Plan Review Details - Permit 21030170
Plan Review Stops For Permit 21030170
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By cthroop Date 2021-08-10 Time 13:35 Rev Time 0.00
Received By cthroop Date 2021-08-10 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-11 Cont ID  
Sent By rmcdouga Date 2021-03-11 Time 14:39 Rev Time 0.00
Received By rmcdouga Date 2021-03-11 Time 14:39 Sent To  
Notes
2021-03-11 14:32:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REVISE THE NOTE ON THE SURVEY. THE GENERATOR EXHAUST
 IS REQUIRED TO BE 10 FEET FROM ANY OPENINGS TO A
 BUILDING. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 2) SUBMIT A MIAMI-DADE OF FLORIDA PRODUCT APPROVAL OR
 SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR THE
 PRE-FABRICATED GENERATOR PAD. THE SIZE DIMENSIONS AND
 WEIGHT OF THE GENERATOR MUST MATCH THE ONES ON THE
 ENGINEERING OR PRODUCT APPROVAL. THE GENERATOR PAD
 DRAWINGS THAT WERE SUBMITTED DO NOT MATCH THE GENERATOR
 SPECIFICATIONS FOR SIZE AND WEIGHT. FBC AMENDMENTS
 107.2.1
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-15 Cont ID  
Sent By cthroop Date 2021-03-15 Time 12:06 Rev Time 0.00
Received By cthroop Date 2021-03-15 Time 09:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By ccole Date 2021-08-10 Time 15:15 Rev Time 0.00
Received By ccole Date 2021-08-10 Time 14:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-04-05 Cont ID  
Sent By ccole Date 2021-04-05 Time 11:18 Rev Time 0.00
Received By ccole Date 2021-04-05 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-08-10 Time   Rev Time 0.00
Received By   Date 2021-07-07 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-24 Cont ID  
Sent By pvalenti Date 2021-04-05 Time 07:54 Rev Time 0.00
Received By pvalenti Date 2021-03-10 Time 17:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-08-10 Cont ID  
Sent By ccole Date 2021-08-10 Time 15:15 Rev Time 0.00
Received By ccole Date 2021-08-10 Time 14:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-05 Cont ID  
Sent By ccole Date 2021-04-05 Time 11:18 Rev Time 0.00
Received By ccole Date 2021-04-05 Time 09:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By cthroop Date 2021-08-10 Time 13:35 Rev Time 0.00
Received By cthroop Date 2021-08-10 Time 13:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-11 Cont ID  
Sent By rmcdouga Date 2021-03-11 Time 14:41 Rev Time 0.00
Received By rmcdouga Date 2021-03-11 Time 14:41 Sent To  
Notes
2021-03-11 14:30:43THE GENERATOR PAD DRAWING THAT WAS SUBMITTED DOES NOT
 HAVE AN ENGINEER'S ORIGINAL SIGNATURE. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15

Review Stop Z ZONING
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By awooten Date 2021-08-10 Time   Rev Time 0.00
Received By awooten Date 2021-08-10 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-03-23 Cont ID  
Sent By awooten Date 2021-03-23 Time   Rev Time  
Received By awooten Date 2021-03-23 Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved