Plan Review Details - Permit 21031163
Plan Review Stops For Permit 21031163
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-07 Cont ID  
Sent By rmcphers Date 2021-06-07 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2021-06-07 Time 13:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-28 Cont ID  
Sent By rmcdouga Date 2021-04-28 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2021-04-28 Time 09:29 Sent To  
Notes
2021-04-28 09:47:44PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A GENERATOR PAD DRAWING WITH ANCHORING
 DETAILS. IF A PREFABRICATED GENERATOR PAD IS TO BE
 USED, SUBMIT SIGNED AND SEALED PAD DRAWINGS FROM A
 FLORIDA LISENCED DESIGN PROFESSIONAL. FBC 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-29 Cont ID  
Sent By jleahy Date 2021-04-29 Time 13:14 Rev Time 0.00
Received By jleahy Date 2021-04-29 Time 12:31 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-06-07 Cont ID  
Sent By aborngra Date 2021-06-07 Time 14:29 Rev Time 0.00
Received By aborngra Date 2021-06-07 Time 14:29 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-05-04 Cont ID  
Sent By aborngra Date 2021-05-04 Time 10:54 Rev Time 0.00
Received By aborngra Date 2021-05-04 Time 10:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-07 Cont ID  
Sent By lmarchan Date 2021-06-07 Time 14:49 Rev Time 0.00
Received By lmarchan Date 2021-06-03 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-05 Cont ID  
Sent By cthroop Date 2021-05-05 Time 09:01 Rev Time 0.00
Received By cthroop Date 2021-04-05 Time 10:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-07 Cont ID  
Sent By rmcphers Date 2021-06-07 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2021-06-07 Time 13:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-28 Cont ID  
Sent By rmcdouga Date 2021-04-28 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2021-04-28 Time 09:29 Sent To  
Notes
2021-04-28 09:44:19SIGNATURE WILL BE REQUIRED IF PREFAB GENERATOR SLAB IS
 USED.

Review Stop Z ZONING
Rev No 2 Status P Date 2021-06-07 Cont ID  
Sent By aborngra Date 2021-06-07 Time 14:29 Rev Time 0.00
Received By aborngra Date 2021-06-07 Time 14:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-04 Cont ID  
Sent By kalexand Date 2021-05-04 Time 10:54 Rev Time 0.00
Received By aborngra Date 2021-05-04 Time 10:54 Sent To  
Notes
***NONE***