Plan Review Details - Permit 21030128
Plan Review Stops For Permit 21030128
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2021-03-18 Cont ID  
Sent By jwitmer Date 2021-03-18 Time 10:04 Rev Time 0.00
Received By jwitmer Date 2021-03-18 Time 10:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-06 Cont ID  
Sent By jwitmer Date 2021-04-06 Time 15:19 Rev Time 0.00
Received By jwitmer Date 2021-04-06 Time 14:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By jwitmer Date 2021-03-18 Time 10:58 Rev Time 0.00
Received By jwitmer Date 2021-03-18 Time 10:02 Sent To  
Notes
2021-03-18 10:54:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21030128
 ADD: 1801 S. FLAGLER DR. # 1608
 CONT: COUNIHAN CONSTRUCTION LLC
 TEL: 561-722-6266
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) SHEET A-1 THE FLOOR PLAN INDICATES NEW FLOORING
 THROUGHOUT, TO BE DETERMINED. A SALES BROCHURE FOR
 WHISPER MAT CS FOR CERAMIC TILE. WHEN THE FLOOR PLAN
 STATES TO BE DETERMINED, THIS BECOMES AN UNKNOWN
 BECAUSE THE SUBMITTED BROCHURE IS FOR A SPECIFIC TYPE
 OF MATERIAL.
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES " THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION AND OR TBD". CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE B FLOOR INSULATION (FBC-B 2020)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723.UILDING OFFICIAL.
  
 2) DISCREPANCY IN THE SCOPE OF WORK. ON THE FLOOR PLAN
 SHEET A-1 THE GENERAL NOTE # 6 STATES NO EXTERIOR
 ENVELOPE WORK. THE PERMIT APPLICATION UNDER THE
 DESCRIPTION OF WORK STATES, REMODEL PER PLAN INCLUDING
 EXTERIOR WINDOW AND SLIDING DOORS. THERE IS NO PRODUCT
 APPROVAL FOR THE SLIDING GLASS DOORS. THERE IS
 SUBMITTED WITHIN THIS PERMIT PACKAGE
 PRODUCT APPROVALS WITH THE DESIGNERS ELECTRONIC
 SIGNATURE FOR NOA 20-0722.09 CGI WINDOWS. SENTINEL 110
 SINGLE HUNG WINDOWS L. M. I. & NOA 20-0406.08 CGI HEAVY
 DUTY TUBE MULLIONS. NEITHER REPORT HAS SHOWN COMPLIANCE
 WITH THE 2020 FBC-B SECTION 1405.13.1. PLEASE IDENTIFY
 ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER
 OF RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 3) 2020 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 3,1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 3.6.1. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 3.6.2. THERE IS NO OVERALL FLOOR PLAN FOR THE TOTAL
 FLOOR AREA OF THIS FLOOR, ZONES 4 & 5 NEED TO BE
 ESTABLISHED.
  
 4) COMPONENTS & CLADDING. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(A)
 EXTERIOR SLIDING DOORS
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-07 Cont ID  
Sent By equinone Date 2021-04-07 Time 11:04 Rev Time 0.00
Received By equinone Date 2021-04-07 Time 08:35 Sent To  
Notes
2021-04-07 11:04:25MUST COMPLY WITH NEC 2017

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-10 Cont ID  
Sent By equinone Date 2021-03-10 Time 08:53 Rev Time 0.00
Received By equinone Date 2021-03-10 Time 08:50 Sent To  
Notes
2021-03-10 08:54:02CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) E1 (GENERAL ELECTRICAL NOTES): NEW CODES ARE IN
 EFFECT. PLEASE CHANGE CODE NOTES TO REFER TO FBC 2020
 7TH EDITION AND NEC 2017.
 2) PLEASE SEE SIGNATURE COMMENTS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-08 Cont ID  
Sent By pleduc Date 2021-03-08 Time   Rev Time 0.00
Received By pleduc Date 2021-03-04 Time 16:01 Sent To  
Notes
2021-03-08 10:24:03COMPLY WITH 7TH ED OF THE FLORIDA FIRE PREVENTION CODE
  
 2018 NFPA 1 & 101 AND OTHER APPLICABLE CODES
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-12 Cont ID  
Sent By medwards Date 2021-04-12 Time 13:52 Rev Time 0.00
Received By medwards Date 2021-04-09 Time 13:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 15:13 Rev Time 0.00
Received By medwards Date 2021-04-06 Time 10:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-05 Cont ID  
Sent By lmarchan Date 2021-04-05 Time 12:26 Rev Time 0.00
Received By lmarchan Date 2021-03-03 Time 16:12 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-03-18 Cont ID  
Sent By jwitmer Date 2021-03-18 Time 10:04 Rev Time 0.00
Received By jwitmer Date 2021-03-18 Time 10:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2021-04-12 Cont ID  
Sent By medwards Date 2021-04-12 Time 13:51 Rev Time 0.00
Received By medwards Date 2021-04-12 Time 13:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 15:10 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-03-15 Cont ID  
Sent By medwards Date 2021-03-15 Time 11:53 Rev Time 0.00
Received By medwards Date 2021-03-15 Time 11:49 Sent To  
Notes
2021-03-15 11:54:48SEE SIGNATURE REVIEW COMMENT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-03-19 Cont ID  
Sent By ccole Date 2021-03-19 Time 13:02 Rev Time 0.00
Received By ccole Date 2021-03-19 Time 12:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-13 Cont ID  
Sent By medwards Date 2021-04-12 Time 13:51 Rev Time 0.00
Received By medwards Date 2021-04-12 Time 13:51 Sent To  
Notes
2021-04-12 13:52:16 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 15:11 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 15:11 Sent To  
Notes
2021-04-08 15:12:49SHEETS 002,003,004 MUST BE DIGITALLY SIGNED AND SEALED
 BY THE DESIGNER OR YOU MAY BRING ORIGINAL SIGNED AND
 SEALED PAPER DRAWINGS TO OUR OFFICE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-03 Cont ID  
Sent By medwards Date 2021-03-03 Time 16:42 Rev Time 0.00
Received By medwards Date 2021-03-03 Time 16:42 Sent To  
Notes
2021-03-03 16:44:18DESIGNER MUST EITHER DIGITALLY SIGN AND SEAL THE
 DRAWINGS AND SUBMIT THEM DIGITALLY OR THEY MUST SIGN
 AND SEAL THE ORIGINAL PAPER DRAWINGS AND BRING THEM TO
 THE OFFICE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2021-04-05 Cont ID  
Sent By kalexand Date 2021-04-05 Time 12:11 Rev Time 0.00
Received By aoliver Date 2021-04-05 Time 12:15 Sent To  
Notes
2021-04-05 12:12:26SCOPE OF WORK ON STATES "NO EXTERIOR ENVELOPE WORK" AO