Plan Review Stops For Permit 21030173 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2021-07-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-07-15 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-07-15 |
Time |
16:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-03-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-03-11 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-03-11 |
Time |
14:14 |
Sent To |
|
|
Notes |
2021-03-11 14:14:21 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-03-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-03-15 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-03-15 |
Time |
15:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2021-07-16 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-07-16 |
Time |
08:01 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-07-16 |
Time |
07:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-04-05 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-04-05 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-04-05 |
Time |
13:47 |
Sent To |
|
|
Notes |
2021-04-05 14:33:16 | 1ST REVIEW FBC-2020 RES. | | PERMIT-21030173 | | 4/5/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE LP TANK ANCHORAGE DETAIL HAS A COPIED ENGINEER'S | | SEAL. DOCUMENTS PREPARED BY A FL. LICENSED ENGINEER | | REQUIRE AN ORIGINAL SIGNATURE AND SEAL IS REQUIRED. | | ENGINEERED DOCUMENTS SUBMITTED ELECTRONICALLY SHALL | | HAVE BEAR THE DIGITAL SIGNATURE AND SEAL OF THE FL. | | LICENSED ENGINEER- FL. STATUTE 471.025 AND SECTION | | 61G15-23.005 FAC. | | | | 2) PLEASE SUBMIT THE SPECS FOR THE 32 KW GENERATOR. THE | | SUBMITTED SPECS ARE FOR SMALLER KW GENERATORS- SECTION | | G2408.1 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-07-16 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-07-16 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-07-13 |
Time |
13:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-03-25 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2021-04-05 |
Time |
07:11 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2021-03-10 |
Time |
17:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2021-07-16 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-07-16 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-07-16 |
Time |
07:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2021-04-05 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-04-05 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-04-05 |
Time |
13:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-07-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-07-15 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-07-15 |
Time |
16:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-03-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-03-11 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-03-11 |
Time |
14:14 |
Sent To |
|
|
Notes |
2021-03-11 14:16:25 | THE ENGINEER'S DIGITAL SIGNATURE ON THE GENERATOR PAD | | DRAWING COULD NOT BE VERIFIED. ELECTRONICALLY SUBMITTED | | DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL | | SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT | | THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER | | THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT | | THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2021-07-16 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2021-07-16 |
Time |
|
Rev Time |
0.00 |
Received By |
rthermid |
Date |
2021-07-16 |
Time |
|
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2021-03-24 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2021-03-24 |
Time |
|
Rev Time |
|
Received By |
rthermid |
Date |
2021-03-24 |
Time |
|
Sent To |
I |
|
Notes |
2021-03-24 11:42:43 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 3/24/2021 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. ADDRESS BUILDING/STRUCTURAL COMMENTS, PER THE | | FLORIDA BUILDING CODE, MECHANICAL EQUIPMENT MUST BE | | SETBACK A MINIMUM OF 10 FEET FROM ALL WINDOWS, DOOR | | OPENINGS. | | 2. PER THE CITY OF WEST PALM BEACH ZONING AND LAND | | DEVELOPMENT REGULATIONS, MECHANICAL EQUIPMENTS CANNOT | | ENCROACH MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | LIKE TO RESUBMIT ELECTRONICALY, EMAIL | | [email protected] AND REQUEST TO HAVE YOUR | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN | | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | ARE FINISHED UPLOADING. | | | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | TTY: 800.955.8771 | | E: [email protected] | | W: WPB.ORG | | |
|
|