Plan Review Details - Permit 21031101
Plan Review Stops For Permit 21031101
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2021-12-15 Cont ID  
Sent By dbattles Date 2021-12-15 Time 16:11 Rev Time 0.00
Received By dbattles Date 2021-12-15 Time 16:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-28 Cont ID  
Sent By rmcdouga Date 2021-04-28 Time 16:10 Rev Time 0.00
Received By rmcdouga Date 2021-04-28 Time 16:10 Sent To  
Notes
2021-04-28 16:21:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IT APPEARS THAT A SEPARATE BUILDING PERMIT MAY BE
 REQUIRED FOR THIS PROJECT. PROVIDE A COMPLETE SCOPE OF
 WORK FOR THIS PROJECT (INCLUDE ALL WORK THAT WILL BE
 DONE). A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
  
 2) FS 471 & 481 FBC 107.2.1.4 QUALITY OF BUILDING
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THIS POLICY MAY INCLUDE SUCH THINGS
 AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER
 ITEMS RELATED TO RECORDS MANAGEMENT. SUBMIT PLANS WITH
 DIMENSIONS AND DRAWN TO SCALE. A FLORIDA LICENSED
 DESIGN PROFESSIONAL MAY BE REQUIRED TO PRODUCE THE
 PLANS IF THERE IS ANY STRUCTURAL WORK OR WORK INVOLVES
 ANY OF THE FIRE RATED TENANT SEPARATION WALLS, CEILINGS
 OR FLOORS.
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2021-04-19 12:06:5604/19/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. A BUILDING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1. THIS PERMIT MUST BE SUBMITTED AS
 A SUB ALONG WITH AN A ELECTRICAL.
  
 2. PLEASE PROVIDE PLANS THAT SHOW THE WORK THAT IS
 RELATED TO THE PROPOSED WORK PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. THE SINK AND LAV HAVE BEEN MOVED SO PLEASE PROVIDE A
 PLUMBING RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 4. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2021-12-15 Cont ID  
Sent By dbattles Date 2021-12-15 Time 16:11 Rev Time 0.00
Received By dbattles Date 2021-12-15 Time 16:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-24 Cont ID  
Sent By jleahy Date 2021-04-24 Time 07:02 Rev Time 0.00
Received By jleahy Date 2021-04-24 Time 07:02 Sent To  
Notes
2021-04-24 07:04:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW ELECTRICAL WORK INVOLVED WITH TIS PROJECT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 09:50 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-28 Cont ID  
Sent By rmcdouga Date 2021-04-28 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2021-04-16 Time 08:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 09:50 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 09:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-19 Cont ID  
Sent By lcrespo Date 2021-04-19 Time 11:35 Rev Time 0.00
Received By lcrespo Date 2021-04-19 Time 11:17 Sent To  
Notes
2021-04-28 16:09:2304/19/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. A BUILDING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1. THIS PERMIT MUST BE SUBMITTED AS
 A SUB ALONG WITH AN A ELECTRICAL.
  
 2. PLEASE PROVIDE PLANS THAT SHOW THE WORK THAT IS
 RELATED TO THE PROPOSED WORK PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. THE SINK AND LAV HAVE BEEN MOVED SO PLEASE PROVIDE A
 PLUMBING RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 4. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-15 Cont ID  
Sent By dbattles Date 2021-12-15 Time 16:10 Rev Time 0.00
Received By dbattles Date 2021-12-15 Time 16:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-19 Cont ID  
Sent By lcrespo Date 2021-04-19 Time 12:07 Rev Time 0.00
Received By lcrespo Date 2021-04-19 Time 12:06 Sent To  
Notes
2021-04-19 12:07:14PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.