2021-03-18 11:43:44 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 21030167 216 ASHWORTH ST |
| MP #21010248 |
| |
| GENERAL NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE |
| EMERGENCY GENERATOR |
| |
| 1ST REVIEW |
| |
| GAS COMMENTS: DENIED |
| |
| 1. SPECIFICATION SHEET FOR GAS RANGE IS COMPLETELY |
| INADEQUATE. PER WPB FBC 107.2.1, PROVIDE FULL |
| MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR |
| GAS RANGE SHOWING THE TOTAL 65,000 BTUS NOTED ON THE |
| RISER DIAGRAM. |
| |
| 2. PER WPB FBC 107.2.1, INDICATE ON THE SPECIFICATION |
| SHEETS FOR ALL EQUIPMENT THE APPLICABLE MODEL NUMBER |
| FOR EACH PIECE OF EQUIPMENT. ALSO, THE BBQ GRILL |
| APPEARS TO BE 42,000 BTUS NOT 40,000. |
| |
| 3. PER WPB FBC 107.2.1, INDICATE ON THE, MANUFACTURER'S |
| SPECIFICATION/INSTALLATION MANUAL PROVIDED, THE |
| FOLLOWING FOR THE NAVIEN TANKLESS WATER HEATER: |
| A) THE MANUFACTURER?S MODEL NUMBER |
| B) THE TYPE OF VENT BEING USED (IE. DIRECT VENT-INDOOR, |
| INDIRECT VENT-INDOOR). IF INDIRECT VENT, PROVIDE |
| COMBUSTION AIR CALCULATIONS PER FBC FG SEC.304.1 AND |
| SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| TERMINATION POINT AND ANCHORING DETAILS OF THE GAS |
| VENT(S) PER FBC FG SECTIONS 502 THRU 505 OR FBC RES |
| SECTIONS G2426 THROUGH G2439. ESPECIALLY SEE FBC FG |
| SECTION 503.8(3), TABLE 503.8 WITH NOTE REFERRING TO |
| SECTION 503.8(2) AS IS APPLICABLE TO BTU INPUT RATING |
| IN EXCESS OF 150,000 BTUS. |
| |
| 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| SPECIFICATION/INSTALLATION MANUAL FOR THE DRYER. |
| |
| 5. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR |
| COMBUSTION AIR FOR THE GAS APPLIANCES LOCATED INSIDE |
| THE BUILDING PER FBC FG SEC.304.1, 614.6 (CLOTHES |
| DRYERS) OR FBC RES SEC. G 2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| |
| 6. PER WPB FBC 107.2.1, SUBMIT A HOUSE PLAN AND IF |
| APPLICABLE A SURVEY PLAN SHOWING THE LOCATION OF THE |
| GAS METER AND ALL GAS APPLIANCES, INDOORS AND OUTDOORS. |
| SHOW THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| WINDOWS IN RELATION TO ANY VENT TERMINALS AND OUTDOOR |
| APPLIANCES. PLEASE NOTE EXHAUST VENTS AND THE GENERATOR |
| (WHICH REQUIRES A SEPARATE PERMIT) SHALL BE INSTALLED A |
| MINIMUM OF 10' FROM MECHANICAL OR GRAVITY AIR INTAKES |
| (WINDOW AND DOOR OPENINGS) INTO THE BUILDING PER FBC |
| RES R303.5.1. ADDITIONALLY, THE EMERGENCY GENERATOR |
| SHALL BE LOCATED A MINIMUM OF 5' AWAY FROM COMBUSTIBLE |
| WALLS PER NFPA 37 SEC. 4.1.4. THE HOUSE PLAN CAN BE |
| HAND DRAWN BUT AS THERE IS AN ARCHITECTURAL PLAN AND |
| SURVEY IN THE MASTER, IT IS RECOMMENDED THAT THE |
| INFORMATION IS PROVIDED BY THE ARCHITECT AND APPLICABLE |
| SHEETS ARE PROVIDED TO YOU FOR YOUR PERMIT APPLICATION. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 7. PER FBC FG 404.17.3, PROVIDE MINIMUM 18 AWG YELLOW |
| INSULATED COPPER TRACER WIRE SUITABLE FOR DIRECT BURIAL |
| OR OTHER APPROVED CONDUCTOR ADJACENT TO UNDERGROUND |
| NONMETALLIC PIPING. ACCESS SHALL BE PROVIDED TO THE |
| TRACER WIRE OR THE TRACER WIRE SHALL TERMINATE ABOVE |
| GROUND AT EACH END OF THE NONMETALLIC PIPING. THE |
| TRACER WIRE SIZE SHALL BE NOT LESS THAN 18 AWG AND THE |
| INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL. |
| |
| 8. PER WPB FBC 107.2.1, SHOW TRANSITION FITTINGS AT |
| CONNECTIONS MADE BETWEEN METALLIC AND PLASTIC PIPING |
| CONFORMING TO ASTM D2513 CATEGORY I OR ASTM F1973 |
| COMPLYING WITH FBC FG 404.17.2. |
| |
| 9. PER WPB FBC 107.2.1, SHOW THE MAXIMUM DISTANCE FROM |
| THE MP REGULATOR(S) TO THE APPLIANCE(S) BEING SERVED, |
| TO SHOW COMPLIANCE WITH FBC FG 402.4.1. |
| END OF COMMENTS. |
| |
| |
| A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| RESPONSE NARRATIVE ADDRESSING THE GAS COMMENTS FROM THE |
| FIRST REVIEW. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| SUBMITTED PLAN WAS HAND DRAWN BY THE CONTRACTOR |
| (QUALIFIER) AND SIGNED IN ACCORDANCE WITH WPB FBC |
| 107.3.4.3, SCANNED AND UPLOADED TO PROJECT DOCS FOR |
| THIS REVIEW. PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE |
| SUBMITTED WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND |
| LICENSE NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A |
| PAPER PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE |
| BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO |
| ISSUANCE OF A PERMIT. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-243-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |
| 21030167 216 ASHWORTH ST |