Plan Review Stops For Permit 21030228 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2021-03-16 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-03-16 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-03-16 |
Time |
11:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2021-03-09 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-03-09 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-03-09 |
Time |
10:19 |
Sent To |
|
|
Notes |
2021-03-09 11:08:37 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE SUBMITTED PALN ARE GENERAL IN NATURE AND DO NOT | | APPEAR | | | | 1) THERE IS NO ADDRESS INDICATED IN THE TITLE BLOCK, | | ONLY A OCCUPANCY NAME. | | | | PLEASE CORRECT WITH THE SPECIFIC ADDRESS. | | | | | | 2) THERE IS NO FLOOR PLAN SHOWING THE LOCATION OF THE | | PROPOSED HOOD SYSTEM | | | | PLEASE PROVIDE A FLOOR WITH THE LOCATION OF THE HOOD. | | | | | | 3) THERE IS NO ROOF PLAN INDICATING THE SPECIFIC | | LOCATION OF THE UNIT AND DIMESIONS TO OTHER EQUIPMENT | | OF ROOF LINES | | | | PLEASE PROVIDE A ROOF PLAN WITH THE LOCATION OF ALL | | EQUIPMENT. | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-03-17 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-17 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-15 |
Time |
16:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-03-09 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-09 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-05 |
Time |
08:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2021-03-17 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-17 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-17 |
Time |
13:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2021-03-09 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-09 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-09 |
Time |
15:53 |
Sent To |
|
|
Notes |
2021-03-09 16:03:07 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21030228 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE SEE FIRE REVIEWERS COMMENTS. | | | | 2) PLEASE PROVIDE A GREASE DUCT DRAWING SHOWING THE | | SIZE OF THE DUCTS AND THE ROUTE OF THE DUCTS FROM THE | | HOODS AND DISHWASHER TO THE TERMINATION POINT ON THE | | ROOF. FBC 107.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
1 |
Status |
P |
Date |
2021-03-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2021-03-04 |
Time |
18:45 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2021-03-04 |
Time |
18:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-03-18 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-18 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-18 |
Time |
13:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-03-17 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-17 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-17 |
Time |
15:00 |
Sent To |
|
|
Notes |
2021-03-17 15:01:36 | SHEET M3.1 IS MISSING THE DESIGNERS DIGITAL SEAL AND | | SIGNATURE. | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-03-09 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-09 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-09 |
Time |
16:04 |
Sent To |
|
|
Notes |
2021-03-09 16:05:16 | THE DESIGNER OF THE CAPTIVE AIRE DRAWINGS MUST PRINT | | THEIR NAME AND SIGN THE DRAWINGS. | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|