Plan Review Details - Permit 21030167
Plan Review Stops For Permit 21030167
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-04-08 Cont ID  
Sent By lcrespo Date 2021-04-08 Time 16:44 Rev Time 0.00
Received By lcrespo Date 2021-04-08 Time 10:52 Sent To  
Notes
2021-04-08 16:45:3704/08/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By jesmith Date 2021-03-18 Time 11:45 Rev Time 0.00
Received By jesmith Date 2021-03-16 Time 14:33 Sent To  
Notes
2021-03-18 11:43:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21030167 216 ASHWORTH ST
 MP #21010248
  
 GENERAL NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE
 EMERGENCY GENERATOR
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
  
 1. SPECIFICATION SHEET FOR GAS RANGE IS COMPLETELY
 INADEQUATE. PER WPB FBC 107.2.1, PROVIDE FULL
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 GAS RANGE SHOWING THE TOTAL 65,000 BTUS NOTED ON THE
 RISER DIAGRAM.
  
 2. PER WPB FBC 107.2.1, INDICATE ON THE SPECIFICATION
 SHEETS FOR ALL EQUIPMENT THE APPLICABLE MODEL NUMBER
 FOR EACH PIECE OF EQUIPMENT. ALSO, THE BBQ GRILL
 APPEARS TO BE 42,000 BTUS NOT 40,000.
  
 3. PER WPB FBC 107.2.1, INDICATE ON THE, MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL PROVIDED, THE
 FOLLOWING FOR THE NAVIEN TANKLESS WATER HEATER:
 A) THE MANUFACTURER?S MODEL NUMBER
 B) THE TYPE OF VENT BEING USED (IE. DIRECT VENT-INDOOR,
 INDIRECT VENT-INDOOR). IF INDIRECT VENT, PROVIDE
 COMBUSTION AIR CALCULATIONS PER FBC FG SEC.304.1 AND
 SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT AND ANCHORING DETAILS OF THE GAS
 VENT(S) PER FBC FG SECTIONS 502 THRU 505 OR FBC RES
 SECTIONS G2426 THROUGH G2439. ESPECIALLY SEE FBC FG
 SECTION 503.8(3), TABLE 503.8 WITH NOTE REFERRING TO
 SECTION 503.8(2) AS IS APPLICABLE TO BTU INPUT RATING
 IN EXCESS OF 150,000 BTUS.
  
 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE DRYER.
  
 5. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR
 COMBUSTION AIR FOR THE GAS APPLIANCES LOCATED INSIDE
 THE BUILDING PER FBC FG SEC.304.1, 614.6 (CLOTHES
 DRYERS) OR FBC RES SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 6. PER WPB FBC 107.2.1, SUBMIT A HOUSE PLAN AND IF
 APPLICABLE A SURVEY PLAN SHOWING THE LOCATION OF THE
 GAS METER AND ALL GAS APPLIANCES, INDOORS AND OUTDOORS.
 SHOW THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO ANY VENT TERMINALS AND OUTDOOR
 APPLIANCES. PLEASE NOTE EXHAUST VENTS AND THE GENERATOR
 (WHICH REQUIRES A SEPARATE PERMIT) SHALL BE INSTALLED A
 MINIMUM OF 10' FROM MECHANICAL OR GRAVITY AIR INTAKES
 (WINDOW AND DOOR OPENINGS) INTO THE BUILDING PER FBC
 RES R303.5.1. ADDITIONALLY, THE EMERGENCY GENERATOR
 SHALL BE LOCATED A MINIMUM OF 5' AWAY FROM COMBUSTIBLE
 WALLS PER NFPA 37 SEC. 4.1.4. THE HOUSE PLAN CAN BE
 HAND DRAWN BUT AS THERE IS AN ARCHITECTURAL PLAN AND
 SURVEY IN THE MASTER, IT IS RECOMMENDED THAT THE
 INFORMATION IS PROVIDED BY THE ARCHITECT AND APPLICABLE
 SHEETS ARE PROVIDED TO YOU FOR YOUR PERMIT APPLICATION.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 7. PER FBC FG 404.17.3, PROVIDE MINIMUM 18 AWG YELLOW
 INSULATED COPPER TRACER WIRE SUITABLE FOR DIRECT BURIAL
 OR OTHER APPROVED CONDUCTOR ADJACENT TO UNDERGROUND
 NONMETALLIC PIPING. ACCESS SHALL BE PROVIDED TO THE
 TRACER WIRE OR THE TRACER WIRE SHALL TERMINATE ABOVE
 GROUND AT EACH END OF THE NONMETALLIC PIPING. THE
 TRACER WIRE SIZE SHALL BE NOT LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 8. PER WPB FBC 107.2.1, SHOW TRANSITION FITTINGS AT
 CONNECTIONS MADE BETWEEN METALLIC AND PLASTIC PIPING
 CONFORMING TO ASTM D2513 CATEGORY I OR ASTM F1973
 COMPLYING WITH FBC FG 404.17.2.
  
 9. PER WPB FBC 107.2.1, SHOW THE MAXIMUM DISTANCE FROM
 THE MP REGULATOR(S) TO THE APPLIANCE(S) BEING SERVED,
 TO SHOW COMPLIANCE WITH FBC FG 402.4.1.
 END OF COMMENTS.
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS COMMENTS FROM THE
 FIRST REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
 SUBMITTED PLAN WAS HAND DRAWN BY THE CONTRACTOR
 (QUALIFIER) AND SIGNED IN ACCORDANCE WITH WPB FBC
 107.3.4.3, SCANNED AND UPLOADED TO PROJECT DOCS FOR
 THIS REVIEW. PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE
 SUBMITTED WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND
 LICENSE NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A
 PAPER PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE
 BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO
 ISSUANCE OF A PERMIT.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030167 216 ASHWORTH ST

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-08 Cont ID  
Sent By lcrespo Date 2021-04-08 Time 16:45 Rev Time 0.00
Received By lcrespo Date 2021-04-02 Time 11:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-18 Cont ID  
Sent By jesmith Date 2021-03-18 Time 12:00 Rev Time 0.00
Received By jesmith Date 2021-03-18 Time 12:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-04-08 Cont ID  
Sent By lcrespo Date 2021-04-08 Time 16:44 Rev Time 0.00
Received By lcrespo Date 2021-04-08 Time 10:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-03-16 Cont ID  
Sent By jesmith Date 2021-03-16 Time 15:19 Rev Time 0.00
Received By jesmith Date 2021-03-16 Time 14:33 Sent To  
Notes
2021-03-16 15:22:11SEE MASTER PERMIT 21010248

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-04-02 Cont ID  
Sent By medwards Date 2021-04-02 Time 15:12 Rev Time 0.00
Received By medwards Date 2021-04-02 Time 15:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-03-18 Cont ID  
Sent By jesmith Date 2021-03-18 Time 11:46 Rev Time 0.00
Received By jesmith Date 2021-03-18 Time 11:46 Sent To  
Notes
2021-03-18 11:57:04SUBMITTED PLAN WAS HAND DRAWN BY THE CONTRACTOR
 (QUALIFIER) AND SIGNED IN ACCORDANCE WITH WPB FBC
 107.3.4.3, SCANNED AND UPLOADED TO PROJECT DOCS FOR
 THIS REVIEW. PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE
 SUBMITTED WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND
 LICENSE NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A
 PAPER PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE
 BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO
 ISSUANCE OF A PERMIT.