Plan Review Stops For Permit 21031115 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2021-08-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-08-23 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-08-23 |
Time |
14:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-04-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-04-07 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-04-07 |
Time |
10:58 |
Sent To |
|
|
Notes |
2021-04-07 11:00:22 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT GENERATOR SLAB DETAILS AND SPECIFY THE TYPE, | | SIZE AND NUMBER OF FASTENERS THAT WILL BE USED TO | | ANCHOR THE GENERATOR TO THE SLAB. IF A PREFABRICATED | | SLAB WILL BE USED SUBMIT PRODUCT APPROVALS OR SIGNED | | AND SEALED SITE SPECIFIC ENGINEERING. FBC 107.2.1 | | | | 2) THE GENERATOR IS LOCATED IN AN AE FLOOD ZONE, WHICH | | IS A SPECIAL FLOOD HAZARD AREA. THE GENERATOR IS | | REQUIRED TO BE LOCATED AT OR ABOVE THE ELEVATION OF THE | | LIVING AREA OF THE HOUSE. FBC-R322.1.6 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-08-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-08-18 |
Time |
06:41 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-08-18 |
Time |
06:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-03-25 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-03-25 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-03-25 |
Time |
14:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2021-09-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-09-27 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-09-27 |
Time |
12:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2021-08-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-08-27 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-08-27 |
Time |
13:20 |
Sent To |
|
|
Notes |
2021-08-27 13:28:05 | 2ND REVIEW FBC-2020 RES. | | PERMIT- 21031115 | | 8/27/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST | | REVIEW PRINTED BELOW STILL EXIST. PLEASE COMPLY. | | | | 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES | | THE NEW GAS PIPING TO THE GENERATOR, AND THE EXISTING | | GAS PIPING AND APPLIANCES AT THE RESIDENCE- SECTION | | G2412.3 & G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 | | FUEL GAS- THE RISER SHALL INDICATE: | | | | A) TYPE OF GAS- NATURAL OR LP. | | B) DELIVERY PRESSURE AT THE METER. | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | D) TYPES AND SIZES OF PIPING. | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | TO THE MOST REMOTE APPLIANCE OUTLET. | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | UNIONS. | | H) OUTLET PRESSURES AT REGULATORS. | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | K) PIPE SIZING TABLES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-04-08 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-04-08 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-04-08 |
Time |
08:15 |
Sent To |
|
|
Notes |
2021-04-08 09:02:31 | 1ST REVIEW FBC-2020 RES. | | PERMIT- 21031115 | | 4/8/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES | | THE NEW GAS PIPING TO THE GENERATOR, AND THE EXISTING | | GAS PIPING AND APPLIANCES AT THE RESIDENCE- SECTION | | G2412.3 & G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 | | FUEL GAS- THE RISER SHALL INDICATE: | | | | A) TYPE OF GAS- NATURAL OR LP. | | B) DELIVERY PRESSURE AT THE METER. | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | D) TYPES AND SIZES OF PIPING. | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | TO THE MOST REMOTE APPLIANCE OUTLET. | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | UNIONS. | | H) OUTLET PRESSURES AT REGULATORS. | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | K) PIPE SIZING TABLES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2021-09-27 |
Time |
|
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2021-09-16 |
Time |
07:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2021-08-27 |
Time |
|
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2021-08-16 |
Time |
06:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-04-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-22 |
Time |
08:41 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-03-23 |
Time |
13:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
N |
Date |
2021-09-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-09-27 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-09-27 |
Time |
12:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2021-08-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-08-27 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-08-27 |
Time |
13:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2021-08-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-04-08 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-04-08 |
Time |
08:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2021-09-27 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-09-27 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-09-27 |
Time |
13:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-08-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-08-23 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-08-23 |
Time |
14:54 |
Sent To |
|
|
Notes |
2021-08-23 14:55:33 | ORIGINAL SIGNED AND SEALED DRAWINGS SENT TO STORAGE. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-08-16 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-08-16 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-08-16 |
Time |
15:47 |
Sent To |
|
|
Notes |
2021-08-16 15:51:43 | PLAN IS A COPY NOT THE ORIGINAL SIGNATURE JLEAHY |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-04-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-04-07 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-04-07 |
Time |
11:10 |
Sent To |
|
|
Notes |
2021-04-07 11:11:23 | WILL NEED TO BE DETERMINED WHEN GENERATOR PAD DRAWINGS | | ARE SUBMITTED. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2021-04-21 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2021-04-21 |
Time |
|
Rev Time |
|
Received By |
rthermid |
Date |
2021-04-21 |
Time |
|
Sent To |
I |
|
Notes |
|
|