Plan Review Details - Permit 21030330
Plan Review Stops For Permit 21030330
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-09 Cont ID  
Sent By jbrooks Date 2021-04-09 Time 11:06 Rev Time 0.00
Received By jbrooks Date 2021-04-09 Time 10:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-30 Cont ID  
Sent By jbrooks Date 2021-03-30 Time 11:30 Rev Time 0.00
Received By jbrooks Date 2021-03-30 Time 07:56 Sent To  
Notes
2021-03-30 11:30:49JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY, THURSDAY & FRIDAY 7:00 AM TO 3:00
 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R7 SELECTED OPTION FOR SYSTEM NO W-2;
 EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15);
 ULTIMATE WIND SPEED (180). ZONE 3 IS MARKED ?N/A? WHICH
 INDICATES SYSTEM CANNOT BE USED WITHIN THE PRESSURE
 ZONE. THE CORRECT EXPOSURE FOR THE LISTED ADDRESS IS
 EXPOSURE B. PLEASE SELECT THE CORRECT OPTIONS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-16 Cont ID  
Sent By jbrooks Date 2021-03-16 Time 10:21 Rev Time 0.00
Received By jbrooks Date 2021-03-16 Time 07:40 Sent To  
Notes
2021-03-16 10:16:36JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R7 COVERS MULTIPLE ROOF SYSTEM NO. W-1
 THRU W-5. PLEASE SELECT CORRECT OPTIONS FOR SYSTEM NO
 W-2; EXPOSURE (B); ENCLOSURE (ENCLOSED); ROOF HEIGHT
 (H<15); ULTIMATE WIND SPEED (180). ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS
 NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-03-11 Cont ID  
Sent By aborngra Date 2021-03-11 Time 12:19 Rev Time 0.00
Received By aborngra Date 2021-03-11 Time 12:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-09 Cont ID  
Sent By jbrooks Date 2021-04-09 Time 11:06 Rev Time 0.00
Received By jbrooks Date 2021-04-02 Time 07:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-30 Cont ID  
Sent By jbrooks Date 2021-03-30 Time 11:31 Rev Time 0.00
Received By jbrooks Date 2021-03-23 Time 07:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-16 Cont ID  
Sent By jbrooks Date 2021-03-16 Time 10:21 Rev Time 0.00
Received By jbrooks Date 2021-03-10 Time 16:42 Sent To  
Notes
***NONE***