Plan Review Details - Permit 21031012
Plan Review Stops For Permit 21031012
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By cthroop Date 2021-04-07 Time 14:33 Rev Time 0.00
Received By cthroop Date 2021-04-07 Time 14:03 Sent To  
Notes
2021-04-07 14:35:33PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1.PROVIDE THE DESIGN PRESSURES OF EACH OPENING.
  
 FBC 107.3.5.3 PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 NOTE: YOU MAY PROVIDE A SCHEDULE OF OPENINGS OR PLACE
 THE DESIGN PRESSURES NEXT TO EACH OPENING ON YOUR PLAN.
  
 2. PROVIDE A FLOOR PLAN. IDENTIFY LOCATION OF EACH
 OPENING.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-04-20 Cont ID  
Sent By aborngra Date 2021-04-20 Time 16:40 Rev Time 0.00
Received By aborngra Date 2021-04-20 Time 16:40 Sent To  
Notes
2021-04-20 16:40:41THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE
 WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF
 AT [email protected] TO REQUEST THE EXAMPLE. AT
 MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOWS AND
 THE PROPOSED WINDOWS - MATERIAL, EXTERIOR FRAME COLOR,
 GLASS GLAZING, LITE PATTERN, MUNTIN PROFILE AND MULLION
 WIDTH. A PHOTO OF EACH ELEVATION WITH EACH WINDOW
 MARKED AND CLEARLY VISIBLE. IF SHUTTERS OR SIMILAR
 VISUAL OBSTRUCTION EXISTS, MULTIPLE PHOTOS MAY BE
 REQUIRED. INCLUDE THE ORDER QUOTE DETAIL.
  
 NOTE: ORIGINAL OR SIGNIFICANT WOOD WINDOWS ON STREET
 FACING ELEVATIONS MAY NEED TO BE RETAINED. THESE
 WINDOWS IF APPLICABLE SHOULD BE RESTORED. OTHER TYPES
 OF FENESTRATION PROTECTION ARE AVAILABLE.
  
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE. CONFIRM THAT
 THE PROPOSED PRODUCT(S) WILL COMPLY WITH THESE
 CONDITIONS.
 1. ALL REPLACEMENT WINDOWS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS) AND
 MATCH THE LOCATION/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS.
 2. THE EXISTING MULLION SHALL REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT.
 3. ALL STREET OR SIDEWALK FACING GLASS SHALL BE CLEAR.
 ALL NON-STREET FACING GLASS SHALL BE CLEAR OR CLEAR
 WITH LOW-E COATING. NO TINT. OBSCURED TEXTURED GLASS
 MAY BE USED ON NON-STREET FACING BATHROOMS ONLY.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-20 Cont ID  
Sent By lmarchan Date 2021-04-20 Time 17:01 Rev Time 0.00
Received By lmarchan Date 2021-03-22 Time 09:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-04-07 Cont ID  
Sent By cthroop Date 2021-04-07 Time 14:35 Rev Time 0.00
Received By cthroop Date 2021-04-07 Time 14:03 Sent To  
Notes
***NONE***