Plan Review Stops For Permit 21031225 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
F |
Date |
2021-09-17 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-09-17 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-09-17 |
Time |
14:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2021-04-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-06 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-06 |
Time |
11:07 |
Sent To |
|
|
Notes |
2021-04-06 11:09:19 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-09-17 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-09-17 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-09-17 |
Time |
14:03 |
Sent To |
|
|
Notes |
2021-09-17 14:20:56 | COMMERCIAL ALTERATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW THE ROOF SLOPE TO COMPLY WITH FBC | | 1507.10.1 SLOPE. | | BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF NOT LESS | | THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL | | (2-PERCENT SLOPE) FOR DRAINAGE, EXCEPT FOR COAL-TAR | | BUILT-UP ROOFS THAT SHALL HAVE A DESIGN SLOPE OF NOT | | LESS THAN ONE-EIGHTH UNIT VERTICAL IN 12 UNITS | | HORIZONTAL (1-PERCENT SLOPE). | | | | 2) DOORS MARKED (E) = A 32" DOOR DOES NOT PROVIDE THE | | CORRECT OPENING WIDTH FBC ACCESSIBILITY 404.2.3 CLEAR | | WIDTH. | | DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES | | (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH | | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF | | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. | | FBC ACCESSIBILITY 203.9 EMPLOYEE WORK AREAS. | | SPACES AND ELEMENTS WITHIN EMPLOYEE WORK AREAS SHALL | | ONLY BE REQUIRED TO COMPLY WITH 206.2.8, 207.1, AND | | 215.3 AND SHALL BE DESIGNED AND CONSTRUCTED SO THAT | | INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER, AND | | EXIT THE EMPLOYEE WORK AREA. | | | | 3) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS | | AND ROOFING SYSTEMS. | | | | 4) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE | | LISTED BY PERMIT NUMBER ON THE DRAWINGS. | | | | 5) PLEASE SHOW THE WIND DESIGN CRITERIA USED (WIND | | SPEED, RISK CATEGORY, EXPOSURE ETC.) PER FBC 1603.1.4 | | | | 6) PLEASE SHOW ACCESSIBLE PARKING AND ACCESS AISLE | | DIMENSIONS TO COMPLY WITH FBC ACCESSIBILITY 502 | | | | 7) PLEASE SHOW THE ACCESSIBLE RESTROOM DETAILS PER FBC | | ACCESSIBILITY CHAPTER 6 - SHOW GRAB BAR HEIGHTS, | | LENGTHS AND LOCATIONS, SHOW MIRROR HEIGHT TO THE | | REFLECTING SURFACE, SHOW PAPER DISPENSER HEIGHTS AND | | DISTANCE FROM WATER CLOSETS ETC.. | | | | 8) JOB COST NEEDS TO BE SHOWN ON THE REVISED BUILDING | | PERMIT APPLICATION. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-04-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-06 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-06 |
Time |
11:09 |
Sent To |
|
|
Notes |
2021-04-06 11:27:22 | COMMERCIAL ALTERATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW THE ROOF SLOPE TO COMPLY WITH FBC | | 1507.10.1 | | 2) CANNOT SET ROOF TOP EQUIPMENT ON EMBEDDED 4X4'S - | | PLEASE SHOW MECHANICAL EQUIPMENT ON THE ROOF TO COMPLY | | WITH FBC 1510.10 MECHANICAL UNITS. | | ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS | | RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF | | SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE | | UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM | | CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10. | | 3) ADDING R30 BAT INSULATION IN 2X10 JOIST WILL NOT | | ALLOW FOR THE REQUIRED AIR GAP SEE FBC 1203.2 | | VENTILATION REQUIRED. | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH | | SEPARATE SPACE BY VENTILATION OPENINGS PROTECTED | | AGAINST THE ENTRANCE OF RAIN AND SNOW. BLOCKING AND | | BRIDGING SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH | | THE MOVEMENT OF AIR. AN AIRSPACE OF NOT LESS THAN 1 | | INCH (25 MM) SHALL BE PROVIDED BETWEEN THE INSULATION | | AND THE ROOF SHEATHING. | | 4) SOFFIT SCREEN VENT FOR ENCLOSED RAFTER SPACES SHOULD | | BE CONTINUOUS TO COMPLY WITH FBC 1203.2 VENTILATION | | REQUIRED. | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH | | SEPARATE SPACE BY VENTILATION OPENINGS PROTECTED | | AGAINST THE ENTRANCE OF RAIN AND SNOW. BLOCKING AND | | BRIDGING SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH | | THE MOVEMENT OF AIR. | | 5) THE CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE | | REVISE THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN | | EFFECT (2020 FBC USING ASCE 7-16). | | 6) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS | | AND ROOFING SYSTEMS. | | 7) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE | | LISTED BY PERMIT NUMBER ON THE DRAWINGS. | | 8) PLEASE SHOW THE WIND DESIGN CRITERIA USED PER FBC | | 1603.1.4 | | 9) PLEASE SHOW THE STRAPPING FOR THE 2X10 JOIST TO THE | | 2X8 BEAMS FBC 1604.8.1 | | 10) PLEASE ACKNOWLEDGE ON THE DRAWINGS THAT THE PARKING | | AREA WILL BE ON A SEPARATE PERMIT. WILL NEED TO SHOW | | ACCESSIBLE PARKING AND ACCESS AISLE TO COMPLY WITH FBC | | CHAPTER 5. | | 11) PLEASE SHOW THE ACCESSIBLE RESTROOM DETAILS PER FBC | | ACCESSIBILITY CHAPTER 6 - SHOW GRAB BAR HEIGHTS, | | LENGTHS AND LOCATIONS, SHOW MIRROR HEIGHT TO THE | | REFLECTING SURFACE, SHOW PAPER DISPENSER HEIGHTS AND | | DISTANCE FROM WATER CLOSETS ETC.. | | 12) JOB COST SHOWN ON THE BUILDING PERMIT APPLICATION | | APPEARS TO BE LOW - PLEASE REVISE THE BUILDING PERMIT | | APPLICATION SHOWING THE CORRECT JOB VALUE - FBC WPB | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION | | OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | DENIED, UNLESS THE APPLICANT CAN SHOW | | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED | | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE | | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL | | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING | | ONLY LAND VALUE. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-09-22 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-09-22 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-09-22 |
Time |
11:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-03-31 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2021-03-31 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2021-03-31 |
Time |
16:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2021-08-24 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-08-24 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-08-24 |
Time |
10:42 |
Sent To |
|
|
Notes |
2021-08-24 10:44:19 | FIRE PROVISO: | | | | FIRE INSPECTOR WILL VERIFY/CONFIMR INSTALLATION DURING | | FIRE INSPECTION FINAL. | | | | | | 1) INSTALL AN EXIT SIGN OVER ONLY EXIT DOOR. | | | | PER NFPA 101, CH 38 NEW BUNISNESS OCCUPANCIES | | | | 38.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS | | SHALL HAVE | | SIGNS IN ACCORDANCE WITH SECTION 7.10. | | | | 7.10.1.2 EXITS. | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | THAT OBVIOUSLY | | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED | | BY AN APPROVED | | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT | | ACCESS. | | | | THERE ARE MULTIPLE DOORS IN THE AREA AND THE EXIT SHALL | | BE CLEARLY MARKED. | | | | | | | | | | 2) PROVIDE AN FIRE EXTINGUISHER. MIN. 10LB ABC | | | | 38.3.5 EXTINGUISHMENT REQUIREMENTS. PORTABLE FIRE | | EXTINGUISHERS | | SHALL BE PROVIDED IN EVERY BUSINESS OCCUPANCY IN | | ACCORDANCE WITH SECTION | | 9.9. | | | | | | 9.9* PORTABLE FIRE EXTINGUISHERS | | WHERE REQUIRED BY ANOTHER SECTION OF THIS CODE, | | PORTABLE FIRE EXTINGUISHERS | | SHALL BE SELECTED, INSTALLED, INSPECTED, AND MAINTAINED | | IN ACCORDANCE | | WITH NFPA 10. | | | | MIN. 10LB ABC IS REQUIRED. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2021-03-25 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-03-25 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-03-25 |
Time |
11:45 |
Sent To |
|
|
Notes |
2021-03-25 11:57:04 | FIRE PROVISO: | | | | FIRE INSPECTOR WILL VERIFY/CONFIMR INSTALLATION DURING | | FIRE INSPECTION FINAL. | | | | | | 1) INSTALL AN EXIT SIGN OVER ONLY EXIT DOOR. | | | | PER NFPA 101, CH 38 NEW BUNISNESS OCCUPANCIES | | | | 38.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS | | SHALL HAVE | | SIGNS IN ACCORDANCE WITH SECTION 7.10. | | | | 7.10.1.2 EXITS. | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | THAT OBVIOUSLY | | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED | | BY AN APPROVED | | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT | | ACCESS. | | | | THERE ARE MULTIPLE DOORS IN THE AREA AND THE EXIT SHALL | | BE CLEARLY MARKED. | | | | | | | | | | 2) PROVIDE AN FIRE EXTINGUISHER. MIN. 10LB ABC | | | | 38.3.5 EXTINGUISHMENT REQUIREMENTS. PORTABLE FIRE | | EXTINGUISHERS | | SHALL BE PROVIDED IN EVERY BUSINESS OCCUPANCY IN | | ACCORDANCE WITH SECTION | | 9.9. | | | | | | 9.9* PORTABLE FIRE EXTINGUISHERS | | WHERE REQUIRED BY ANOTHER SECTION OF THIS CODE, | | PORTABLE FIRE EXTINGUISHERS | | SHALL BE SELECTED, INSTALLED, INSPECTED, AND MAINTAINED | | IN ACCORDANCE | | WITH NFPA 10. | | | | MIN. 10LB ABC IS REQUIRED. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-09-22 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-09-22 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-08-23 |
Time |
06:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2021-04-08 |
Time |
|
Rev Time |
0.00 |
Received By |
cdecoeur |
Date |
2021-03-24 |
Time |
15:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2021-04-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-06 |
Time |
12:55 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-06 |
Time |
12:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2021-08-30 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-08-30 |
Time |
07:13 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-08-30 |
Time |
07:13 |
Sent To |
|
|
Notes |
2021-08-30 07:13:49 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21031225 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON | | EACH USE OF SPACE IN THIS TENANT SPACE ACCORDING TO FBC | | M 403.3.1.1 AND TABLE 403.3.1.1 ON THE DRAWINGS. | | | | 2) PLEASE SHOW HOW THE OUTDOOR AIR IS BEING SUPPLIED TO | | THIS AREA. FBC CHAPTER 4. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2021-04-05 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2021-04-05 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2021-04-05 |
Time |
14:05 |
Sent To |
|
|
Notes |
2021-04-05 15:23:57 | PLAN DENIED | | 1) HEAT LOAD REQUIRED SECTION C 403.2.1 FLORIDA ENERGY | | CODE 2020 | | 2) EQUIPMENT SCHEDULE REQUIRED ON PLAN SECTION 107 FBC | | 3) SHOW LOCATION OF A/C CONDENSERS ON PLAN. SECTION 107 | | FBC | | 4) REFER TO SECTION 307.2.4.1 DUCTLESS MINI SPLIT | | SYSTEM TRAPS 2020 FBC (M) | | 5) PROVIDE OUTDOOR AIR CALCULATION PER TABLE 403.3.1.1 | | MINIMUM VENTILATION RATES | | 2020FBC (M) | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2021-09-13 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-09-13 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-09-13 |
Time |
10:59 |
Sent To |
|
|
Notes |
2021-09-13 11:55:50 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT- 21031225 | | 9/13/2021 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE | | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN | | CAPS FOR FURTHER CLARIFICATION. | | | | 1) FAILED A, B, & C. NO PLUMBING DRAWINGS PROVIDED. | | SHEET A-1: PROVIDE PLUMBING PLANS FOR THE ALTERED | | TOILET ROOM IN COMPLIANCE WITH SECTIONS 107.2.1 AND | | 107.3.5.3.1 WPB, AND FBC- 2020 PLUMBING. PROVIDE THE | | FOLLOWING LIST OF ITEMS: | | | | A) SANITARY DRAINAGE AND WATER RISER DRAWINGS. | | | | B) PLUMBING FLOOR PLAN LAYOUT DRAWING. | | | | C) PLUMBING FIXTURE SCHEDULE. | | | | 3) FAILED ALL ITEMS BELOW EXCEPT C WHICH WAS REMOVED | | FROM THE COMMENT LIST. A-1: THE CURRENT TOILET ROOM | | DESIGN IS INCOMPLETE AND NOT IN COMPLIANCE WITH THE | | FBC- 2020 ACCESSIBILITY CODE. REFER TO SECTIONS 202.3, | | 213.1, AND 213.3.1 FBC ACC AND PROVIDE ENLARGED TOILET | | ROOM DRAWINGS SHOWING COMPLIANCE WITH THE FOLLOWING | | ITEMS- FBC ACC: | | | | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | WATER CLOSET- SECTION 604.3. | | | | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | LAVATORY- SECTION 606.2. | | | | D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- | | SECTION 604.2. | | | | E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED | | FLOOR- SECTION 604.4. | | | | F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE | | REFLECTIVE SURFACE- SECTION 603.3. | | | | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, | | FIGURES 604. | | | | H) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION | | 604.6. | | | | I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED | | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND | | FIGURE 604.7. | | | | K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION | | 606.2. | | | | IT APPEARS THAT THE EXISTING WINDOWS BY THE RESTROOM | | WOULD HAVE TO BE REMOVED IN ORDER TO MEET COMPLIANCE | | WITH THE FBC ACC. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-04-08 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-04-08 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-04-08 |
Time |
11:59 |
Sent To |
|
|
Notes |
2021-04-08 12:52:11 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 21031225 | | 4/8/2021 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET A-1: PROVIDE PLUMBING PLANS FOR THE ALTERED | | TOILET ROOM IN COMPLIANCE WITH SECTIONS 107.2.1 AND | | 107.3.5.3.1 WPB, AND FBC- 2020 PLUMBING. PROVIDE THE | | FOLLOWING LIST OF ITEMS: | | | | A) SANITARY DRAINAGE AND WATER RISER DRAWINGS. | | | | B) PLUMBING FLOOR PLAN LAYOUT DRAWING. | | | | C) PLUMBING FIXTURE SCHEDULE. | | | | 2) A-1: THE PROPOSED PROJECT SHALL BE IN COMPLIANCE | | WITH THE FBC-2020 EXISTING BUILDING CODE. PLEASE REFER | | TO SECTION 301.1 AND INDICATE WHICH COMPLIANCE METHOD | | WILL BE USED- PRESCRIPTIVE, WORK AREA, OR PERFORMANCE. | | A COMPLETE REVIEW CANNOT BE COMPLETED UNTIL A METHOD IS | | CHOSEN AND PLANS ARE REVISED IN ACCORDANCE WITH THE | | COMPLIANCE METHOD. | | | | 3) A-1: THE CURRENT TOILET ROOM DESIGN IS INCOMPLETE | | AND NOT IN COMPLIANCE WITH THE FBC- 2020 ACCESSIBILITY | | CODE. REFER TO SECTIONS 202.3, 213.1, AND 213.3.1 FBC | | ACC AND PROVIDE ENLARGED TOILET ROOM DRAWINGS SHOWING | | COMPLIANCE WITH THE FOLLOWING ITEMS- FBC ACC: | | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | WATER CLOSET- SECTION 604.3. | | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | LAVATORY- SECTION 606.2. | | C) TURNING SPACE DIAMETER- SECTION 304.3. | | D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- | | SECTION 604.2. | | E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED | | FLOOR- SECTION 604.4. | | F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE | | REFLECTIVE SURFACE- SECTION 603.3 | | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, | | FIGURES 604. | | H) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION | | 604.6. | | I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED | | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND | | FIGURE 604.7. | | K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION | | 606.2. | | | | 4) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2021-09-17 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-09-17 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-09-17 |
Time |
14:21 |
Sent To |
|
|
Notes |
2021-09-17 14:21:41 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-04-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-06 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-06 |
Time |
12:56 |
Sent To |
|
|
Notes |
2021-04-06 12:56:49 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-09-17 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-09-17 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-09-17 |
Time |
14:22 |
Sent To |
|
|
Notes |
2021-09-17 14:26:13 | SIGNATURE REVIEW | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | DRAWINGS LABELED "002 A-1 ONE STORY OFFICE REMODLE.PDF | | V2 " DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | DIVISION AT THE CITY HALL. | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2021-03-29 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-29 |
Time |
05:58 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-29 |
Time |
05:57 |
Sent To |
|
|
Notes |
2021-03-29 05:59:17 | ORIGINAL SIGNED AND SEALED PAPER DRAWING ROUTED TO | | STORAGE. ME |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-08-31 |
|
|
Cont ID |
|
Sent By |
ckimmerl |
Date |
2021-08-31 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
ckimmerl |
Date |
2021-08-31 |
Time |
16:46 |
Sent To |
|
|
Notes |
2021-08-31 16:45:46 | - PERMIT VALUE EXCEEDS 50 PERCENT OF THE IMPROVEMENT | | VALUE ON THE PROPERTY, REQUIRES A SEPARATE LANDSCAPE | | PLAN. | | | | - REQUIRES CLARIFICATION ON THE SOUTHERN CURB-CUT ALONG | | 8TH STREET, IS THIS BEING REMOVED? THE PROPOSED | | ADA/HANDICAPPED WALKWAY AND PARKING SPACE IS IN | | CONFLICT WITH THIS DRIVE ACCESS AND CURB CUT. ADA | | PARKING SPACE ALSO REQUIRES 5-FOOT LANDSCAPE BUFFER | | ALONG 8TH AND WESTERN EDGE OF PROPERTY. | | | | - SIZE AND LOCATION OF SPACES FOR THE DISABLED. PARKING | | SPACES FOR THE DISABLED SHALL BE DESIGNED AS REQUIRED | | BY THE FOLLOWING: ALL SPACES SHALL HAVE ACCESS TO A | | CURB RAMP OR CURB CUT, WHEN NECESSARY, TO ALLOW | | ENTRANCE TO THE BUILDING SERVED. SPACES SHALL BE | | LOCATED SO THAT USERS ARE NOT COMPELLED TO WALK OR | | OTHERWISE MOVE BEHIND PARKED VEHICLES, EXCLUDING OTHER | | VEHICLES PARKED IN ADJACENT PARKING SPACES FOR THE | | DISABLED. DIAGONAL OR PERPENDICULAR PARKING SPACES | | SHALL BE A MINIMUM OF 12 FEET WIDE AND 18 FEET LONG. | | EACH DISABLED PARKING SPACE SHALL BE PROMINENTLY | | OUTLINED WITH PAINT AND POSTED WITH A PERMANENT SIGN OF | | COLOR AND DESIGN APPROVED BY THE STATE DEPARTMENT OF | | TRANSPORTATION. THE SIGN SHALL CONTAIN THE | | INTERNATIONALLY ACCEPTED WHEELCHAIR SYMBOL AND THE | | CAPTION "PARKING BY DISABLED PERMIT ONLY." | | | | - 5-FOOT LANDCAPE BUFFER REQUIRED ALONG THE PROPOSED | | WESTERN EMPLOYEE PARKING SPACES. SCREENING PARKING FROM | | NEIGHBORING RESIDENTIAL USES WITH 36 INCH HEDGES AND | | SHADE TREES PLANTED AT 30 FT INTERVALS. | | | | - NORTHERN PORTION OF PROPERTY ADJACENT TO ALLEYWAY | | REQUIRES ADDITIONAL LANDSCAPE SCREENING, PLEASE INCLUDE | | ADDITIONAL SHADE TREE AT NORTHEASTERN CORNER OF | | PROPERTY (ALLEY AND TAMARIND). | | | | - STAFF RECOMMENDS SPEAKING WITH GENIA BAKER OF THE | | COMMUNITY REDEVELOPMENT AGENCY (CRA) TO FURTHER DISCUSS | | IMPROVEMENTS TO THE SITE. HER CONTACT IS AS FOLLOWS: | | [email protected] 822-1550 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2021-04-01 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2021-04-01 |
Time |
17:31 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2021-04-01 |
Time |
17:31 |
Sent To |
|
|
Notes |
2021-04-01 17:40:33 | 1. PLEASE PROVIDE A RECENT SURVEY OF THE SITE. | | 2. PROPOSED IMPROVEMENTS EXCEED 50% OF THE IMPROVEMENT | | VALUE OF THE EXISTING BUILDING, THEREFORE UPGRADES TO | | THE LANDSCAPE WOULD BE REQUIRED. | | 3. PLEASE SUBMIT A SITE PLAN INDICATING THE PARKING | | DIMENSIONS, DRIVE AISLE DIMENSIONS AND LANDSCAPE | | DIMENSIONS. | | 4. A 5 FEET LANDSCAPE BUFFER WOULD BE REQUIRED AROUND | | THE PARKING LOT, AND TREES SHALL BE PLANTED ON THE | | BUFFER EVERY 30 FEET. | | 5. PLEASE INDICATE THE PROPERTY LINE IN THE SITE PLAN. | | PLEASE CONTACT ANA MARIA APONTE AT 561-822-1439 TO | | FURTHER DISCUSSED COMPLIANCE WITH THE ZONING CODE. |
|
|