Plan Review Details - Permit 21021450
Plan Review Stops For Permit 21021450
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-29 Cont ID  
Sent By rmcphers Date 2021-03-29 Time 09:21 Rev Time 0.00
Received By rmcphers Date 2021-03-29 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-12 Cont ID  
Sent By rmcphers Date 2021-03-12 Time 12:24 Rev Time 0.00
Received By rmcphers Date 2021-03-12 Time 12:16 Sent To  
Notes
2021-03-12 12:37:22WINDOWS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A BUILDING LAYOUT/FLOOR PLAN SHOWING
 THE LOCATION OF THE UNIT (605) IN THE BUILDING AND THE
 DISTANCE FROM THE CORNER OF THE BUILDING TO THE EDGE OF
 THE WINDOW OPENING. NEEDED TO DETERMINE IF THE WINDOW
 IS IN A WIND ZONE 4 OR 5.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-29 Cont ID  
Sent By rmcphers Date 2021-03-29 Time 09:21 Rev Time 0.00
Received By rmcphers Date 2021-03-17 Time 13:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-12 Cont ID  
Sent By rmcphers Date 2021-03-12 Time 12:39 Rev Time 0.00
Received By rmcphers Date 2021-02-26 Time 10:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-29 Cont ID  
Sent By rmcphers Date 2021-03-29 Time 09:21 Rev Time 0.00
Received By rmcphers Date 2021-03-29 Time 09:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-12 Cont ID  
Sent By rmcphers Date 2021-03-12 Time 12:37 Rev Time 0.00
Received By rmcphers Date 2021-03-12 Time 12:37 Sent To  
Notes
2021-03-12 12:38:48ENGINEERING PROVIDED NEEDS TO BE ELECTRONICALLY SIGNED
 BY THE ENGINEER -
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL