Plan Review Details - Permit 21031200
Plan Review Stops For Permit 21031200
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-13 Cont ID  
Sent By rmcphers Date 2021-04-13 Time 09:58 Rev Time 0.00
Received By rmcphers Date 2021-04-13 Time 09:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By mcphers Date 2021-04-07 Time 09:39 Rev Time 0.00
Received By rmcphers Date 2021-04-07 Time 09:39 Sent To  
Notes
2021-04-07 09:52:35REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING ADDED FOR EXTERIOR WALL REPAIR - PLEASE
 PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF THE
 EXTERIOR WALL REPAIR.
 2) DRAWING ADDED FOR THE EXTERIOR WALL REPAIR NEEDS TO
 BE THE ORIGINAL SIGNED AND SEALED COPY FROM THE
 ARCHITECT - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE
 ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN
 REVIEW. DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-20 Cont ID  
Sent By jleahy Date 2021-04-20 Time 16:10 Rev Time 0.00
Received By jleahy Date 2021-04-20 Time 16:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-31 Cont ID  
Sent By jleahy Date 2021-03-31 Time 16:22 Rev Time 0.00
Received By jleahy Date 2021-03-31 Time 16:17 Sent To  
Notes
2021-03-31 16:27:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC PLANS FOR WORK TO BE DONE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aoliver Date 2021-04-09 Time 10:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-07 Cont ID  
Sent By rmcphers Date 2021-04-07 Time 09:55 Rev Time 0.00
Received By rmcphers Date 2021-03-24 Time 18:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-04-01 Cont ID  
Sent By lcrespo Date 2021-04-01 Time 16:24 Rev Time 0.00
Received By lcrespo Date 2021-04-01 Time 10:32 Sent To  
Notes
2021-04-01 16:24:4304/01/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-13 Cont ID  
Sent By rmcphers Date 2021-04-13 Time 09:58 Rev Time 0.00
Received By rmcphers Date 2021-04-13 Time 09:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By rmcphers Date 2021-04-07 Time 09:52 Rev Time 0.00
Received By rmcphers Date 2021-04-07 Time 09:52 Sent To  
Notes
2021-04-07 09:53:16SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL