Plan Review Details - Permit 21030951
Plan Review Stops For Permit 21030951
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-05-03 Cont ID  
Sent By cpuell Date 2021-05-03 Time 15:10 Rev Time 0.00
Received By cpuell Date 2021-05-03 Time 15:10 Sent To  
Notes
2021-05-03 15:11:16FRONT BUILDING READDRESSED FROM 318 GREENWOOD TO 316
 GREENWOOD, BACK PROPERTY READDRESSED FROM 318 1/2
 GREENWOOD TO 318 GREENWOOD

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-04-20 Cont ID  
Sent By cpuell Date 2021-04-20 Time 12:57 Rev Time 0.00
Received By cpuell Date 2021-04-20 Time 12:57 Sent To  
Notes
2021-04-20 12:57:50HALF ADDRESS VIOLATION ON PROPERTY, PLEASE HAVE OWNER
 CONTACT [email protected] TO READDRESS HALF ADDRESS

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-03-22 Cont ID  
Sent By cpuell Date 2021-03-22 Time 12:50 Rev Time 0.00
Received By cpuell Date 2021-03-22 Time 12:50 Sent To  
Notes
2021-03-22 12:51:11HALF ADDRESS VIOLATION ON PROPERTY, PLEASE HAVE OWNER
 CONTACT [email protected] TO READDRESS HALF ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-05-03 Cont ID  
Sent By pvalenti Date 2021-05-03 Time 07:03 Rev Time 0.00
Received By pvalenti Date 2021-04-29 Time 07:41 Sent To  
Notes
2021-05-03 07:05:56PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 PROVIDE (2) LAYERS OF THE PROPOSED UNDERLAYMENT OR
 ALTERNATE METHOD AS PER FBC R 905.1.1.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-20 Cont ID  
Sent By pvalenti Date 2021-04-20 Time 15:54 Rev Time 0.00
Received By pvalenti Date 2021-04-20 Time 15:43 Sent To  
Notes
2021-04-20 16:04:42PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 PROVIDE (2) LAYERS OF THE PROPOSED UNDERLAYMENT OR
 ALTERNATE METHOD AS PER FBC R 905.1.1.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By pvalenti Date 2021-03-24 Time 15:53 Rev Time 0.00
Received By pvalenti Date 2021-03-24 Time 15:06 Sent To  
Notes
2021-03-24 16:06:35****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107.2, THE IMAGES SUBMITTED UNDER THE TITLE
 FORM 100 MAIN HOUSE APPEAR TO SHOW MORE THAN (1)
 STRUCTURE WITH INDICATIONS OF BEING PART OF THIS PERMIT
 WHILE THE APPLICATION INDICATES MAIN HOUSE ONLY. PLEASE
 CLARIFY THE PROPOSED WORK.
  
 2) FBC B 107.2, THE SUBMITTED SPECIFICATIONS FOR SNAP
 MAX FROM EXTREME METAL FABRICATORS METHOD "A" DOES NOT
 SHOW A RATING FOR 170 MPH (ZONE 3) WITHIN THE PROVIDED
 TABLES. PLEASE PROVIDE ANOTHER METHOD TO MEET THE
 WINDLOAD REQUIREMENTS FOR ZONE 3.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-04-20 Cont ID  
Sent By aborngra Date 2021-04-20 Time 12:00 Rev Time 0.00
Received By aborngra Date 2021-04-20 Time 12:00 Sent To  
Notes
2021-04-20 11:59:26THE VICTORIAN CLASSIC SHINGLE SHALL HAVE A MILL,
 ANODIZED, OR GALVANIZED FINISH.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-03-25 Cont ID  
Sent By aborngra Date 2021-03-25 Time 14:58 Rev Time 0.00
Received By aborngra Date 2021-03-25 Time 14:58 Sent To  
Notes
2021-03-25 14:58:49THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. REVISE TO METAL SHINGLE ROOF WITH A MILL, GALVANIZED
 OR ANODIZED FINISH. STANDING SEAM METAL ROOF IS
 INAPPROPRIATE FOR THIS STRUCTURE.
  
 FOR EXAMPLE, BERRIDGE VICTORIAN OR CLASSIC SHINGLES ARE
 AN OPTION. THIS IS NOT A RECOMMENDATION.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-03 Cont ID  
Sent By cpuell Date 2021-05-03 Time 15:11 Rev Time 0.00
Received By cpuell Date 2021-04-21 Time 14:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-20 Cont ID  
Sent By pvalenti Date 2021-04-20 Time 16:04 Rev Time 0.00
Received By pvalenti Date 2021-04-19 Time 11:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-25 Cont ID  
Sent By lmarchan Date 2021-03-25 Time 16:14 Rev Time 0.00
Received By lmarchan Date 2021-03-19 Time 08:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-24 Cont ID  
Sent By pvalenti Date 2021-03-24 Time 15:52 Rev Time 0.00
Received By pvalenti Date 2021-03-24 Time 15:06 Sent To  
Notes
***NONE***