID  
Sent By ckimmerl Date 2021-08-31 Time 16:46 Rev Time 0.00
Received By ckimmerl Date 2021-08-31 Time 16:46 Sent To  
Notes
2021-08-31 16:45:46- PERMIT VALUE EXCEEDS 50 PERCENT OF THE IMPROVEMENT
 VALUE ON THE PROPERTY, REQUIRES A SEPARATE LANDSCAPE
 PLAN.
  
 - REQUIRES CLARIFICATION ON THE SOUTHERN CURB-CUT ALONG
 8TH STREET, IS THIS BEING REMOVED? THE PROPOSED
 ADA/HANDICAPPED WALKWAY AND PARKING SPACE IS IN
 CONFLICT WITH THIS DRIVE ACCESS AND CURB CUT. ADA
 PARKING SPACE ALSO REQUIRES 5-FOOT LANDSCAPE BUFFER
 ALONG 8TH AND WESTERN EDGE OF PROPERTY.
  
 - SIZE AND LOCATION OF SPACES FOR THE DISABLED. PARKING
 SPACES FOR THE DISABLED SHALL BE DESIGNED AS REQUIRED
 BY THE FOLLOWING: ALL SPACES SHALL HAVE ACCESS TO A
 CURB RAMP OR CURB CUT, WHEN NECESSARY, TO ALLOW
 ENTRANCE TO THE BUILDING SERVED. SPACES SHALL BE
 LOCATED SO THAT USERS ARE NOT COMPELLED TO WALK OR
 OTHERWISE MOVE BEHIND PARKED VEHICLES, EXCLUDING OTHER
 VEHICLES PARKED IN ADJACENT PARKING SPACES FOR THE
 DISABLED. DIAGONAL OR PERPENDICULAR PARKING SPACES
 SHALL BE A MINIMUM OF 12 FEET WIDE AND 18 FEET LONG.
 EACH DISABLED PARKING SPACE SHALL BE PROMINENTLY
 OUTLINED WITH PAINT AND POSTED WITH A PERMANENT SIGN OF
 COLOR AND DESIGN APPROVED BY THE STATE DEPARTMENT OF
 TRANSPORTATION. THE SIGN SHALL CONTAIN THE
 INTERNATIONALLY ACCEPTED WHEELCHAIR SYMBOL AND THE
 CAPTION "PARKING BY DISABLED PERMIT ONLY."
  
 - 5-FOOT LANDCAPE BUFFER REQUIRED ALONG THE PROPOSED
 WESTERN EMPLOYEE PARKING SPACES. SCREENING PARKING FROM
 NEIGHBORING RESIDENTIAL USES WITH 36 INCH HEDGES AND
 SHADE TREES PLANTED AT 30 FT INTERVALS.
  
 - NORTHERN PORTION OF PROPERTY ADJACENT TO ALLEYWAY
 REQUIRES ADDITIONAL LANDSCAPE SCREENING, PLEASE INCLUDE
 ADDITIONAL SHADE TREE AT NORTHEASTERN CORNER OF
 PROPERTY (ALLEY AND TAMARIND).
  
 - STAFF RECOMMENDS SPEAKING WITH GENIA BAKER OF THE
 COMMUNITY REDEVELOPMENT AGENCY (CRA) TO FURTHER DISCUSS
 IMPROVEMENTS TO THE SITE. HER CONTACT IS AS FOLLOWS:
 [email protected] 822-1550

Review Stop Z ZONING
Rev No 1 Status F Date 2021-04-01 Cont ID  
Sent By aaponte Date 2021-04-01 Time 17:31 Rev Time 0.00
Received By aaponte Date 2021-04-01 Time 17:31 Sent To  
Notes
2021-04-01 17:40:331. PLEASE PROVIDE A RECENT SURVEY OF THE SITE.
 2. PROPOSED IMPROVEMENTS EXCEED 50% OF THE IMPROVEMENT
 VALUE OF THE EXISTING BUILDING, THEREFORE UPGRADES TO
 THE LANDSCAPE WOULD BE REQUIRED.
 3. PLEASE SUBMIT A SITE PLAN INDICATING THE PARKING
 DIMENSIONS, DRIVE AISLE DIMENSIONS AND LANDSCAPE
 DIMENSIONS.
 4. A 5 FEET LANDSCAPE BUFFER WOULD BE REQUIRED AROUND
 THE PARKING LOT, AND TREES SHALL BE PLANTED ON THE
 BUFFER EVERY 30 FEET.
 5. PLEASE INDICATE THE PROPERTY LINE IN THE SITE PLAN.
 PLEASE CONTACT ANA MARIA APONTE AT 561-822-1439 TO
 FURTHER DISCUSSED COMPLIANCE WITH THE ZONING CODE.