Plan Review Stops For Permit 21021356 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
N |
Date |
2022-06-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-06-23 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-06-23 |
Time |
08:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-04-29 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-29 |
Time |
08:06 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-28 |
Time |
14:32 |
Sent To |
|
|
Notes |
2021-04-29 08:06:34 | GENERATOR AND FUEL TANK | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) DRAWING LS-2 SHOWS FUEL TANK ROOM AS (S-2) PLEASE | | PROVIDE INFORMATION AS TO WHY AN (S-2) OCCUPANCY AND | | NOT AN (H-?) OCCUPANCY CONTROL AREA FBC 414.2 | | AND FBC 414.1.3 INFORMATION REQUIRED. | | A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL | | IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF | | HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED | | SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO | | SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION | | CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE | | METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT | | NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS | | AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE | | REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION | | AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON, | | FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL | | AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY. | | | | FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP | | H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING | | THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO | | AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF | | EVERY BUILDING AND STRUCTURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-07-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-07-11 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-07-11 |
Time |
09:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-04-27 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-04-27 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-04-26 |
Time |
14:39 |
Sent To |
|
|
Notes |
2021-04-27 13:54:44 | SEE PERMIT 20121068 FOR THE ELECTRICAL LAYOUT OF THE | | GENERATOR. JLEAHY |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2022-06-27 |
|
|
Cont ID |
|
Sent By |
|
Date |
2022-06-27 |
Time |
|
Rev Time |
0.00 |
Received By |
bdolan |
Date |
2022-06-27 |
Time |
09:12 |
Sent To |
|
|
Notes |
2022-06-27 09:12:44 | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | INSPECTIONS AND APPROVAL. | | | | LT. BRIAN DOLAN | | DIVISION OF FIRE PREVENTION | | 561-804-4752 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
bdolan |
Date |
2021-05-05 |
Time |
|
Rev Time |
0.00 |
Received By |
bdolan |
Date |
2021-05-05 |
Time |
13:10 |
Sent To |
|
|
Notes |
2021-05-05 13:12:38 | THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE | | DEPARTMENT. PER CITY CODES, ALL WORK IS SUBJECT TO | | FIELD INSPECTIONS AND APPROVAL. | | | | LT. BRIAN DOLAN | | DIVISION OF FIRE PREVENTION | | 561-804-4752 | | [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2022-06-08 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-06-08 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-06-08 |
Time |
13:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2021-05-03 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-05-03 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-05-03 |
Time |
12:37 |
Sent To |
|
|
Notes |
2021-05-03 12:47:20 | DIESEL FUEL GENERATOR- GAS REVIEW NOT REQUIRED- SEE | | MECHANICAL REVIEW. | | CCOLE- 5/3/2021. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-07-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-07-11 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-06-23 |
Time |
15:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-06-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-06-23 |
Time |
08:32 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-06-07 |
Time |
07:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-05-21 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-05-21 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-04-12 |
Time |
08:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2022-06-15 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-06-15 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-06-15 |
Time |
15:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2021-04-30 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-04-30 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-04-30 |
Time |
08:40 |
Sent To |
|
|
Notes |
2021-04-30 09:30:42 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21021356 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE SEE BUILDING REVIEWER COMMENTS. | | | | 2) A MECHANICAL SUB-PERMIT WILL BE REQUIRED FOR THIS | | GENERATOR INSTALLATION. | | | | 3) PLEASE PROVIDE A DETAIL DRAWING OF THE GENERATOR IN | | THE GENERATOR ROOM. PLEASE INCLUDE THE EXHAUST DETAILS | | OF THE GENERATOR INCLUDING LOCATION OF THE TERMINATION | | AND HEIGHT IT IS EXITING THE BUILDING. FBC 107.2.1; FBC | | M 607 | | | | 4) PLEASE SHOW THE PROPERTY LINES AND DISTANCE AWAY | | FROM PROPERTY LINES FOR THE GENERATOR EXHAUST. FBC M | | 501.3.1 | | | | 5) PLEASE SHOW THE METHOD OF TANK FILL FOR THE DIESEL | | FUEL TANK. FBC M 1305.6 | | | | 6) PLEASE PROVIDE A DETAIL FUEL PIPING DRAWING | | INDICATING THE PIPING TYPE AND SIZES. FBC M 1305 | | | | 7) PLEASE SOW THE VENT PIPING FOR THE TANK AND THE | | TERMINATION LOCATION. FBC M 1305.7 | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2022-06-08 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-06-08 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-06-08 |
Time |
13:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2021-05-03 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-05-03 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-05-03 |
Time |
12:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2022-07-11 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2022-07-11 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2022-07-11 |
Time |
10:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2022-06-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-06-23 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-06-23 |
Time |
08:29 |
Sent To |
|
|
Notes |
2022-06-23 08:31:03 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) DRAWINGS E-407, A-101, E-602, E-502 DO NOT SHOW AS | | DIGITALLY SIGNED IN ADOBE READER - | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2021-04-28 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-28 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-28 |
Time |
14:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2022-06-13 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-06-13 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-06-13 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2021-05-20 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2021-05-20 |
Time |
|
Rev Time |
|
Received By |
rthermid |
Date |
2021-05-20 |
Time |
|
Sent To |
I |
|
Notes |
2021-05-20 12:08:53 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 5/20/21 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PROVIDE A SURVEY OF THE PROPERTY SHOWING THE | | LOCATION AND THE SETBACKS OF THE PROPOSED GENERATOR TO | | ALL PROPERTY LINES. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | LIKE TO RESUBMIT ELECTRONICALY, EMAIL | | [email protected] AND REQUEST TO HAVE YOUR | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN | | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | ARE FINISHED UPLOADING. | | | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | TTY: 800.955.8771 | | E: [email protected] | | W: WPB.ORG | | |
|
|