Plan Review Details - Permit 21021356
Plan Review Stops For Permit 21021356
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2022-06-23 Cont ID  
Sent By rmcphers Date 2022-06-23 Time 08:29 Rev Time 0.00
Received By rmcphers Date 2022-06-23 Time 08:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-29 Cont ID  
Sent By rmcphers Date 2021-04-29 Time 08:06 Rev Time 0.00
Received By rmcphers Date 2021-04-28 Time 14:32 Sent To  
Notes
2021-04-29 08:06:34GENERATOR AND FUEL TANK
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING LS-2 SHOWS FUEL TANK ROOM AS (S-2) PLEASE
 PROVIDE INFORMATION AS TO WHY AN (S-2) OCCUPANCY AND
 NOT AN (H-?) OCCUPANCY CONTROL AREA FBC 414.2
 AND FBC 414.1.3 INFORMATION REQUIRED.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
  
 FOR BUILDINGS AND STRUCTURES WITH AN OCCUPANCY IN GROUP
 H, SEPARATE FLOOR PLANS SHALL BE SUBMITTED IDENTIFYING
 THE LOCATIONS OF ANTICIPATED CONTENTS AND PROCESSES SO
 AS TO REFLECT THE NATURE OF EACH OCCUPIED PORTION OF
 EVERY BUILDING AND STRUCTURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-11 Cont ID  
Sent By jleahy Date 2022-07-11 Time 09:54 Rev Time 0.00
Received By jleahy Date 2022-07-11 Time 09:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-27 Cont ID  
Sent By jleahy Date 2021-04-27 Time 13:53 Rev Time 0.00
Received By jleahy Date 2021-04-26 Time 14:39 Sent To  
Notes
2021-04-27 13:54:44SEE PERMIT 20121068 FOR THE ELECTRICAL LAYOUT OF THE
 GENERATOR. JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-06-27 Cont ID  
Sent By   Date 2022-06-27 Time   Rev Time 0.00
Received By bdolan Date 2022-06-27 Time 09:12 Sent To  
Notes
2022-06-27 09:12:44PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By bdolan Date 2021-05-05 Time   Rev Time 0.00
Received By bdolan Date 2021-05-05 Time 13:10 Sent To  
Notes
2021-05-05 13:12:38THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE
 DEPARTMENT. PER CITY CODES, ALL WORK IS SUBJECT TO
 FIELD INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2022-06-08 Cont ID  
Sent By ccole Date 2022-06-08 Time 14:02 Rev Time 0.00
Received By ccole Date 2022-06-08 Time 13:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-05-03 Cont ID  
Sent By ccole Date 2021-05-03 Time 12:45 Rev Time 0.00
Received By ccole Date 2021-05-03 Time 12:37 Sent To  
Notes
2021-05-03 12:47:20DIESEL FUEL GENERATOR- GAS REVIEW NOT REQUIRED- SEE
 MECHANICAL REVIEW.
 CCOLE- 5/3/2021.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-11 Cont ID  
Sent By jleahy Date 2022-07-11 Time 10:23 Rev Time 0.00
Received By jleahy Date 2022-06-23 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-23 Cont ID  
Sent By rmcphers Date 2022-06-23 Time 08:32 Rev Time 0.00
Received By rmcphers Date 2022-06-07 Time 07:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-21 Cont ID  
Sent By medwards Date 2021-05-21 Time 09:09 Rev Time 0.00
Received By medwards Date 2021-04-12 Time 08:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-06-15 Cont ID  
Sent By medwards Date 2022-06-15 Time 15:58 Rev Time 0.00
Received By medwards Date 2022-06-15 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-30 Cont ID  
Sent By medwards Date 2021-04-30 Time 09:30 Rev Time 0.00
Received By medwards Date 2021-04-30 Time 08:40 Sent To  
Notes
2021-04-30 09:30:421ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21021356
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE BUILDING REVIEWER COMMENTS.
  
 2) A MECHANICAL SUB-PERMIT WILL BE REQUIRED FOR THIS
 GENERATOR INSTALLATION.
  
 3) PLEASE PROVIDE A DETAIL DRAWING OF THE GENERATOR IN
 THE GENERATOR ROOM. PLEASE INCLUDE THE EXHAUST DETAILS
 OF THE GENERATOR INCLUDING LOCATION OF THE TERMINATION
 AND HEIGHT IT IS EXITING THE BUILDING. FBC 107.2.1; FBC
 M 607
  
 4) PLEASE SHOW THE PROPERTY LINES AND DISTANCE AWAY
 FROM PROPERTY LINES FOR THE GENERATOR EXHAUST. FBC M
 501.3.1
  
 5) PLEASE SHOW THE METHOD OF TANK FILL FOR THE DIESEL
 FUEL TANK. FBC M 1305.6
  
 6) PLEASE PROVIDE A DETAIL FUEL PIPING DRAWING
 INDICATING THE PIPING TYPE AND SIZES. FBC M 1305
  
 7) PLEASE SOW THE VENT PIPING FOR THE TANK AND THE
 TERMINATION LOCATION. FBC M 1305.7
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-06-08 Cont ID  
Sent By ccole Date 2022-06-08 Time 14:02 Rev Time 0.00
Received By ccole Date 2022-06-08 Time 13:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-05-03 Cont ID  
Sent By ccole Date 2021-05-03 Time 12:45 Rev Time 0.00
Received By ccole Date 2021-05-03 Time 12:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-11 Cont ID  
Sent By jleahy Date 2022-07-11 Time 10:19 Rev Time 0.00
Received By jleahy Date 2022-07-11 Time 10:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-06-23 Cont ID  
Sent By rmcphers Date 2022-06-23 Time 08:29 Rev Time 0.00
Received By rmcphers Date 2022-06-23 Time 08:29 Sent To  
Notes
2022-06-23 08:31:03SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS E-407, A-101, E-602, E-502 DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-04-28 Cont ID  
Sent By rmcphers Date 2021-04-28 Time 14:46 Rev Time 0.00
Received By rmcphers Date 2021-04-28 Time 14:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-06-13 Cont ID  
Sent By asangele Date 2022-06-13 Time 10:24 Rev Time 0.00
Received By asangele Date 2022-06-13 Time 10:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-05-20 Cont ID  
Sent By rthermid Date 2021-05-20 Time   Rev Time  
Received By rthermid Date 2021-05-20 Time   Sent To I
Notes
2021-05-20 12:08:53ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 5/20/21
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A SURVEY OF THE PROPERTY SHOWING THE
 LOCATION AND THE SETBACKS OF THE PROPOSED GENERATOR TO
 ALL PROPERTY LINES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved