Plan Review Details - Permit 21030387
Plan Review Stops For Permit 21030387
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2021-04-19 Cont ID  
Sent By cpuell Date 2021-04-19 Time 09:48 Rev Time 0.00
Received By cpuell Date 2021-04-19 Time 09:48 Sent To  
Notes
2021-04-19 09:49:06SCOPE OF WORK FOR BOTH BUILDINGS 3709 S OLIVE AVE AND
 301 CENTRAL DR

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2021-04-15 Cont ID  
Sent By cpuell Date 2021-04-15 Time 17:16 Rev Time 0.00
Received By cpuell Date 2021-04-15 Time 17:16 Sent To  
Notes
2021-04-15 17:16:46COMMENTS NOT FROM 3.25.21 OR 4.6.21: TWO BUILDINGS ON
 PROPERTY, WILL THE WORK BE FOR THE EAST OR WEST BLDG?
 WEST BLDGING HAS A HALF ADDRESS, PLEASE HAVE OWNER
 CONTACT [email protected] TO DISCUSS READDRESSING THE NO
 LONGER ALLOWED HALF ADDRESS.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-04-06 Cont ID  
Sent By cpuell Date 2021-04-06 Time 12:51 Rev Time 0.00
Received By cpuell Date 2021-04-06 Time 12:50 Sent To  
Notes
2021-04-06 12:51:29COMMENTS NOT ADDRESSED: TWO BUILDINGS ON PROPERTY, WILL
 THE WORK BE FOR THE EAST OR WEST BLDG? WEST BLDGING HAS
 A HALF ADDRESS, PLEASE HAVE OWNER CONTACT
 [email protected] TO DISCUSS READDRESSING THE NO LONGER
 ALLOWED HALF ADDRESS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-03-25 Cont ID  
Sent By cpuell Date 2021-03-25 Time 16:04 Rev Time 0.00
Received By cpuell Date 2021-03-25 Time 16:04 Sent To  
Notes
2021-03-25 16:05:40TWO BUILDINGS ON PROPERTY, WILL THE WORK BE FOR THE
 EAST OR WEST BLDG? WEST BLDGING HAS A HALF ADDRESS,
 PLEASE HAVE OWNER CONTACT CPUELLWWPB.ORG TO DISCUSS
 READDRESSING THE NO LONGER ALLOWED HALF ADDRESS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-05-04 Cont ID  
Sent By equinone Date 2021-05-04 Time 14:06 Rev Time 0.00
Received By equinone Date 2021-05-04 Time 14:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-04-22 Cont ID  
Sent By equinone Date 2021-04-22 Time 10:50 Rev Time 0.00
Received By equinone Date 2021-04-22 Time 10:50 Sent To  
Notes
2021-04-22 10:56:53CODES IN EFFECT
  
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SERVICE CONDUCTORS ARE UNDERSIZED AS PER THE LOAD
 CALCULATIONS SUBMITTED. PLEASE PROVIDE ADEQUATE
 CONDUCTORS. NEC 230.23. PLEASE NOTICE THAT THE AMPACITY
 OF THE SERVICE CONDUCTORS CANNOT BE DERATED IN THIS
 CASE. NEC 310.15(7).
 DEMAND LOAD INDICATED IS 131 AMPS (BUILD 1) + 96 AMPS
 (BUILD 2) = 227 AMPS. MINIMUM SIZE FOR SERVICE
 CONDUCTORS IS 4/0 CU (SERVICE CONDUCTORS CANNOT BE
 DERATED NEC 310.15(7))
  
 CORRECTED
  
 2) PLEASE SHOW LOCATION OF SERVICE METERS, DISCONNECTS,
 AND NEW PANELS.
  
 NOT CORRECTED. PLEASE PROVIDE LOCATIONS OF METERS,
 DISCONNECTS AND PANELS
  
 2) PLEASE SPECIFY SIZE OF BREAKER FOR MAIN DISCONNECT A
 (150 AMPS). IF NOT USING A BREAKER PLEASE SPECIFY HOW
 FEEDER FROM DISCONNECT A TO NEW PANEL BUILD IS
 PROTECTED (TAP RULES?)
  
 NOT CORRECTED. WE CANNOT DETERMINE HOW THE FEEDER FROM
 DISCONNECT A TO PANEL BUILD 1 IS PROTECTED. WHAT IS THE
 DISTANCE FROM DISCONNECT A TO THE PANEL? DOES THE
 DISCONNECT HAS AN INTEGRATED BREAKER?
  
 3) PLEASE INDICATE SHORT CIRCUIT INTERRUPTING CAPACITY
 FOR DISCONNECTS AND PANEL BOARDS. FBC 107
  
 NOT CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 THE RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-04-07 Cont ID  
Sent By equinone Date 2021-04-07 Time 09:34 Rev Time 0.00
Received By equinone Date 2021-04-07 Time 09:25 Sent To  
Notes
2021-04-07 09:51:36CODES IN EFFECT
  
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SERVICE CONDUCTORS ARE UNDERSIZED AS PER THE LOAD
 CALCULATIONS SUBMITTED. PLEASE PROVIDE ADEQUATE
 CONDUCTORS. NEC 230.23. PLEASE NOTICE THAT THE AMPACITY
 OF THE SERVICE CONDUCTORS CANNOT BE DERATED IN THIS
 CASE. NEC 310.15(7).
 DEMAND LOAD INDICATED IS 131 AMPS (BUILD 1) + 96 AMPS
 (BUILD 2) = 227 AMPS. MINIMUM SIZE FOR SERVICE
 CONDUCTORS IS 4/0 CU (SERVICE CONDUCTORS CANNOT BE
 DERATED NEC 310.15(7))
  
 2) PLEASE SHOW LOCATION OF SERVICE METERS, DISCONNECTS,
 AND NEW PANELS.
  
 2) PLEASE SPECIFY SIZE OF BREAKER FOR MAIN DISCONNECT A
 (150 AMPS). IF NOT USING A BREAKER PLEASE SPECIFY HOW
 FEEDER FROM DISCONNECT A TO NEW PANEL BUILD IS
 PROTECTED (TAP RULES?)
  
 3) PLEASE INDICATE SHORT CIRCUIT INTERRUPTING CAPACITY
 FOR DISCONNECTS AND PANEL BOARDS. FBC 107
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 THE RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-25 Cont ID  
Sent By equinone Date 2021-03-25 Time 15:40 Rev Time 0.00
Received By equinone Date 2021-03-25 Time 15:40 Sent To  
Notes
2021-03-25 15:41:05CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SERVICE CONDUCTORS ARE UNDERSIZED AS PER THE LOAD
 CALCULATIONS SUBMITTED. PLEASE PROVIDE ADEQUATE
 CONDUCTORS. NEC 230.23. PLEASE NOTICE THAT THE AMPACITY
 OF THE SERVICE CONDUCTORS CANNOT BE DERATED IN THIS
 CASE. NEC 310.15(7).
 2) DOES THE 150 AMPS DISCONNECT FOR BUILD 2 HAS A
 CIRCUIT BREAKER? IF YES, PLEASE INDICATE BREAKER SIZE
 CON RISER DIAGRAM.
 3) PLEASE INDICATE SHORT CIRCUIT INTERRUPTING CAPACITY
 FOR DISCONNECTS AND PANEL BOARDS. FBC 107
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-04 Cont ID  
Sent By equinone Date 2021-05-04 Time 14:10 Rev Time 0.00
Received By equinone Date 2021-04-27 Time 11:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-22 Cont ID  
Sent By equinone Date 2021-04-22 Time 10:58 Rev Time 0.00
Received By equinone Date 2021-04-14 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-07 Cont ID  
Sent By equinone Date 2021-04-07 Time 09:52 Rev Time 0.00
Received By equinone Date 2021-04-01 Time 12:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-25 Cont ID  
Sent By equinone Date 2021-03-25 Time 15:41 Rev Time 0.00
Received By equinone Date 2021-03-10 Time 11:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-03-25 Cont ID  
Sent By equinone Date 2021-03-25 Time 15:41 Rev Time 0.00
Received By equinone Date 2021-03-25 Time 15:41 Sent To  
Notes
***NONE***