Plan Review Details - Permit 21030802
Plan Review Stops For Permit 21030802
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-22 Cont ID  
Sent By pvalenti Date 2021-04-22 Time 07:56 Rev Time 0.00
Received By pvalenti Date 2021-04-22 Time 07:47 Sent To  
Notes
2021-04-22 07:58:11PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107, PLEASE PROVIDE ENGINEER?S SIGNATURE & SEAL
 ON PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-06 Cont ID  
Sent By pvalenti Date 2021-04-06 Time 14:17 Rev Time 0.00
Received By pvalenti Date 2021-04-06 Time 14:17 Sent To  
Notes
2021-04-06 14:26:06PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107, PLEASE PROVIDE ENGINEER'S SIGNATURE & SEAL
 ON PLAN.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2021-04-01 Cont ID  
Sent By jleahy Date 2021-04-01 Time 06:49 Rev Time 0.00
Received By jleahy Date 2021-04-01 Time 06:48 Sent To  
Notes
2021-04-01 06:50:32NON-ILLUMINATED SIGN JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-22 Cont ID  
Sent By pvalenti Date 2021-04-22 Time 08:02 Rev Time 0.00
Received By pvalenti Date 2021-04-08 Time 12:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-07 Cont ID  
Sent By lmarchan Date 2021-04-07 Time 10:52 Rev Time 0.00
Received By lmarchan Date 2021-03-26 Time 13:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-04-22 Cont ID  
Sent By pvalenti Date 2021-04-22 Time 07:59 Rev Time 0.00
Received By pvalenti Date 2021-04-22 Time 07:47 Sent To  
Notes
2021-04-22 08:01:38SIGNATURE REVIEW DENIED:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN MAIL AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-06 Cont ID  
Sent By pvalenti Date 2021-04-06 Time 14:17 Rev Time 0.00
Received By pvalenti Date 2021-04-06 Time 13:50 Sent To  
Notes
2021-04-06 14:18:02PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURE REVIEW DENIED:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN MAIL AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-04-15 Cont ID  
Sent By eschneid Date 2021-04-15 Time 13:47 Rev Time 0.50
Received By eschneid Date 2021-04-15 Time 11:37 Sent To  
Notes
2021-04-15 13:44:40FASCIA SIGN
  
 1) THIS IS A SECOND FASCIA SIGN FOR THE STOREFRONT
 WHICH THE ROSEMARY SQUARE TENANT SIGN ONLY PERMIT ON A
 CASE BY CASE BASIS. SIGNS PERMITTED ON A CASE BY CASE
 BASIS REQUIRE A WAIVER I APPROVAL LETTER FROM CITYPLACE
 RETAIL, LLC.
  
 2) THE PROPOSED LOCATION OF THIS FASCIA SIGN IS NOT IN
 THE STOREFRONT TYPE 2 FASCIA SIGN LOCATION. ALTERNATIVE
 HORIZONTAL AND VERTICAL PLACEMENTS OF FASCIA SIGNS ARE
 PERMITTED IF GRANTED A WAIVER I APPROVAL LETTER FROM
 CITYPLACE RETAIL, LLC. PLEASE NOTE THAT THIS LOCATION
 REQUIRES A WAIVER FOR BOTH THE HORIZONTAL AND VERTICAL
 PLACEMENT.
  
 3) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THE
 STUD MOUNTS TO BE SERIES 316 STAINLESS STEEL ANCHOR
 BOLTS. THE PLANS SHOW ALUMINUM STUDS, WHICH ARE NOT
 PERMITTED.
  
 4) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT THE SIGN COPY AREA SHALL MAINTAIN A MARGIN AT
 LEAST THREE (3) INCHES FROM ANY EDGE OF THE PERCEIVED
 SIGN AREA. WHILE THE PLANS SHOW SUFFICIENT DIMENSION TO
 MEET THE REQUIREMENT, IT IS NOT CLEARLY DEMONSTRATED ON
 THE PLANS. PROVIDE VERIFICATION THAT THE REQUIREMENT IS
 MET.
  
 5) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 NON-INTERNALLY ILLUMINATED FASCIA SIGNS CONSISTING OF
 INDIVIDUAL LETTERS BE AT LEAST ONE-HALF INCH THICK. THE
 PROPOSED THICKNESS DOES NOT MEET THIS REQUIREMENT.
  
 6) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT PEG MOUNTED, NON-INTERNALLY ILLUMINATED,
 INDIVIDUAL LETTERS FOR FASCIA SIGNS BE MOUNTED A
 MINIMUM OF ONE (1) INCH FROM THE WALL. PROVIDE
 VERIFICATION THAT THE REQUIREMENT IS MET.
  
 PERMITTED AREA: 70 SF
 PERMIT 21030800 AREA: 14.1 SF
 PROPOSED AREA: 4 SF
 TOTAL AREA: 18.1 SF
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By eschneid Date 2021-04-07 Time 10:23 Rev Time 0.25
Received By eschneid Date 2021-04-07 Time 10:23 Sent To  
Notes
2021-04-07 10:34:38FAILED
  
 1) THIS TENANT LOCATION IS DESIGNATED AS A STOREFRONT
 TYPE 2, SINGLE HEIGHT TENANT WITH LOWER AND UPPER LEVEL
 ARCADE, IN THE ROSEMARY SQUARE SIGN CRITERIA. THE
 STOREFRONT TYPE 2 ONLY PERMITS FASCIA IDENTITY SIGNS ON
 THE EXTERIOR FACADE OF THE BUILDING (SUBJECT TO A
 WAIVER I APPROVAL BY CITYPLACE RETAIL, LLC), NOT ON THE
 FACADE UNDER THE ARCADE. THE PROPOSED SIGN LOCATION IS
 NOT PERMITTED BY THE ROSEMARY SQUARE SIGN CRITERIA AND
 THERE IS NO WAIVER PROCESS INCLUDED TO PERMIT THIS SIGN
 LOCATION.
  
 2) STAFF HAS NOT REVIEWED THE SIGN DESIGN AS THIS IS
 NOT A PERMITTED SIGN.
  
 3) THE ONLY TYPES OF SIGNS PERMITTED BY THE ROSEMARY
 SQUARE SIGN CRITERIA WITHIN THE ARCADE ARE SIGN TYPE 2A
 OR 2B BLADE SIGN (WALL OR CEILING), SIGN TYPE 3 WINDOW
 GRAPHICS AND FLOOR ENTRY SIGNS. NOTE: BASED ON THE
 ELEVATION DRAWING SUBMITTED WITH THE PERMIT, IT APPEARS
 THAT A GRAPHIC OF THE SAME SIZE AS THE NOT PERMITTED
 WALL SIGN COULD BE APPLIED TO THE WINDOW ADJACENT TO
 THE DOOR. ALL OF THE PERMITTED SIGN TYPES REQUIRE SIGN
 PERMIT REVIEW AND APPROVAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  