Plan Review Details - Permit 21021355
Plan Review Stops For Permit 21021355
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-12 Cont ID  
Sent By rmcphers Date 2022-08-12 Time 08:34 Rev Time 0.00
Received By rmcphers Date 2022-08-12 Time 08:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-29 Cont ID  
Sent By rmcphers Date 2021-04-29 Time 09:47 Rev Time 0.00
Received By rmcphers Date 2021-04-28 Time 15:26 Sent To  
Notes
2021-04-29 09:29:153RD FLOOR GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A DRAWING THAT SHOWS THE PATH OF THE
 GAS LINE TO COMPLY WITH FBC 403.4.8.2 FUEL LINE PIPING
 PROTECTION.
 FUEL LINES SUPPLYING A GENERATOR SET INSIDE A BUILDING
 SHALL BE SEPARATED FROM AREAS OF THE BUILDING OTHER
 THAN THE ROOM THE GENERATOR IS LOCATED IN BY AN
 APPROVED METHOD OR ASSEMBLY THAT HAS A FIRE-RESISTANCE
 RATING OF NOT LESS THAN 2 HOURS. WHERE THE BUILDING IS
 PROTECTED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR
 903.3.1.2, THE REQUIRED FIRE-RESISTANCE RATING SHALL BE
 REDUCED TO 1 HOUR.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-08-12 Cont ID  
Sent By jleahy Date 2022-08-12 Time 10:14 Rev Time 0.00
Received By jleahy Date 2022-08-12 Time 10:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-26 Cont ID  
Sent By equinone Date 2021-04-26 Time 14:20 Rev Time 0.00
Received By equinone Date 2021-04-26 Time 14:20 Sent To  
Notes
2021-04-26 14:25:55CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) PLEASE PROVIDE A RISER DIAGRAM SHOWING SERVICE
 EQUIPMENT, SERVICE AND FEEDER CONDUCTOR SIZES, TRANSFER
 SWITCHES, BREAKER SIZES, INTERRUPTING CAPACITY OF
 DISCONNECTS AND PANELS, GROUNDING DETAILS. INCLUDE
 RATINGS, SIZES, ETC FOR ALL EQUIPMENT. FBC 107, NEC
 2016
  
 2) DRAWINGS SUBMITTED NEED TO BE DIGITALLY SIGNED BY PE
 OR HAVE THE NAME, LICENSE AND SIGNATURE OF ELECTRICAL
 CONTRACTOR QUALIFIER. FBC 107
  
 3) DOCUMENT SUBMITTED HAVE SPECS FOR BOTH A 1000KW AND
 A 30 KW GENERATOR. PLEASE SEPARATE THE SPECS THAT APPLY
 TO THE EQUIPMENT BEING INSTALLED UNDER THIS PERMIT.
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-04 Cont ID  
Sent By   Date 2022-08-04 Time   Rev Time 0.00
Received By bdolan Date 2022-08-04 Time 14:14 Sent To  
Notes
2022-08-04 14:16:01THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE
 DEPARTMENT, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 PLEASE ADDRESS GAS REVIEW COMMENTS PRIOR TO FINAL
 APPROVALS.
  
 PREVIOUS FIRE COMMENTS ADDRESSED IN RESUB.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By bdolan Date 2021-05-14 Time   Rev Time 0.00
Received By bdolan Date 2021-05-12 Time 11:54 Sent To  
Notes
2021-05-14 11:58:04PLEASE ADVISE/ELABORATE ON 30KW GENERATOR, WHAT IS
 USE/PURPOSE OF THIS GENERATOR? WHAT EQUIPMENT OR
 SYSTEMS ARE TIED INTO THIS GENERATOR?
 ARE THERE ANY LIFE SAFETY DEVICES TIED INTO THIS
 SUBSIDIARY GENERATOR? GENERATOR IS NG, WHERE DOES LINE
 FOR GENERATOR FUEL RUN?
  
 THANK YOU.
  
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-11-15 Cont ID  
Sent By rwbrown Date 2022-11-15 Time 05:52 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-08-03 Cont ID  
Sent By ccole Date 2022-08-03 Time 15:57 Rev Time 0.00
Received By ccole Date 2022-08-03 Time 13:39 Sent To  
Notes
2022-08-03 15:59:382ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 21021355- STANDBY GENERATOR
 8/3/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 NFPA 37, 54 & 110
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAPS.
  
 3) FAILED. CORRECT SHEET E-407 SHOWING GENERATOR SPECS
 FOR MTU 4R0063 GS30. THE APPROVED SUBMITTAL UPLOADED IS
 FOR A CUMMINGS C30 NG- SECTION 107.2.1 WPB AND SECTION
 305.1 FBC FG. CORRECTION NOT PROVIDED.
  
 7) FAILED. INDICATE HOW COMBUSTION AIR WILL BE PROVIDED
 TO THE GENERATOR AND PROVIDE CALCULATIONS- SECTION
 304.1 FBC FG. A) SHEET M103: THE COMBUSTION AIR
 CALCULATIONS SHOW THEY ARE BASED ON 38,500 BTU/HR LOAD
 HOWEVER THE GENERATOR SPECS INDICATE 389,000 BTU/HR.
 PLEASE CORRECT. B) M103: PLEASE LABEL THE SUPPLY CFMS
 AT THE DIFFUSER IN THE GENERATOR ROOM.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS.
  
 1) SHEETS P-101B, P-242, & P-505: THE UPDATED PLAN
 SHEETS DO NOT MATCH.
  
 A) SHEET P-101B SHOWS ONLY ONE METER AND THE PIPE RUNS
 AND PIPE SIZES DO NOT MATCH THE ENLARGED PIPING LAYOUT
 DRAWING (P-242) AND THE RISER (P-505.
  
 B) P-242 SHOWS A 2-1/2 LOW PRESSURE SUPPLY LINE ON
 LEVEL 01 FROM THE METER TO THE VERTICAL RISER PIPE,
 HOWEVER THE ISOMETRIC DRAWING (P-505) SHOWS A 3-INCH
 PIPE. WHICH IS IT?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-05-03 Cont ID  
Sent By ccole Date 2021-05-03 Time 12:02 Rev Time 0.00
Received By ccole Date 2021-05-03 Time 07:06 Sent To  
Notes
2021-05-03 12:03:071ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 21021355- STANDBY GENERATOR
 LA CLARA MASTER PERMIT- 18081528 & REVISION- 20070795)
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 NFPA 37, 54 & 110
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REFER TO SECTION 403.4.8 AND INDICATE IF THE
 NEW GAS GENERATOR IS FOR EMERGENCY OR STANDBY USE.
 INDICATE WHICH POWER LOADS IT WILL BE SUPPLYING-
 SECTIONS 403.4.8.3 & 403.4.8.4 FBC B.
  
 2) PLEASE REFER TO SECTION 5.1 NFPA 110 AND PROVIDE
 EVIDENCE THAT THERE IS NO PROBABILITY OF INTERRUPTION
 OF NATURAL GAS SERVICE WHICH WOULD WARRANT AN ON-SITE
 STORAGE OF AN ALTERNATE ENERGY SOURCE TO ALLOW FULL
 OUTPUT OF THE EMERGENCY POWER SUPPLY SYSTEM (EPSS) TO
 BE DELIVERED FOR THE CLASS SPECIFIED- EITHER LEVEL 1 OR
 LEVEL 2- SECTIONS 4.1- 4.4.4 & TABLES 4.1A & 4.1(B).
  
 3) CORRECT SHEET E-407 SHOWING GENERATOR SPECS FOR MTU
 4R0063 GS30. THE APPROVED SUBMITTAL UPLOADED IS FOR A
 CUMMINGS C30 NG- SECTION 107.2.1 WPB AND SECTION 305.1
 FBC FG.
  
 4) THE APPROVED GAS RISER (SHEET P505) UNDER REVISION
 20070795 TO MASTER 18081528 INDICATES NON-COMPLIANCE
 WITH SECTION 5.5.1 NFPA 110 WHICH REQUIRES A DEDICATED
 GAS LINE TO SUPPLY THE GENERATOR (ENERGY CONVERTER- SEE
 SECTIONS 5.2.3 & 5.2.4). THE CURRENT RISER SHOWS THE 2
 PSI SERVICE LINE ALSO SUPPLYING GAS TO 3 WATER HEATERS,
 2 POOL HEATERS, AND A BOILER. IT ALSO SHOWS A HIGHER
 BTU LOAD FOR THE GENERATOR WHICH MAY NOT AFFECT PIPE
 SIZING HOWEVER THE DRAWING MUST BE UPDATED. PLEASE
 SUBMIT A CORRECTED GAS RISER UNDER THIS PERMIT-
 21021355, AND UNDER 18081528 THAT SHOW THE NEW
 GENERATOR BTU LOAD AND DEDICATED GAS LINE- SECTION
 107.2.1, 107.3.5.1.5 WPB AND SECTION 402.1 FBC FG.
  
 A) RISER: REFER TO SECTIONS 7.9.7 & 7.9.8 NFPA 1110 AND
 SHOW THE SEPARATE SHUTOFF VALVE FOR THE DEDICATED
 GENERATOR LINE AND INDICATE THAT SIGNAGE WILL BE POSTED
 AT THE VALVE TO INDICATE IT IS SUPPLYING AN EMERGENCY
 GENERATOR.
  
 5) REFER TO SECTION 403.4.8.2 FBC B- FUEL LINE PIPING
 PROTECTION AND SUBMIT DRAWINGS AND DETAILS SHOW
 COMPLIANCE-
 FUEL LINES SUPPLYING A GENERATOR SET INSIDE A BUILDING
 SHALL BE SEPARATED FROM AREAS OF THE BUILDING OTHER
 THAN THE ROOM THE GENERATOR IS LOCATED IN BY AN
 APPROVED METHOD OR ASSEMBLY THAT HAS A FIRE-RESISTANCE
 RATING OF NOT LESS THAN 2 HOURS. WHERE THE BUILDING IS
 PROTECTED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR
 903.3.1.2, THE REQUIRED FIRE-RESISTANCE RATING SHALL BE
 REDUCED TO 1 HOUR.
  
 6) PROVIDE AN ENLARGED GAS PIPING SCHEMATIC FOR THE
 GENERATOR SHOWING TYPES AND SIZES OF GAS PIPING, PIPING
 SUPPORTS, AND LOCATIONS OF REGULATOR, MANUAL AND
 AUTOMATIC SHUTOFF VALVES, DRIP LEG, PIPE UNIONS, AND
 FLEX CONNECTOR AT THE GENERATOR- SECTIONS 7.9.3.2 &
 7.9.6 NFPA 110, AND SECTIONS 402.1, 402.3, 407, 408,
 409, 410, 411.1.5 & 616.2 FBC FG.
  
 A) PLEASE INDICATE THE SELECTED MAKE AND MODEL NUMBER
 OF THE REGULATOR, AND SUBMIT MARKED UP OR HIGHLIGHTED
 REGULATOR SPECS SHOWING THE SELECTED MODEL, THE INPUT
 AND OUTPUT PIPE SIZES AND PRESSURES, AND ORIFICE SIZE-
 SECTION 410.2 FBC FG.
  
 B) PROVIDE A REGULATOR AND RELIEF VALVE VENTING PLAN
 AND DIAGRAM IN ACCORDANCE WITH SECTION 5.3- 5.3.2.1
 NFPA 37, UNLESS THE SPECS SHOW COMPLIANCE WITH SECTION
 5.3.1.2 (ITEMS 1-4).
  
 C) PLEASE REFER TO SECTIONS 5.4.1, 5.4.3, & 5.4.4 NFPA
 54 AND MARK UP THE GENERATOR GAS PIPING DIAGRAM AND
 RISER TO SHOW LOCATIONS OF AND COMPLIANCE INFORMATION
 FOR THE MANUAL AND AUTOMATIC SHUTOFF VALVES.
  
 7) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE
 GENERATOR AND PROVIDE CALCULATIONS- SECTION 304.1 FBC
 FG.
  
 8) PROVIDE A VENTING PLAN AND ENLARGED DIAGRAM SHOWING
 THE TYPES AND SIZES OF VENTS, CONNECTORS, OFFSETS, AND
 TERMINATION CAP. SHOW THE LENGTH OF EACH CUT SEGMENT OF
 VENT- HORIZONTAL, VERTICAL, CONNECTORS, OFFSETS- AND
 THE TOTAL LENGTH OF THE SYSTEM- SEE SECTIONS 305.1,
 502, AND 503 FBC FG. A) PROVIDE VENT SUPPORT DETAILS-
 SECTION 503.6.11.
  
 B) PROVIDE VENT TERMINATION CLEARANCE MEASUREMENTS-
 SECTION 503.8 FBC FG.
  
 C) PROVIDE FIRESTOPPING DETAILS- SECTION 714.1 FBC B.
  
 D) PROVIDE SUBMITTALS FOR ALL MANUFACTURED PRODUCTS
 WITH APPROVAL STAMPS BY THE ENGINEER OF RECORD- SECTION
 107.2.1 WPB.
  
 9) PROVIDE A GENERATOR ACCEPTANCE TEST NARRATIVE IN
 ACCORDANCE WITH SECTION 713.1- 7.13.4.6 NFPA 110.
  
 10) SUBMIT A GAS-SUB PERMIT APPLICATION- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-15 Cont ID  
Sent By rwbrown Date 2022-11-15 Time 05:53 Rev Time 0.00
Received By rwbrown Date 2022-11-06 Time 07:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-12 Cont ID  
Sent By jleahy Date 2022-08-12 Time 10:14 Rev Time 0.00
Received By jleahy Date 2022-08-02 Time 16:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-24 Cont ID  
Sent By ccole Date 2021-05-24 Time 14:59 Rev Time 0.00
Received By ccole Date 2021-04-12 Time 08:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-08-10 Cont ID  
Sent By medwards Date 2022-08-10 Time 09:53 Rev Time 0.00
Received By medwards Date 2022-08-10 Time 09:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-30 Cont ID  
Sent By medwards Date 2021-04-30 Time 08:37 Rev Time 0.00
Received By medwards Date 2021-04-30 Time 07:09 Sent To  
Notes
2021-04-30 08:37:501ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21021355
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A MECHANICAL SUB-PERMIT WILL BE REQUIRED FOR THIS
 GENERATOR INSTALLATION.
  
 2) PLEASE PROVIDE A DETAIL DRAWING OF THE GENERATOR IN
 THE GENERATOR ROOM. PLEASE IDENTIFY THE INTAKE AIR
 LOCATION AND INCLUDE THE EXHAUST DETAILS OF THE
 GENERATOR. THE ORIGINAL APPROVED DRAWINGS DO NOT SHOW
 THE GENERATOR ROOM INSIDE OF THE MECHANICAL ROOM. THERE
 IS ELEVATOR PRESSURIZATION DUCT WORK FOR OUTDOOR AIR
 LOCATED INSIDE OF THIS ROOM. IF THE NEW WALLS FOR THE
 GENERATOR ROOM ARE REQUIRED TO BE FIRE RATED PLEASE
 REVISE THE APPROVED DRAWING SHOWING THE RATED WALLS AND
 THE PROTECTION REQUIRED FOR THE ELEVATOR PRESSURIZATION
 DUCTWORK. FBC 107.2.1; FBC M 607
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2022-11-15 Cont ID  
Sent By rwbrown Date 2022-11-15 Time 05:52 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-08-03 Cont ID  
Sent By ccole Date 2022-08-03 Time 13:47 Rev Time 0.00
Received By ccole Date 2022-08-03 Time 13:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-05-03 Cont ID  
Sent By ccole Date 2021-05-03 Time 08:57 Rev Time 0.00
Received By ccole Date 2021-05-03 Time 07:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-15 Cont ID  
Sent By rwbrown Date 2022-11-15 Time 05:52 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-08-10 09:55:17MECHANICAL DIGITAL SIGNATURES APPROVED. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-04-29 Cont ID  
Sent By rmcphers Date 2021-04-29 Time 09:50 Rev Time 0.00
Received By rmcphers Date 2021-04-29 Time 09:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-05 Cont ID  
Sent By afowlkes Date 2022-08-05 Time 13:20 Rev Time 0.00
Received By afowlkes Date 2022-08-05 Time 13:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-21 Cont ID  
Sent By kalexand Date 2021-05-21 Time 14:34 Rev Time 0.00
Received By kalexand Date 2021-05-21 Time 14:34 Sent To I
Notes
***NONE***