Plan Review Details - Permit 21031164
Plan Review Stops For Permit 21031164
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-23 Cont ID  
Sent By rmcdouga Date 2021-06-23 Time 14:56 Rev Time 0.00
Received By rmcdouga Date 2021-06-23 Time 14:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-26 Cont ID  
Sent By rmcdouga Date 2021-04-26 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2021-04-26 Time 11:08 Sent To  
Notes
2021-04-26 11:25:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE 10' FROM ANY
 OPENINGS INTO THE BUILDING. R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2) SUBMIT GENERATOR PAD AND GENERATOR TO PAD ANCHORING
 DETAILS. IF A PRE-FABRICATED GENERATOR PAD IS TO BE
 USED, SUBMIT PRODUCT APPROVALS OR SITE SPECIFIC
 ENGINEERING. FBC 107.2.1
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-21 Cont ID  
Sent By fgiaquin Date 2021-04-21 Time 20:49 Rev Time 0.00
Received By fgiaquin Date 2021-04-21 Time 20:16 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-06-15 Cont ID  
Sent By ccole Date 2021-06-15 Time 07:40 Rev Time 0.00
Received By ccole Date 2021-06-15 Time 07:40 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By ccole Date 2021-04-21 Time 10:55 Rev Time 0.00
Received By ccole Date 2021-04-21 Time 07:24 Sent To  
Notes
2021-04-21 10:55:361ST REVIEW FBC-2020 RES.
 PERMIT- 21031164
 4/21/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 NFPA 58
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULT: DENIED- REVIEW COMMENTS BELOW.
  
 1) INSTALLATION OF THE LP TANK UNDER THE DRIVEWAY WILL
 REQUIRE SUBMITTAL OF SPECIFIC INSTALLATION GUIDELINES
 FROM THE TANK MANUFACTURER OTHERWISE THE TANK SHALL BE
 RELOCATED- SECTION G2408.1 FBC RES. THE GUIDELINES
 SHALL INDICATE HOW THE TANK LOCATED UNDER THE DRIVEWAY
 WILL BE PROTECTED FROM VEHICULAR DAMAGE AND INCLUDE
 SPECIFICATIONS AND INSTRUCTIONS FOR INSTALLATION OF AN
 IMPACT AND LOAD RESISTANT, LISTED AND LABELED TANK LID
 COVER- SECTION 6.8.6.1 (E) AND SECTION G2408.1 FBC RES.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 3) PROVIDE A UG LP TANK INSTALLATION AND HOLD-DOWN
 DETAIL SHOWING HOW THE TANK WILL BE ANCHORED TO PREVENT
 FLOTATION, COLLAPSE, OR LATERAL MOVEMENT. PLEASE
 INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE
 BURIAL DEPTH, ANCHORING BASE MATERIAL, AND THE TYPES,
 SIZES, AND NUMBERS OF ANCHORS, CABLES OR STRAPS, AND
 THE TYPE OF PROTECTIVE SLEEVES FOR THE CABLES OR
 STRAPS- SECTION 6.8.6.1 NFPA-58. PLEASE NOTE THE TANK
 SHALL BE INSTALLED A MINIMUM OF 18 IN. BELOW GRADE.
  
 4) THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION
 BY INSTALLATION OF A CATHODIC PROTECTION SYSTEM
 CONSISTING OF A SACRIFICIAL ANODE OR AN IMPRESSED
 CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA
 58. INDICATE THE TYPE OF PROTECTION AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 6.17.1.
  
 5) GAS RISER:
 A) LIST THE MAKES AND MODELS OF THE REGULATORS AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS MARKED UP TO SHOW
 THE SELECTED MODELS, INLET AND OUTLET PRESSURES AND
 PIPE SIZES- SECTION 6.10.1 NFPA 58.
 B) CORRECT THE 360,000 BTU LOAD FOR THE 24 KW
 GENERATOR. THE SPECS SHOW 306,000 BTU LOAD- 6.11.2
 C) SHOW THE REQUIRED FLEX CONNECTOR AT THE GENERATOR
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 6.11.3.9
 D) LIST THE PIPE SIZING TABLES USED- SECTION 16.1 NFPA
 58 & SECTION G2413.4 FBC RES.
  
 6) SURVEY: CORRECT THE 5 FT. GENERATOR CLEARANCE
 DISTANCE TO OPENINGS INTO THE BUILDING. MINIMUM 10 FT.
 CLEARANCE IS REQUIRED- SECTION R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-23 Cont ID  
Sent By rmcdouga Date 2021-06-23 Time 14:56 Rev Time 0.00
Received By rmcdouga Date 2021-06-04 Time 09:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-11 Cont ID  
Sent By medwards Date 2021-05-11 Time 17:09 Rev Time 0.00
Received By medwards Date 2021-04-05 Time 16:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-06-14 Cont ID  
Sent By ccole Date 2021-06-14 Time 17:58 Rev Time 0.00
Received By ccole Date 2021-06-14 Time 17:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-21 Cont ID  
Sent By ccole Date 2021-04-21 Time 09:17 Rev Time 0.00
Received By ccole Date 2021-04-21 Time 07:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-23 Cont ID  
Sent By rmcdouga Date 2021-06-23 Time 14:55 Rev Time 0.00
Received By rmcdouga Date 2021-06-23 Time 14:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-26 Cont ID  
Sent By rmcdouga Date 2021-04-26 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2021-04-26 Time 11:08 Sent To  
Notes
2021-04-26 11:26:42SIGNATURE WILL BE REVIEWED WHEN GENERATOR PAD DRAWINGS
 ARE SUBMITTED.