Plan Review Details - Permit 21030009
Plan Review Stops For Permit 21030009
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-07-23 Cont ID  
Sent By jgomez Date 2021-07-23 Time 15:16 Rev Time 0.00
Received By jgomez Date 2021-07-22 Time 14:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-07-16 Cont ID  
Sent By jgomez Date 2021-07-16 Time 12:43 Rev Time 0.00
Received By jgomez Date 2021-07-16 Time 08:45 Sent To  
Notes
2021-07-16 12:47:56RESIDENTIAL(R3) ELEVATION CERTIFICATE. THIRD BUILDING
 REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
 SUBMITTAL #21030009 (MASTER 16061174).
  
  
 COMMENTS FOR REVISED ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR MAIN HOUSE:
  
 ORIGINAL COMMENT:
 3- - ELEVATION OF LOWEST MACHINERY OR EQUIPMENT SHOWN
 ON ITEM C2(E) DOESN'T MATCH ELEVATION SHOWN ON SURVEY
 SUBMITTED. REVISE AS REQUIRED.
 NOTE: CLARIFY WHAT ARE THE ELEVATIONS 7.40', 7.45' AND
 7.44' SHOWN ON THE SURVEY NEXT TO THE A/C PADS?.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE TO REVISED SUBMITTAL:
 COMMENT FOR ITEM C2:E STATES "A/C EQUIPMENT PAD".
 ACCORDING TO PHOTOS SUBMITTED, THE A/C EQUIPMENT IS NOT
 MOUNTED ON THE CONCRETE PAD. IT IS MOUNTED ON A/C
 STANDS. THIS NEEDS TO BE CLEARLY IDENTIFIED ON THE
 COMMENTS SECTION.
 NOTE: INFORMATION SHOWN ON SURVEY SUBMITTED IS NOT
 CLEAR ALSO. IT SHOWS 3 ELEVATION MARKS (7.24', 7.27',
 7.30') ON THE CONCRETE SLAB AND ANOTHER LOWER ELEVATION
 (5.65') POINTING TO THE CONCRETE SLAB. WHAT IS THE
 CORRECT CONCRETE PAD ELEVATION?
  
  
  
 REVISE SURVEY SUBMITTED:
  
 ORIGINAL COMMENT:
 2- FLOOD ZONE INFORMATION SPECIFIED AT THE BOTTOM
 MIDDLE OF SHEET IS OLD. THE CURRENT FLOOD MAP WENT INTO
 EFFECT ON 10/05/2017. REVISE ALL FLOOD INFORMATION AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE TO REVISED SUBMITTAL:
 REPEAT COMMENT. NOT ADDRESSED. THE FLOOD INFORMATION
 WAS NOT UPDATED.
 FLOOD ZONE A5. COMMUNITY NUMBER: 120229. PANEL:
 1202290020. SUFFIX: B
 IS OLD INFORMATION. SEE SECTION B OF THE ELEVATION
 CERTIFICATE FOR CORRECT UPDATED INFORMATION AND REVISE
 AS REQUIRED.
  
 NEW COMMENTS BASED ON REVISED SURVEY:
 3- SURVEY SUBMITTED NOW SHOWS A NEW BENCHMARK "FOUND
 PK/TAB SITE BENCHMARK ELEVATION =24.40'.
 WHAT IS THE ELEVATION DATUM USED FOR THIS ELEVATION
 24.40'?
 WHYS IS THIS ELEVATION SO HIGH COMPARED TO THE OTHER
 ELEVATIONS SHOWN ON THE SURVEY?
  
 4- INFORMATION SHOWN ON SURVEY SUBMITTED IS NOT CLEAR.
 IT SHOWS 3 ELEVATION MARKS (7.24', 7.27', 7.30') ON THE
 CONCRETE SLAB AND ANOTHER LOWER ELEVATION (5.65')
 POINTING TO THE CONCRETE SLAB.
 WHAT IS THE CORRECT SLAB ELEVATION?
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-25 Cont ID  
Sent By jgomez Date 2021-06-25 Time 13:58 Rev Time 0.00
Received By jgomez Date 2021-06-25 Time 13:06 Sent To  
Notes
2021-06-25 14:00:3906/25/21 RESPONSE TO REAGAN BRENNER:
  
 GOOD MORNING TO ALL. MR. GOMEZ, I AM WORKING ON THE
 REVISION OF THE GARAGE ELEVATION CERTIFICATE FOR MR.
 AND MRS. FARINO THIS MORNING. I WOULD LIKE TO ASK FOR A
 HELP WHILE THE NEW PHOTO IS PENDING.
 I HAVE REVISED THE VENTING INFORMATION IN SECTION A8 A
 & C. AS THIS IS NOT FINALIZED, MAY I ASK FOR YOUR
 REVIEW TO ENSURE WE ARE ON FIRM GROUND TO MOVE FORWARD?
 IF SO, WE WILL ADD THE UPDATED PHOTOGRAPH PROVIDED BY
 MR. AND MRS. FARINO SHOWING THE 6TH VENT ADDED. WILL
 THIS BE SUFFICIENT FOR THEIR SUBMITTAL? WE REALLY WANT
 TO HELP GET THEIR PROJECT COMPLETED FOR THEM. THANK YOU
 SO MUCH FOR YOUR GUIDANCE.
 THANK YOU,
 REAGAN BRENNER
 COMPASS SURVEYING
 6250 NORTH MILITARY TRAIL, SUITE 102
 WEST PALM BEACH, FL 33407
 1-800-226-4807
  
  
  
 GOOD AFTERNOON MR. BRENNER,
 THE ELEVATION CERTIFICATE YOU SENT ME DOESN'T PROVIDE
 ANY INFORMATION IN SECTION A8.
 RIGHT NOW, WE NEED TO WAIT UNTIL THE NEW FLOOD VENT IS
 INSTALLED. COORDINATED WITH MRS. FARINO. SHE ALSO HAS A
 COPY OF THE REVISED GARAGE SHOWING THE CORRECT GARAGE
 SQUARE FOOTAGE AND NUMBER OF REQUIRED FLOOD VENTS.
 ATTACHED PLEASE FIND A COPY OF THE FLOOD VENT PRODUCT
 APPROVAL SO YOU CAN FIND THE NET AREA OF EACH VENT.
 ALSO, I HAVE ATTACHED AC COPY OF THE FEMA ELEVATION
 CERTIFICATE INSTRUCTIONS. THE INSTRUCTIONS WILL HELP
 YOU TO SEE WHAT INFORMATION NEEDS TO BE COMPLETED AND
 HOW. THIS IS MY PERSONAL HIGHLIGHTED COPY (DISREGARD MY
 HIGHLIGHTING AND NOTES).
  
 IN ADDITION, I WANT TO EMPHASIZE THAT WE NEED AN
 ELEVATION CERTIFICATE FOR THE MAIN HOUSE AND ANOTHER
 ONE FOR THE GARAGE.
 PLEASE SEE COMMENTS BELOW FROM MY LAST REVIEW. CHECK
 THAT ALL INFORMATION IS COORDINATED WHEN YOU ARE READY
 TO PREPARE THE FINAL SURVEY AND FINAL ELEVATIONS
 CERTIFICATES.
 YOU CAN CONTACT ME IF YOU HAVE A SPECIFIC QUESTION.
 THANK YOU
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 RESIDENTIAL(R3) ELEVATION CERTIFICATE. SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
 SUBMITTAL #21030009 (MASTER 16061174).
  
 COMMENTS FOR REVISED ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR MAIN HOUSE:
  
 1- ITEM A3 ON PAGE 1 OF 6 IS INCORRECT. THIS ITEM IS
 ASKING FOR THE PROPERTY DESCRIPTION. FORM SUBMITTED
 SAYS 1B. WHAT IS 1B? REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH
 FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS
 REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT SHOWN ON
 ITEM C2(E) DOESN'T MATCH ELEVATION SHOWN ON SURVEY
 SUBMITTED. REVISE AS REQUIRED.
 NOTE: CLARIFY WHAT ARE THE ELEVATIONS 7.40', 7.45' AND
 7.44' SHOWN ON THE SURVEY NEXT TO THE A/C PADS?.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT DOESN'T
 MEET THE CITY FREEBOARD REQUIREMENT OF 1 FOOT ABOVE THE
 BASE FLOOD ELEVATION AS REQUIRED BY CITY ORDINANCE
 4658-16.
 EQUIPMENT NEEDS TO BE RAISED AND ELEVATION CERTIFICATE
 NEEDS TO BE REVISED ACCORDINGLY.
 NOTE: ORIGINAL PLANS WERE APPROVED BEFORE THE NEW FLOOD
 MAPS TOOK EFFECT. PREVIOUS MAPS WERE BASED ON NGVD 1929
 ELEVATION DATUM. BASED ON NGVD, THE BASE FLOOD
 ELEVATION WAS 7 FEET AND THE REQUIRED FINISHED FLOOR
 ELEVATION WAS 8 FEET NGVD.
  
 5- COMMENTS ON SECTION D ON PAGE 2 OF 6 SPECIFIES A/C
 EQUIPMENT PAD LOCATED EASTERLY SIDE OF HOUSE. BASED ON
 SURVEY SUBMITTED, THIS IS INCORRECT. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 6- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM
 C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED
 BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS.
 PROVIDE SURVEY SHOWING THOSE ELEVATIONS.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 7- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO
 BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION.
 SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019
 EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY
 THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND
 SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED
 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE
 BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT
 PHOTOS.
 NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE
 AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE
 YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF
 CERTIFICATION.
  
  
 COMMENTS FOR ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR GARAGE:
  
 1- REVISE/CLARIFY DESCRIPTION ON ITEM A4 ON PAGE 1 OF
 6. WHAT IS A "DEATTACHED GARAGE"?. REVISE/CLARIFY AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ITEM A7 ON PAGE 1 OF 6 IS INCORRECT. THERE IS NOT
 CRAWLSPACE IN THE GARAGE. REVISE AS REQUIRED.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 3- SQUARE FOOTAGE SPECIFIED ON ITEM A8(A) ON PAGE 1 OF
 6 IS INCORRECT. ACCORDING TO SURVEY SUBMITTED THE
 GARAGE SQUARE FOOTAGE IS 733 S.F. NOT 586 S.F. REVISE
 AS REQUIRED. NOTE: SQUARE FOOTAGE IS TAKEN FROM
 EXTERIOR WALLS.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 4- TOTAL NET AREA OF FLOOD OPENINGS SPECIFIED ON ITEM
 A8(C) ON PAGE 1 OF 6 IS INCORRECT. SURVEYOR PROVIDED
 COMMENT AT BOTTOM OF SECTION D STATING "VENTING BASED
 ON FLOOD SOLUTIONS VENTS FS 1412 PER CLIENTS".
 ACCORDING TO ENGINEERED VENT PRODUCT APPROVAL FL17588
 SUBMITTED WITH PERMIT APPLICATION #16061174 THE
 SELECTED VENT FS-1412 HAS A NET FREE AREA OF 106.7 SQ.
 IN. PER VENT. IF THERE ARE 5 VENTS, THEN THE TOTAL NET
 AREA IS 533.5 SQ. IN. NOT 1000 SQ. IN. REVISE AS
 REQUIRED. NOTE: COORDINATE WITH ITEM #5 BELOW.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 5- BASED ON ITEMS #3 AND #4 ABOVE IT LOOKS LIKE THE
 ENGINEER OF RECORD FOR PERMIT #16061174 NEEDS TO REVISE
 THE PLANS AND NUMBER OF REQUIRED FLOOD VENTS. SHEET A-2
 SPECIFIES A GARAGE AREA OF 586 S.F. ALSO, ENGINEER
 SHOWS 5 FLOOD VENTS (MODEL FS-1412 PRODUCT APPROVAL
 FL17588) ON WEST AND EAST WALLS.
 ENGINEER OF RECORD NEEDS TO PROVIDE CORRECT GARAGE
 SQUARE FOOTAGE AND REVISE THE NUMBER OF REQUIRED VENTS.
 SUBMIT REVISE PLANS FOR REVIEW. REVISION FEES APPLY.
 SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: SQUARE FOOTAGE IS TAKEN FROM EXTERIOR WALLS.
  
 6- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH
 FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS
 REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7- ITEM C2(B) SHOWN ON PAGE 2 OF 6 IS INCORRECT. THERE
 IS NOT NEXT HIGHER FLOOR IN THE GARAGE. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 8- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM
 C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED
 BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS.
 PROVIDE SURVEY SHOWING THOSE ELEVATIONS.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 9- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO
 BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION.
 SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019
 EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY
 THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND
 SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED
 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE
 BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT
 PHOTOS.
 NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE
 AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE
 YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF
 CERTIFICATION.
  
  
 REVISE SURVEY SUBMITTED:
  
 1- SURVEY SUBMITTED IS AN SPECIFIC PURPOSE
 SURVEY-"NORTHERLY FORMBOARDTIE IN". SEE TOP OF SURVEY.
 IF THIS SURVEY IS FOR ELEVATION CERTIFICATE FINISHED
 CONSTRUCTION, THEN THE SURVEY SHOULD BE A FINAL SURVEY
 AS WELL NOT A FORMBOARD SURVEY. PROVIDE FINAL SURVEY.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- FLOOD ZONE INFORMATION SPECIFIED AT THE BOTTOM
 MIDDLE OF SHEET IS OLD. THE CURRENT FLOOD MAP WENT INTO
 EFFECT ON 10/05/2017. REVISE ALL FLOOD INFORMATION AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SURVEY DOESN'T MATCH APPROVED PLANS AND PHOTOS SHOWN
 ON THE ELEVATION CERTIFICATES. THERE IS A BREEZEWAY
 CONNECTING THE GARAGE TO THE MAIN HOUSE. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE REVISED SURVEY WITH SURVEYORS ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: THIS CAN BE ACHIEVED BY UPLOADING DOCUMENTS WITH
 SURVEYOR'S DIGITAL SIGNATURE OR BY PROVIDING HARD COPY
 PLANS/DOCUMENTS WITH SURVEYOR'S ORIGINAL
 SEAL/SIGNATURE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-18 Cont ID  
Sent By jgomez Date 2021-05-18 Time 15:21 Rev Time 0.00
Received By jgomez Date 2021-05-18 Time 09:36 Sent To  
Notes
2021-05-18 15:23:49RESIDENTIAL(R3) ELEVATION CERTIFICATE. SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
 SUBMITTAL #21030009 (MASTER 16061174).
  
 COMMENTS FOR REVISED ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR MAIN HOUSE:
  
 1- ITEM A3 ON PAGE 1 OF 6 IS INCORRECT. THIS ITEM IS
 ASKING FOR THE PROPERTY DESCRIPTION. FORM SUBMITTED
 SAYS 1B. WHAT IS 1B? REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH
 FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS
 REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT SHOWN ON
 ITEM C2(E) DOESN'T MATCH ELEVATION SHOWN ON SURVEY
 SUBMITTED. REVISE AS REQUIRED.
 NOTE: CLARIFY WHAT ARE THE ELEVATIONS 7.40', 7.45' AND
 7.44' SHOWN ON THE SURVEY NEXT TO THE A/C PADS?.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT DOESN'T
 MEET THE CITY FREEBOARD REQUIREMENT OF 1 FOOT ABOVE THE
 BASE FLOOD ELEVATION AS REQUIRED BY CITY ORDINANCE
 4658-16.
 EQUIPMENT NEEDS TO BE RAISED AND ELEVATION CERTIFICATE
 NEEDS TO BE REVISED ACCORDINGLY.
 NOTE: ORIGINAL PLANS WERE APPROVED BEFORE THE NEW FLOOD
 MAPS TOOK EFFECT. PREVIOUS MAPS WERE BASED ON NGVD 1929
 ELEVATION DATUM. BASED ON NGVD, THE BASE FLOOD
 ELEVATION WAS 7 FEET AND THE REQUIRED FINISHED FLOOR
 ELEVATION WAS 8 FEET NGVD.
  
 5- COMMENTS ON SECTION D ON PAGE 2 OF 6 SPECIFIES A/C
 EQUIPMENT PAD LOCATED EASTERLY SIDE OF HOUSE. BASED ON
 SURVEY SUBMITTED, THIS IS INCORRECT. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 6- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM
 C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED
 BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS.
 PROVIDE SURVEY SHOWING THOSE ELEVATIONS.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 7- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO
 BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION.
 SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019
 EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY
 THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND
 SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED
 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE
 BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT
 PHOTOS.
 NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE
 AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE
 YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF
 CERTIFICATION.
  
  
 COMMENTS FOR ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR GARAGE:
  
 1- REVISE/CLARIFY DESCRIPTION ON ITEM A4 ON PAGE 1 OF
 6. WHAT IS A "DEATTACHED GARAGE"?. REVISE/CLARIFY AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ITEM A7 ON PAGE 1 OF 6 IS INCORRECT. THERE IS NOT
 CRAWLSPACE IN THE GARAGE. REVISE AS REQUIRED.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 3- SQUARE FOOTAGE SPECIFIED ON ITEM A8(A) ON PAGE 1 OF
 6 IS INCORRECT. ACCORDING TO SURVEY SUBMITTED THE
 GARAGE SQUARE FOOTAGE IS 733 S.F. NOT 586 S.F. REVISE
 AS REQUIRED. NOTE: SQUARE FOOTAGE IS TAKEN FROM
 EXTERIOR WALLS.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 4- TOTAL NET AREA OF FLOOD OPENINGS SPECIFIED ON ITEM
 A8(C) ON PAGE 1 OF 6 IS INCORRECT. SURVEYOR PROVIDED
 COMMENT AT BOTTOM OF SECTION D STATING "VENTING BASED
 ON FLOOD SOLUTIONS VENTS FS 1412 PER CLIENTS".
 ACCORDING TO ENGINEERED VENT PRODUCT APPROVAL FL17588
 SUBMITTED WITH PERMIT APPLICATION #16061174 THE
 SELECTED VENT FS-1412 HAS A NET FREE AREA OF 106.7 SQ.
 IN. PER VENT. IF THERE ARE 5 VENTS, THEN THE TOTAL NET
 AREA IS 533.5 SQ. IN. NOT 1000 SQ. IN. REVISE AS
 REQUIRED. NOTE: COORDINATE WITH ITEM #5 BELOW.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 5- BASED ON ITEMS #3 AND #4 ABOVE IT LOOKS LIKE THE
 ENGINEER OF RECORD FOR PERMIT #16061174 NEEDS TO REVISE
 THE PLANS AND NUMBER OF REQUIRED FLOOD VENTS. SHEET A-2
 SPECIFIES A GARAGE AREA OF 586 S.F. ALSO, ENGINEER
 SHOWS 5 FLOOD VENTS (MODEL FS-1412 PRODUCT APPROVAL
 FL17588) ON WEST AND EAST WALLS.
 ENGINEER OF RECORD NEEDS TO PROVIDE CORRECT GARAGE
 SQUARE FOOTAGE AND REVISE THE NUMBER OF REQUIRED VENTS.
 SUBMIT REVISE PLANS FOR REVIEW. REVISION FEES APPLY.
 SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: SQUARE FOOTAGE IS TAKEN FROM EXTERIOR WALLS.
  
 6- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH
 FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS
 REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7- ITEM C2(B) SHOWN ON PAGE 2 OF 6 IS INCORRECT. THERE
 IS NOT NEXT HIGHER FLOOR IN THE GARAGE. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 8- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM
 C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED
 BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS.
 PROVIDE SURVEY SHOWING THOSE ELEVATIONS.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 9- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO
 BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION.
 SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019
 EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY
 THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND
 SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED
 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE
 BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT
 PHOTOS.
 NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE
 AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE
 YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF
 CERTIFICATION.
  
  
 REVISE SURVEY SUBMITTED:
  
 1- SURVEY SUBMITTED IS AN SPECIFIC PURPOSE
 SURVEY-"NORTHERLY FORMBOARDTIE IN". SEE TOP OF SURVEY.
 IF THIS SURVEY IS FOR ELEVATION CERTIFICATE FINISHED
 CONSTRUCTION, THEN THE SURVEY SHOULD BE A FINAL SURVEY
 AS WELL NOT A FORMBOARD SURVEY. PROVIDE FINAL SURVEY.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- FLOOD ZONE INFORMATION SPECIFIED AT THE BOTTOM
 MIDDLE OF SHEET IS OLD. THE CURRENT FLOOD MAP WENT INTO
 EFFECT ON 10/05/2017. REVISE ALL FLOOD INFORMATION AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SURVEY DOESN'T MATCH APPROVED PLANS AND PHOTOS SHOWN
 ON THE ELEVATION CERTIFICATES. THERE IS A BREEZEWAY
 CONNECTING THE GARAGE TO THE MAIN HOUSE. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE REVISED SURVEY WITH SURVEYORS ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: THIS CAN BE ACHIEVED BY UPLOADING DOCUMENTS WITH
 SURVEYOR'S DIGITAL SIGNATURE OR BY PROVIDING HARD COPY
 PLANS/DOCUMENTS WITH SURVEYOR'S ORIGINAL
 SEAL/SIGNATURE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-10 Cont ID  
Sent By jgomez Date 2021-03-11 Time 14:04 Rev Time 0.00
Received By jgomez Date 2021-03-10 Time 10:55 Sent To  
Notes
2021-03-10 14:05:41REVISED 03/11/21. JG.
 RESIDENTIAL (R3) ELEVATION CERTIFICATE BUILDING REVIEW
 COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
 SUBMITTAL #21030009 (MASTER 16061174)
  
 1- ELEVATION CERTIFICATE WAS CERTIFIED BY THE SURVEYOR
 ON 02/24/21. SURVEYOR USED OLD FORM WITH EXPIRATION
 DATE NOVEMBER 30, 2018. SURVEYOR NEEDS TO USE THE
 UPDATED ELEVATION CERTIFICATE FORM WITH EXPIRATION DATE
 NOVEMBER 30, 2022). COMPLETE REVISED FORM AND RESUBMIT.
 SEE FEMA 2019 ELEVATION CERTIFICATE AND INSTRUCTIONS
 2019 EDITION.
  
 2- SURVEYOR COMPLETED SECTION C2 A TRHU H USING NGVD
 1929.
 SECTION C2 A TRHU H MUST USE THE SAME DATUM ON WHICH
 THE BFE IS BASED IN ITEM B9. SURVEYOR TO REVISE AS
 REQUIRED. ALSO, PROVIDE SURVEY SHOWING ALL THE
 ELEVATIONS AS REQUIRED BY CITY PROCEDURES TO VERIFY
 COMPLIANCE.
 SEE FEMA 2019 ELEVATION CERTIFICATE AND INSTRUCTIONS
 2019 EDITION.
  
 NOTE:
 ORIGINAL ADDITION PERMIT APPLICATION WAS REVIEWED UNDER
 PERMIT #16061174. PLAN REVIEW WAS DONE BASED ON NGVD
 1929 VERTICAL DATUM.
 PLEASE PROVIDE CONVERSION CALCULATIONS FROM NAVD 1988
 TO NGVD 1929 VERTICAL DATUM IN THE COMMENTS SECTION D.
  
 3- SQUARE FOOTAGE OF ATTACHED GARAGE DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. ALSO, SURVEY SUBMITTED
 DOESN'T SHOW AN ATTACHED GARAGE.
 PROVIDE UPDATED SURVEY.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE:
 IT LOOKS LIKE THE GARAGE MAY NOT BE CONSIDERED AS AN
 ATTACHED GARAGE. THE GARAGE IS CONNECTED TO THE MAIN
 HOUSE BY A BREEZEWAY. IT DOESN'T SEEM TO BE
 STRUCTURALLY CONNECTED TO THE MAIN HOUSE. GARAGE MAY
 REQUIRE A SEPARATE ELEVATION CERTIFICATE. THIS WILL BE
 DISCUSSED WITH THE BUILDING OFFICIAL.
  
 4- PHOTOGRAPHS SUBMITTED DON'T PROVIDE ANY DATE WHEN
 THEY WERE TAKEN. PHOTOS NEED TO BE TAKEN WITHIN 90 DAYS
 FROM DATE OF CERTIFICATION. REVISE AS REQUIRED.
 SEE FEMA 2019 ELEVATION CERTIFICATE AND INSTRUCTIONS
 2019 EDITION.
  
 5- ITEM A9. B) AND A9. D) SPECIFY NO FLOOD OPENINGS.
 ACCORDING TO SHEET A-2 OF REVISION #18040410 THERE ARE
 4 ENGINEERED FLOOD VENTS INSTALLED IN THE GARAGE. THIS
 WILL NEED TO BE ADDRESSED BY THE OWNER/CONTRACTOR
 BECAUSE THE GARAGE IS BELOW THE BASE FLOOD ELEVATION.
 ELEVATION CERTIFICATE MAY NEED TO BE REVISED BASED ON
 THE REVISED PLANS.
  
 6- SURVEYOR INDICATES THAT THE LOWEST ELEVATION OF
 MACHINERY OR EQUIPMENT IS 6.77 (NGVD 1929). THE A/C
 EQUIPMENT ELEVATION DOESN'T COMPLY WITH THE CITY
 REQUIREMENTS. EQUIPMENT NEEDS TO BE RAISED AND REVISED
 ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-07-23 Cont ID  
Sent By jgomez Date 2021-07-23 Time 15:17 Rev Time 0.00
Received By jgomez Date 2021-07-22 Time 14:18 Sent To I
Notes
2021-07-22 14:18:5907/22/21 MET W/ MRS. KIM FARINO. DROPPED OFF FINAL
 ELEVATION CERTIFICATE AND SURVEY. JG.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-16 Cont ID  
Sent By jgomez Date 2021-07-16 Time 12:48 Rev Time 0.00
Received By jgomez Date 2021-07-08 Time 10:08 Sent To I
Notes
2021-07-08 10:08:4707/08/21 MET W/ MRS. KIM FARINO. DROPPED OFF FINAL
 ELEVATION CERTIFICATE AND SURVEY. JG.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-25 Cont ID  
Sent By jgomez Date 2021-06-25 Time 14:01 Rev Time 0.00
Received By jgomez Date 2021-06-25 Time 13:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-17 Cont ID  
Sent By jgomez Date 2021-05-17 Time 15:15 Rev Time 0.00
Received By jgomez Date 2021-05-10 Time 16:35 Sent To  
Notes
2021-05-17 15:18:3805/17/21 OWNER DROPPED OFF HOUSE AND GARAGE ELEVATION
 CERTIFICATES WITH SURVEYOR'S EMBOSSED SEAL AND
 SIGNATURE DATED 05/06/21. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-10 Cont ID  
Sent By jgomez Date 2021-03-10 Time 14:05 Rev Time 0.00
Received By jgomez Date 2021-03-01 Time 06:37 Sent To I
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2021-07-23 Cont ID  
Sent By jgomez Date 2021-07-23 Time 15:16 Rev Time 0.00
Received By jgomez Date 2021-07-23 Time 15:16 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2021-07-16 Cont ID  
Sent By jgomez Date 2021-07-16 Time 12:48 Rev Time 0.00
Received By jgomez Date 2021-07-16 Time 08:46 Sent To  
Notes
2021-07-16 12:48:26RESIDENTIAL(R3) ELEVATION CERTIFICATE. THIRD BUILDING
 REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
 SUBMITTAL #21030009 (MASTER 16061174).
  
  
 COMMENTS FOR REVISED ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR MAIN HOUSE:
  
 ORIGINAL COMMENT:
 3- - ELEVATION OF LOWEST MACHINERY OR EQUIPMENT SHOWN
 ON ITEM C2(E) DOESN'T MATCH ELEVATION SHOWN ON SURVEY
 SUBMITTED. REVISE AS REQUIRED.
 NOTE: CLARIFY WHAT ARE THE ELEVATIONS 7.40', 7.45' AND
 7.44' SHOWN ON THE SURVEY NEXT TO THE A/C PADS?.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE TO REVISED SUBMITTAL:
 COMMENT FOR ITEM C2:E STATES "A/C EQUIPMENT PAD".
 ACCORDING TO PHOTOS SUBMITTED, THE A/C EQUIPMENT IS NOT
 MOUNTED ON THE CONCRETE PAD. IT IS MOUNTED ON A/C PADS.
 THIS NEEDS TO BE CLEARLY IDENTIFIED ON THE COMMENTS
 SECTION.
 NOTE: INFORMATION SHOWN ON SURVEY SUBMITTED IS NOT
 CLEAR ALSO. IT SHOWS 3 ELEVATION MARKS (7.24', 7.27',
 7.30') ON THE CONCRETE SLAB AND ANOTHER LOWER ELEVATION
 (5.65') POINTING TO THE CONCRETE SLAB. WHAT IS THE
 CORRECT CONCRETE PAD ELEVATION?
  
  
  
 REVISE SURVEY SUBMITTED:
  
 ORIGINAL COMMENT:
 2- FLOOD ZONE INFORMATION SPECIFIED AT THE BOTTOM
 MIDDLE OF SHEET IS OLD. THE CURRENT FLOOD MAP WENT INTO
 EFFECT ON 10/05/2017. REVISE ALL FLOOD INFORMATION AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE TO REVISED SUBMITTAL:
 REPEAT COMMENT. NOT ADDRESSED. THE FLOOD INFORMATION
 WAS NOT UPDATED.
 FLOOD ZONE A5. COMMUNITY NUMBER: 120229. PANEL:
 1202290020. SUFFIX: B
 IS OLD INFORMATION. SEE SECTION B OF THE ELEVATION
 CERTIFICATE FOR CORRECT UPDATED INFORMATION AND REVISE
 AS REQUIRED.
  
 NEW COMMENTS BASED ON REVISED SURVEY:
 3- SURVEY SUBMITTED NOW SHOWS A NEW BENCHMARK "FOUND
 PK/TAB SITE BENCHMARK ELEVATION =24.40'.
 WHAT IS THE ELEVATION DATUM USED FOR THIS ELEVATION
 24.40'?
 WHYS IS THIS ELEVATION SO HIGH COMPARED TO THE OTHER
 ELEVATIONS SHOWN ON THE SURVEY?
  
 4- INFORMATION SHOWN ON SURVEY SUBMITTED IS NOT CLEAR.
 IT SHOWS 3 ELEVATION MARKS (7.24', 7.27', 7.30') ON THE
 CONCRETE SLAB AND ANOTHER LOWER ELEVATION (5.65')
 POINTING TO THE CONCRETE SLAB.
 WHAT IS THE CORRECT SLAB ELEVATION?
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2021-06-25 Cont ID  
Sent By jgomez Date 2021-06-25 Time 14:05 Rev Time 0.00
Received By jgomez Date 2021-06-25 Time 14:05 Sent To  
Notes
2021-06-25 14:06:2106/25/21 RESPONSE TO REAGAN BRENNER:
  
 GOOD MORNING TO ALL. MR. GOMEZ, I AM WORKING ON THE
 REVISION OF THE GARAGE ELEVATION CERTIFICATE FOR MR.
 AND MRS. FARINO THIS MORNING. I WOULD LIKE TO ASK FOR A
 HELP WHILE THE NEW PHOTO IS PENDING.
 I HAVE REVISED THE VENTING INFORMATION IN SECTION A8 A
 & C. AS THIS IS NOT FINALIZED, MAY I ASK FOR YOUR
 REVIEW TO ENSURE WE ARE ON FIRM GROUND TO MOVE FORWARD?
 IF SO, WE WILL ADD THE UPDATED PHOTOGRAPH PROVIDED BY
 MR. AND MRS. FARINO SHOWING THE 6TH VENT ADDED. WILL
 THIS BE SUFFICIENT FOR THEIR SUBMITTAL? WE REALLY WANT
 TO HELP GET THEIR PROJECT COMPLETED FOR THEM. THANK YOU
 SO MUCH FOR YOUR GUIDANCE.
 THANK YOU,
 REAGAN BRENNER
 COMPASS SURVEYING
 6250 NORTH MILITARY TRAIL, SUITE 102
 WEST PALM BEACH, FL 33407
 1-800-226-4807
  
  
  
 GOOD AFTERNOON MR. BRENNER,
 THE ELEVATION CERTIFICATE YOU SENT ME DOESN'T?T PROVIDE
 ANY INFORMATION IN SECTION A8.
 RIGHT NOW, WE NEED TO WAIT UNTIL THE NEW FLOOD VENT IS
 INSTALLED. COORDINATED WITH MRS. FARINO. SHE ALSO HAS A
 COPY OF THE REVISED GARAGE SHOWING THE CORRECT GARAGE
 SQUARE FOOTAGE AND NUMBER OF REQUIRED FLOOD VENTS.
 ATTACHED PLEASE FIND A COPY OF THE FLOOD VENT PRODUCT
 APPROVAL SO YOU CAN FIND THE NET AREA OF EACH VENT.
 ALSO, I HAVE ATTACHED AC COPY OF THE FEMA ELEVATION
 CERTIFICATE INSTRUCTIONS. THE INSTRUCTIONS WILL HELP
 YOU TO SEE WHAT INFORMATION NEEDS TO BE COMPLETED AND
 HOW. THIS IS MY PERSONAL HIGHLIGHTED COPY (DISREGARD MY
 HIGHLIGHTING AND NOTES).
  
 IN ADDITION, I WANT TO EMPHASIZE THAT WE NEED AN
 ELEVATION CERTIFICATE FOR THE MAIN HOUSE AND ANOTHER
 ONE FOR THE GARAGE.
 PLEASE SEE COMMENTS BELOW FROM MY LAST REVIEW. CHECK
 THAT ALL INFORMATION IS COORDINATED WHEN YOU ARE READY
 TO PREPARE THE FINAL SURVEY AND FINAL ELEVATIONS
 CERTIFICATES.
 YOU CAN CONTACT ME IF YOU HAVE A SPECIFIC QUESTION.
 THANK YOU
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 RESIDENTIAL(R3) ELEVATION CERTIFICATE. SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
 SUBMITTAL #21030009 (MASTER 16061174).
  
 COMMENTS FOR REVISED ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR MAIN HOUSE:
  
 1- ITEM A3 ON PAGE 1 OF 6 IS INCORRECT. THIS ITEM IS
 ASKING FOR THE PROPERTY DESCRIPTION. FORM SUBMITTED
 SAYS 1B. WHAT IS 1B? REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH
 FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS
 REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT SHOWN ON
 ITEM C2(E) DOESN'T MATCH ELEVATION SHOWN ON SURVEY
 SUBMITTED. REVISE AS REQUIRED.
 NOTE: CLARIFY WHAT ARE THE ELEVATIONS 7.40', 7.45' AND
 7.44' SHOWN ON THE SURVEY NEXT TO THE A/C PADS?.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT DOESN'T
 MEET THE CITY FREEBOARD REQUIREMENT OF 1 FOOT ABOVE THE
 BASE FLOOD ELEVATION AS REQUIRED BY CITY ORDINANCE
 4658-16.
 EQUIPMENT NEEDS TO BE RAISED AND ELEVATION CERTIFICATE
 NEEDS TO BE REVISED ACCORDINGLY.
 NOTE: ORIGINAL PLANS WERE APPROVED BEFORE THE NEW FLOOD
 MAPS TOOK EFFECT. PREVIOUS MAPS WERE BASED ON NGVD 1929
 ELEVATION DATUM. BASED ON NGVD, THE BASE FLOOD
 ELEVATION WAS 7 FEET AND THE REQUIRED FINISHED FLOOR
 ELEVATION WAS 8 FEET NGVD.
  
 5- COMMENTS ON SECTION D ON PAGE 2 OF 6 SPECIFIES A/C
 EQUIPMENT PAD LOCATED EASTERLY SIDE OF HOUSE. BASED ON
 SURVEY SUBMITTED, THIS IS INCORRECT. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 6- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM
 C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED
 BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS.
 PROVIDE SURVEY SHOWING THOSE ELEVATIONS.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 7- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO
 BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION.
 SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019
 EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY
 THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND
 SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED
 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE
 BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT
 PHOTOS.
 NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE
 AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE
 YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF
 CERTIFICATION.
  
  
 COMMENTS FOR ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR GARAGE:
  
 1- REVISE/CLARIFY DESCRIPTION ON ITEM A4 ON PAGE 1 OF
 6. WHAT IS A "DEATTACHED GARAGE"?. REVISE/CLARIFY AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ITEM A7 ON PAGE 1 OF 6 IS INCORRECT. THERE IS NOT
 CRAWLSPACE IN THE GARAGE. REVISE AS REQUIRED.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 3- SQUARE FOOTAGE SPECIFIED ON ITEM A8(A) ON PAGE 1 OF
 6 IS INCORRECT. ACCORDING TO SURVEY SUBMITTED THE
 GARAGE SQUARE FOOTAGE IS 733 S.F. NOT 586 S.F. REVISE
 AS REQUIRED. NOTE: SQUARE FOOTAGE IS TAKEN FROM
 EXTERIOR WALLS.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 4- TOTAL NET AREA OF FLOOD OPENINGS SPECIFIED ON ITEM
 A8(C) ON PAGE 1 OF 6 IS INCORRECT. SURVEYOR PROVIDED
 COMMENT AT BOTTOM OF SECTION D STATING "VENTING BASED
 ON FLOOD SOLUTIONS VENTS FS 1412 PER CLIENTS".
 ACCORDING TO ENGINEERED VENT PRODUCT APPROVAL FL17588
 SUBMITTED WITH PERMIT APPLICATION #16061174 THE
 SELECTED VENT FS-1412 HAS A NET FREE AREA OF 106.7 SQ.
 IN. PER VENT. IF THERE ARE 5 VENTS, THEN THE TOTAL NET
 AREA IS 533.5 SQ. IN. NOT 1000 SQ. IN. REVISE AS
 REQUIRED. NOTE: COORDINATE WITH ITEM #5 BELOW.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 5- BASED ON ITEMS #3 AND #4 ABOVE IT LOOKS LIKE THE
 ENGINEER OF RECORD FOR PERMIT #16061174 NEEDS TO REVISE
 THE PLANS AND NUMBER OF REQUIRED FLOOD VENTS. SHEET A-2
 SPECIFIES A GARAGE AREA OF 586 S.F. ALSO, ENGINEER
 SHOWS 5 FLOOD VENTS (MODEL FS-1412 PRODUCT APPROVAL
 FL17588) ON WEST AND EAST WALLS.
 ENGINEER OF RECORD NEEDS TO PROVIDE CORRECT GARAGE
 SQUARE FOOTAGE AND REVISE THE NUMBER OF REQUIRED VENTS.
 SUBMIT REVISE PLANS FOR REVIEW. REVISION FEES APPLY.
 SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: SQUARE FOOTAGE IS TAKEN FROM EXTERIOR WALLS.
  
 6- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH
 FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS
 REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7- ITEM C2(B) SHOWN ON PAGE 2 OF 6 IS INCORRECT. THERE
 IS NOT NEXT HIGHER FLOOR IN THE GARAGE. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 8- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM
 C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED
 BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS.
 PROVIDE SURVEY SHOWING THOSE ELEVATIONS.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 9- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO
 BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION.
 SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019
 EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY
 THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND
 SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED
 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE
 BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT
 PHOTOS.
 NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE
 AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE
 YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF
 CERTIFICATION.
  
  
 REVISE SURVEY SUBMITTED:
  
 1- SURVEY SUBMITTED IS AN SPECIFIC PURPOSE
 SURVEY-"NORTHERLY FORMBOARDTIE IN". SEE TOP OF SURVEY.
 IF THIS SURVEY IS FOR ELEVATION CERTIFICATE FINISHED
 CONSTRUCTION, THEN THE SURVEY SHOULD BE A FINAL SURVEY
 AS WELL NOT A FORMBOARD SURVEY. PROVIDE FINAL SURVEY.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- FLOOD ZONE INFORMATION SPECIFIED AT THE BOTTOM
 MIDDLE OF SHEET IS OLD. THE CURRENT FLOOD MAP WENT INTO
 EFFECT ON 10/05/2017. REVISE ALL FLOOD INFORMATION AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SURVEY DOESN'T MATCH APPROVED PLANS AND PHOTOS SHOWN
 ON THE ELEVATION CERTIFICATES. THERE IS A BREEZEWAY
 CONNECTING THE GARAGE TO THE MAIN HOUSE. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE REVISED SURVEY WITH SURVEYORS ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: THIS CAN BE ACHIEVED BY UPLOADING DOCUMENTS WITH
 SURVEYOR'S DIGITAL SIGNATURE OR BY PROVIDING HARD COPY
 PLANS/DOCUMENTS WITH SURVEYOR'S ORIGINAL
 SEAL/SIGNATURE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-05-18 Cont ID  
Sent By jgomez Date 2021-05-18 Time 16:03 Rev Time 0.00
Received By jgomez Date 2021-05-18 Time 16:03 Sent To  
Notes
2021-05-18 16:04:04RESIDENTIAL(R3) ELEVATION CERTIFICATE. SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
 SUBMITTAL #21030009 (MASTER 16061174).
  
 COMMENTS FOR REVISED ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR MAIN HOUSE:
  
 1- ITEM A3 ON PAGE 1 OF 6 IS INCORRECT. THIS ITEM IS
 ASKING FOR THE PROPERTY DESCRIPTION. FORM SUBMITTED
 SAYS 1B. WHAT IS 1B? REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH
 FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS
 REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT SHOWN ON
 ITEM C2(E) DOESN'T MATCH ELEVATION SHOWN ON SURVEY
 SUBMITTED. REVISE AS REQUIRED.
 NOTE: CLARIFY WHAT ARE THE ELEVATIONS 7.40', 7.45' AND
 7.44' SHOWN ON THE SURVEY NEXT TO THE A/C PADS?.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT DOESN'T
 MEET THE CITY FREEBOARD REQUIREMENT OF 1 FOOT ABOVE THE
 BASE FLOOD ELEVATION AS REQUIRED BY CITY ORDINANCE
 4658-16.
 EQUIPMENT NEEDS TO BE RAISED AND ELEVATION CERTIFICATE
 NEEDS TO BE REVISED ACCORDINGLY.
 NOTE: ORIGINAL PLANS WERE APPROVED BEFORE THE NEW FLOOD
 MAPS TOOK EFFECT. PREVIOUS MAPS WERE BASED ON NGVD 1929
 ELEVATION DATUM. BASED ON NGVD, THE BASE FLOOD
 ELEVATION WAS 7 FEET AND THE REQUIRED FINISHED FLOOR
 ELEVATION WAS 8 FEET NGVD.
  
 5- COMMENTS ON SECTION D ON PAGE 2 OF 6 SPECIFIES A/C
 EQUIPMENT PAD LOCATED EASTERLY SIDE OF HOUSE. BASED ON
 SURVEY SUBMITTED, THIS IS INCORRECT. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 6- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM
 C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED
 BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS.
 PROVIDE SURVEY SHOWING THOSE ELEVATIONS.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 7- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO
 BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION.
 SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019
 EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY
 THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND
 SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED
 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE
 BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT
 PHOTOS.
 NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE
 AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE
 YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF
 CERTIFICATION.
  
  
 COMMENTS FOR ELEVATION CERTIFICATE CERTIFIED ON
 05/06/2021 FOR GARAGE:
  
 1- REVISE/CLARIFY DESCRIPTION ON ITEM A4 ON PAGE 1 OF
 6. WHAT IS A "DEATTACHED GARAGE"?. REVISE/CLARIFY AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ITEM A7 ON PAGE 1 OF 6 IS INCORRECT. THERE IS NOT
 CRAWLSPACE IN THE GARAGE. REVISE AS REQUIRED.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 3- SQUARE FOOTAGE SPECIFIED ON ITEM A8(A) ON PAGE 1 OF
 6 IS INCORRECT. ACCORDING TO SURVEY SUBMITTED THE
 GARAGE SQUARE FOOTAGE IS 733 S.F. NOT 586 S.F. REVISE
 AS REQUIRED. NOTE: SQUARE FOOTAGE IS TAKEN FROM
 EXTERIOR WALLS.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 4- TOTAL NET AREA OF FLOOD OPENINGS SPECIFIED ON ITEM
 A8(C) ON PAGE 1 OF 6 IS INCORRECT. SURVEYOR PROVIDED
 COMMENT AT BOTTOM OF SECTION D STATING "VENTING BASED
 ON FLOOD SOLUTIONS VENTS FS 1412 PER CLIENTS".
 ACCORDING TO ENGINEERED VENT PRODUCT APPROVAL FL17588
 SUBMITTED WITH PERMIT APPLICATION #16061174 THE
 SELECTED VENT FS-1412 HAS A NET FREE AREA OF 106.7 SQ.
 IN. PER VENT. IF THERE ARE 5 VENTS, THEN THE TOTAL NET
 AREA IS 533.5 SQ. IN. NOT 1000 SQ. IN. REVISE AS
 REQUIRED. NOTE: COORDINATE WITH ITEM #5 BELOW.
 SEC. 107..2.1 CITY AMENDMENTS.
  
 5- BASED ON ITEMS #3 AND #4 ABOVE IT LOOKS LIKE THE
 ENGINEER OF RECORD FOR PERMIT #16061174 NEEDS TO REVISE
 THE PLANS AND NUMBER OF REQUIRED FLOOD VENTS. SHEET A-2
 SPECIFIES A GARAGE AREA OF 586 S.F. ALSO, ENGINEER
 SHOWS 5 FLOOD VENTS (MODEL FS-1412 PRODUCT APPROVAL
 FL17588) ON WEST AND EAST WALLS.
 ENGINEER OF RECORD NEEDS TO PROVIDE CORRECT GARAGE
 SQUARE FOOTAGE AND REVISE THE NUMBER OF REQUIRED VENTS.
 SUBMIT REVISE PLANS FOR REVIEW. REVISION FEES APPLY.
 SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: SQUARE FOOTAGE IS TAKEN FROM EXTERIOR WALLS.
  
 6- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH
 FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS
 REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7- ITEM C2(B) SHOWN ON PAGE 2 OF 6 IS INCORRECT. THERE
 IS NOT NEXT HIGHER FLOOR IN THE GARAGE. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 8- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM
 C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED
 BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS.
 PROVIDE SURVEY SHOWING THOSE ELEVATIONS.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 9- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO
 BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION.
 SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019
 EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY
 THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND
 SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED
 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE
 BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT
 PHOTOS.
 NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE
 AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE
 YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF
 CERTIFICATION.
  
  
 REVISE SURVEY SUBMITTED:
  
 1- SURVEY SUBMITTED IS AN SPECIFIC PURPOSE
 SURVEY-"NORTHERLY FORMBOARDTIE IN". SEE TOP OF SURVEY.
 IF THIS SURVEY IS FOR ELEVATION CERTIFICATE FINISHED
 CONSTRUCTION, THEN THE SURVEY SHOULD BE A FINAL SURVEY
 AS WELL NOT A FORMBOARD SURVEY. PROVIDE FINAL SURVEY.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- FLOOD ZONE INFORMATION SPECIFIED AT THE BOTTOM
 MIDDLE OF SHEET IS OLD. THE CURRENT FLOOD MAP WENT INTO
 EFFECT ON 10/05/2017. REVISE ALL FLOOD INFORMATION AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SURVEY DOESN'T MATCH APPROVED PLANS AND PHOTOS SHOWN
 ON THE ELEVATION CERTIFICATES. THERE IS A BREEZEWAY
 CONNECTING THE GARAGE TO THE MAIN HOUSE. REVISE AS
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE REVISED SURVEY WITH SURVEYORS ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: THIS CAN BE ACHIEVED BY UPLOADING DOCUMENTS WITH
 SURVEYOR'S DIGITAL SIGNATURE OR BY PROVIDING HARD COPY
 PLANS/DOCUMENTS WITH SURVEYOR'S ORIGINAL
 SEAL/SIGNATURE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-07-23 Cont ID  
Sent By jgomez Date 2021-07-23 Time 15:12 Rev Time 0.00
Received By jgomez Date 2021-07-23 Time 15:11 Sent To  
Notes
2021-07-23 15:16:16ELEVATION CERTIFICATES AND SURVEY (HARD COPIES) WITH
 SURVEYOR'S ORIGINAL SEAL/SIGNATURE SENT TO SAMANTHA'S
 OFFICE (ELEVATION CERTIFICATE BOX). JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-16 Cont ID  
Sent By jgomez Date 2021-07-16 Time 12:42 Rev Time 0.00
Received By jgomez Date 2021-07-16 Time 08:45 Sent To  
Notes
2021-07-16 12:43:09ELEVATION CERTIFICATE AND SURVEY HARDCOPIES SUBMITTED.
 JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-18 Cont ID  
Sent By jgomez Date 2021-05-18 Time 16:05 Rev Time 0.00
Received By jgomez Date 2021-05-18 Time 16:05 Sent To  
Notes
2021-05-18 16:05:46NOTE:
 REVISED ELEVATION CERTIFICATE AND SURVEY WILL BE
 REQUIRED TO HAVE ORIGINAL SEAL/SIGNATURE EITHER DIGITAL
 OR CARD COPY. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-10 Cont ID  
Sent By jgomez Date 2021-03-10 Time 13:41 Rev Time 0.00
Received By jgomez Date 2021-03-10 Time 13:41 Sent To  
Notes
2021-03-10 13:42:59NOTE:
 REVISED ELEVATION CERTIFICATE AND SURVEY WILL BE
 REQUIRED TO HAVE ORIGINAL SEAL/SIGNATURE EITHER DIGITAL
 OR CARD COPY. JG.