Plan Review Details - Permit 21030661
Plan Review Stops For Permit 21030661
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:00 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 16:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By cthroop Date 2021-05-07 Time 08:39 Rev Time 0.00
Received By cthroop Date 2021-05-07 Time 08:29 Sent To  
Notes
2021-05-07 08:37:16PLAN REVIEW / BUILDING / GENERATOR
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 1) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4) STRUCTURAL PAD DETAIL SHALL BE SIGNED BY DESIGNER.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 NOTICE: R303.5.1 INTAKE OPENINGS: MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-18 Cont ID  
Sent By jleahy Date 2021-06-18 Time 16:08 Rev Time 0.00
Received By jleahy Date 2021-06-18 Time 16:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By equinone Date 2021-05-07 Time 13:11 Rev Time 0.00
Received By equinone Date 2021-05-07 Time 13:11 Sent To  
Notes
2021-05-07 14:19:05CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. SEE NEW COMMENTS BELOW
  
 1) SERVICE CONDUCTORS TO EACH OF THE 200 AMPS ATS ARE
 2/0 CU FOR EACH OF THE . NEC 310.15(B)(7) DOES NOT
 ALLOW DERATING OF SERVICE
 CONDUCTORS WHEN SERVIDE CONDUCTORS ARE NOT SUPPLYING
 THE ENTIRE LOAD. MINIMUM SIZE SHALL BE #3/0 CONDUCTORS
 OR PROVIDE CLARIFICATION.
  
  
 SINCERELY,
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-06-03 Cont ID  
Sent By lmarchan Date 2021-06-03 Time 15:40 Rev Time 0.00
Received By lmarchan Date 2021-06-03 Time 15:40 Sent To  
Notes
2021-06-03 15:40:27GAS WILL BE APPLIED FOR SEPARATELY PER CUSTOMER. LEM

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By ccole Date 2021-05-07 Time 07:44 Rev Time 0.00
Received By ccole Date 2021-05-07 Time 07:34 Sent To  
Notes
2021-05-07 07:45:341ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21030661
 5/7/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A COMPLETE GAS RISER DRAWING FOR THE
 GENERATOR THAT INCLUDES ALL NEW AND EXISTING GAS PIPING
 AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 &
 G2412.4 FBC RES. CURRENTLY, GAS PERMIT- 20010077 FOR
 GAS PIPING TO THE POOL HEATER IS UNDER REVIEW. PLEASE
 CONSULT WITH THE OWNER OF THE RESIDENCE AS IT APPEARS
 COORDINATION WITH THE OTHER GAS PIPING CONTRACTOR WILL
 BE REQUIRED. THE COMPLETE GAS RISER SHALL INDICATE:
  
 A) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 B) TYPES AND SIZES OF PIPING.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 I) PIPE SIZING TABLES.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS MARKED UP OR HIGHLIGHTED TO SHOW THE
 SELECTED MODEL, INPUT AND OUT PRESSURES AND PIPE SIZES,
 AND ORIFICE SIZES- G2421.1 & G2421.2 FBC RES.
  
 3) SURVEY: PLEASE INDICATE THE REQUIRED 10 FT.
 CLEARANCE FOR THE GENERATOR EXHAUST TO WINDOW AND DOOR
 OPENINGS INTO THE BUILDING- SECTION R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2021-05-11 Cont ID  
Sent By fmittner Date 2021-05-11 Time 11:55 Rev Time 0.00
Received By fmittner Date 2021-05-11 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2021-06-15 Time 09:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 14:03 Rev Time 0.00
Received By jleahy Date 2021-04-09 Time 15:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-05-07 Cont ID  
Sent By ccole Date 2021-05-07 Time 08:02 Rev Time 0.00
Received By ccole Date 2021-05-07 Time 07:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 16:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By cthroop Date 2021-05-07 Time 08:37 Rev Time 0.00
Received By cthroop Date 2021-05-07 Time 08:29 Sent To  
Notes
2021-05-07 08:39:21STRUCTURAL PAD DETAIL SHALL BE SIGNED BY DESIGNER.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-11 Cont ID  
Sent By fmittner Date 2021-05-11 Time 11:56 Rev Time 0.00
Received By fmittner Date 2021-05-11 Time 11:56 Sent To  
Notes
***NONE***