Plan Review Details - Permit 21030664
Plan Review Stops For Permit 21030664
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-05-24 Cont ID  
Sent By rmcdouga Date 2021-05-24 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2021-05-24 Time 16:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By rmcdouga Date 2021-04-07 Time 09:02 Rev Time 0.00
Received By rmcdouga Date 2021-04-07 Time 09:02 Sent To  
Notes
2021-04-07 09:16:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PERMIT APPLICATION SPECIFIES A 22 KW GENERATOR
 AND THE OTHER PERMIT DOCUMENTS SPECIFY A 32 KW
 GENERATOR. CLARIFY. FBC AMENDMENTS 107.2.1
  
 2) SUBMIT PRODUCT APPROVALS OR SIGNED AND SEALED SITE
 SPECIFIC ENGINEERING FOR THE PRE-FABRICATED GENERATOR
 PAD. FBC AMENDMENTS 107.3.4
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-18 Cont ID  
Sent By jleahy Date 2021-05-18 Time 13:28 Rev Time 0.00
Received By jleahy Date 2021-05-17 Time 17:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-25 Cont ID  
Sent By cthroop Date 2021-03-25 Time 15:15 Rev Time 0.00
Received By cthroop Date 2021-03-25 Time 15:05 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-04-13 Cont ID  
Sent By lmarchan Date 2021-04-13 Time 16:11 Rev Time 0.00
Received By lmarchan Date 2021-04-13 Time 16:11 Sent To  
Notes
2021-04-13 16:11:24GAS APPLIED FOR SEPARATELY

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By ccole Date 2021-04-08 Time 10:06 Rev Time 0.00
Received By ccole Date 2021-04-08 Time 09:04 Sent To  
Notes
2021-04-08 10:07:041ST REVIEW FBC-2020 RES.
 PERMIT- 21030664
 4/8/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED GAS RISER DRAWING IS FOR THE PROPERTY
 OWNER AT 211 DYER RD. THE PROJECT ADDRESS IS 10824
 OSPREY TRACE- OWNER STANLEY KRANGEL. PLEASE SUBMIT THE
 CORRECT RISER DRAWING- SECTION 107.2.1 WPB.
  
 2) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 THE NEW GAS PIPING TO THE GENERATOR AND ALL EXISTING
 GAS PIPING AND APPLIANCES AT THE RESIDENCE- SECTION
 G2412.3 & G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24
 FUEL GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-24 Cont ID  
Sent By rmcdouga Date 2021-05-24 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2021-05-07 Time 15:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-14 Cont ID  
Sent By cthroop Date 2021-04-14 Time 09:10 Rev Time 0.00
Received By cthroop Date 2021-03-23 Time 16:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-08 Cont ID  
Sent By ccole Date 2021-04-08 Time 10:08 Rev Time 0.00
Received By ccole Date 2021-04-08 Time 09:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-24 Cont ID  
Sent By rmcdouga Date 2021-05-24 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2021-05-24 Time 16:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By rmcdouga Date 2021-04-07 Time 09:16 Rev Time 0.00
Received By rmcdouga Date 2021-04-07 Time 09:16 Sent To  
Notes
2021-04-07 09:18:02THE PRE-FABRICATED GENERATOR PAD ENGINEERING THAT WAS
 SUBMITTED IS NOT DIGITALLY SIGNED BY THE ENGINEER.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-04-13 Cont ID  
Sent By rthermid Date 2021-04-13 Time 13:24 Rev Time 0.00
Received By kalexand Date 2021-04-13 Time 13:24 Sent To I
Notes
***NONE***