Plan Review Details - Permit 21021343
Plan Review Stops For Permit 21021343
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2021-03-17 Cont ID  
Sent By jwitmer Date 2021-03-17 Time 08:03 Rev Time 0.00
Received By jwitmer Date 2021-03-17 Time 07:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-24 Cont ID  
Sent By jwitmer Date 2021-03-24 Time 10:14 Rev Time 0.00
Received By jwitmer Date 2021-03-24 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time 8:58 Rev Time 0.00
Received By jwitmer Date 2021-03-17 Time 07:57 Sent To  
Notes
2021-03-17 08:46:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21021343
 ADD: 400 NORTHPOINT PKWY. # 100
 CONT: FISHER CONTRACTING CORP.
 TEL: 561-691-4716
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MARCH 17TH/2021
 ACTION: DENIED
  
 1) THE COVER SHEET/ PROJECT DATA:
 1A) THE PROJECT DATA LIST THE CONSTRUCTION TYPE AS:
 IV-B. PLEASE NOTE IN THE 2020 FBC-B TYPE IV-B
 CONSTRUCTION IS CONSIDERED HEAVY TIMBER-UNPROTECTED SEE
 THE 2020 FBC-B SECTION 602.4. PLEASE CORRECT
 CONSTRUCTION TYPE.
  
 1B) THE OCCUPANT LOAD STATED ON THE PLAN IS 3219 SQ.
 FT./ 100 OCCUPANT LOAD FACTOR = 33 PERSONS. PLEASE
 REVIEW IN THE 2020 FBC-B TABLE 1004.1.2 FOR BUSINESS
 OCCUPANCY THE OCCUPANT LOAD FACTOR HAS BEEN INCREASED
 TO 150 SQ. FT. PER PERSON OR 3219 / 150 = 21.46 OR 22
 PERSONS. BUSINESS 22 OCCUPANTS = 8 WAREHOUSE = 30
 OCCUPANTS TOTAL OCCUPANT LOAD.
  
 2) SHEET LS1 LIFE SAFETY SHEET:
 2A) THE PROJECT DATA LIST THE CONSTRUCTION TYPE AS:
 IV-B. PLEASE NOTE IN THE 2020 FBC-B TYPE IV-B
 CONSTRUCTION IS CONSIDERED HEAVY TIMBER-UNPROTECTED SEE
 THE 2020 FBC-B SECTION 602.4. PLEASE CORRECT
 CONSTRUCTION TYPE.
  
 2B) THE OCCUPANT LOAD STATED ON THE PLAN IS 3219 SQ.
 FT./ 100 OCCUPANT LOAD FACTOR = 33 PERSONS. PLEASE
 REVIEW IN THE 2020 FBC-B TABLE 1004.1.2 FOR BUSINESS
 OCCUPANCY THE OCCUPANT LOAD FACTOR HAS BEEN INCREASED
 TO 150 SQ. FT. PER PERSON OR 3219 / 150 = 21.46 OR 22
 PERSONS. BUSINESS 22 OCCUPANTS = 8 WAREHOUSE = 30
 OCCUPANTS TOTAL OCCUPANT LOAD.
  
 2C) UNDER THE HEADING CODE INVESTIGATIONS THE PLANS
 STATE THE OCCUPANCIES AS (B) BUSINESS AND (S1) STORAGE
 OCCUPANCY TYPES. PLEASE IDENTIFY THE TYPES OF PRODUCTS
 TO BE STORED IN THE S1 OCCUPANCY TO DETERMINE OCCUPANCY
 STORAGE TYPE. 2020 FBC-B SECTIONS 311.2 S-1 VERSES
 311.3 S-2 AND TABLE 508.4 OCCUPANCY SEPARATION.
  
 2D) ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2.
 THERE SEEMS TO BE A ONE-HOUR WALL BETWEEN THE BUSINESS
 OCCUPANCY AND THE STORAGE OCCUPANCY. THERE IS NO WALL
 LEGEND DEFINING THE WALL TYPES. ALSO WITHIN THIS SAME
 RATED WALL TYPE THERE APPEARS TO BE 2 OPENINGS ONE INTO
 THE OFFICE AREA THE OTHER INTO OFFICE 106. SHEET A-1
 ALSO SHOWS A ONE-HOUR FIRE PARTITION BETWEEN THE OFFICE
 AREA AND STORAGE AREA. IN THIS PLAN THE ONE OPENING IS
 IDENTIFIED AS DOOR # 12 AND IN THE OFFICE 106 A WINDOW
 TYPE G IS IDENTIFIED. PLEASE COLLATE PLANS TO REFLECT
 THE SAME CONFIGURATION.
  
 3) SHEET A2 RESTROOM ELEVATIONS PLEASE NOTE THE
 RESTROOM GRAB BARS ARE TO BE NO LONGER MEASURED FROM
 FINISH FLOOR TO THE CENTERLINE OF THE GRAB BAR BUT TO
 THE TOP OF THE GRASPABLE SURFACE. THIS CHANGE OCCURRED
 UNDER THE 2017 FBC-ACCESSIBILITY CODE 3 YEARS AGO. 2020
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-16 Cont ID  
Sent By jleahy Date 2021-03-16 Time 09:51 Rev Time 0.00
Received By jleahy Date 2021-03-16 Time 09:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-03-24 Cont ID  
Sent By pleduc Date 2021-03-24 Time   Rev Time 0.00
Received By pleduc Date 2021-03-24 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-04 Cont ID  
Sent By pleduc Date 2021-03-04 Time   Rev Time 0.00
Received By pleduc Date 2021-03-04 Time 10:11 Sent To  
Notes
2021-03-04 10:12:42FIRE PROVISO:
  
 FIRE SPRINKLER MODIFICATIONS ARE REQUIRED AROUND NEW
 AREAS.
  
 MAINTAIN FIRE SPRINKLER SYSTEM THROUGHOUT CONSTRUCTION
 INCLUDING DEMO.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-06 Cont ID  
Sent By medwards Date 2021-04-06 Time 13:31 Rev Time 0.00
Received By medwards Date 2021-04-01 Time 16:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-30 Cont ID  
Sent By medwards Date 2021-03-30 Time 15:34 Rev Time 0.00
Received By medwards Date 2021-03-23 Time 09:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-03-17 Time   Rev Time 0.00
Received By lmarchan Date 2021-02-25 Time 08:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-04-06 Cont ID  
Sent By medwards Date 2021-04-06 Time 13:29 Rev Time 0.00
Received By medwards Date 2021-04-06 Time 13:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-03-30 Cont ID  
Sent By medwards Date 2021-03-30 Time 15:18 Rev Time 0.00
Received By medwards Date 2021-03-30 Time 15:18 Sent To  
Notes
2021-03-30 15:25:39PLEASE PROVIDE THE SPECIFICATION SHEETS FOR THE SYSTEM
 DESIGNED AND SOLD FOR DEHUMIDIFICATION PURPOSES ONLY.
 FBC EC C101.4.2.4 (5) THIS RTU APPEARS TO BE A STANDARD
 RTU NOT A DEHUMIDIFICATION SYSTEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-03-16 Cont ID  
Sent By medwards Date 2021-03-16 Time 11:01 Rev Time 0.00
Received By medwards Date 2021-03-16 Time 07:28 Sent To  
Notes
2021-03-16 11:02:071ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21021343
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE ARE DEHUMIDIFYING UNITS AVAILABLE FOR
 COMMERCIAL WAREHOUSES, IF THIS IS THE INTENT PLEASE
 SUBMIT SPECIFICATIONS AND CALCULATIONS FOR THIS USE. IF
 USING A RTU THEN YOU MUST SUBMIT ENERGY CALCULATIONS
 ALONG WITH THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C101.4.2.4 (5) FBC EC C402; FBC M
 312.1 I CANNOT COMPLETE THE REVIEW UNTIL THIS COMMENT
 HAS BEEN ADDRESSED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-03-25 Cont ID  
Sent By ccole Date 2021-03-25 Time 17:03 Rev Time 0.00
Received By ccole Date 2021-03-25 Time 16:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-17 Cont ID  
Sent By ccole Date 2021-03-17 Time 10:34 Rev Time 0.00
Received By ccole Date 2021-03-17 Time 08:41 Sent To  
Notes
2021-03-17 10:34:501ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21021343
 3/17/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COVER SHEET: THE PLUMBING FIXTURE CALCULATIONS DO
 NOT INCLUDE THE STORAGE OCCUPANCY CALCULATIONS- TABLE
 403.1 FBC P.
  
 2) A1: PLEASE LABEL THE TOILET ROOMS AS EITHER MALE OR
 FEMALE ACCORDING TO TABLE 403.1 AND 403.2 FBC P.
  
 3) SHEET A-2: SHOW THE HEIGHTS OF THE GRAB BARS FROM
 THE FINISHED FLOORS TO THE TOPS OF THE GRIPPING
 SURFACES- - SECTION 609.4 FBC ACC.
  
 4) A-2: THE REAR GRAB BEHIND THE WATER CLOSET MUST BE
 CENTERED ACCORDING TO SECTION AND FIGURE 604.5.2 FBC
 ACC.
  
 5) A-2: RELOCATE THE WATER CLOSET FLUSH CONTROL TO THE
 OPEN SIDE OF THE WATER CLOSET- SECTION 604.6 FBC ACC.
  
 6) P1: PROVIDE A PLUMBING FIXTURE SCHEDULE LISTING
 MAKES, MODELS AND COMPLIANCE STANDARDS- SECTIONS 419,
 422, AND 425 FBC P.
  
 7) P1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CHRONOMITE WATER HEATER VERIFYING THE UNIT IS ASSE 1070
 LISTED TO PROVIDE TEMPERED WATER TO THE LAVATORIES. IF
 THE UNIT IS NOT ASSE 1070 APPROVED PLEASE PROVIDE A
 MIXING VALVE IN ACCORDANCE WITH SECTION 607.1.2 FBC P.
  
 8) P1: THE WATER RISER SHOWS A COLD WATER LINE TO THE
 EXISTING MOP SINK, HOWEVER HOT WATER IS REQUIRED PER
 SECTION 607.1 FBC P. PLEASE SHOW THE SOURCE OF THE HOT
 WATER.
  
 9) P1: PLEASE REMOVE THE WORD ASSUMED FROM THE SANITARY
 RISER AND PROVIDE COMPLETE WET VENTING DETAILS FOR THE
 NEW ADA TOILET ROOM- SECTION 912.1 FBC P.
  
 10) P1: SHOW IN THE SANITARY RISER THERE IS AN EXISTING
 VENT TO THE OUTDOORS SERVING THE BUILDING DRAIN AS
 REQUIRED BY SECTION 904.1 FBC P.
  
 11) P1: THE NOTE AT BOTTOM LEFT OF THE SHEET CALLS OUT
 TRAP PRIMER VALVE FOR FLOOR DRAIN, HOWEVER NO FLOOR
 DRAIN IS SHOWN IN THE DRAWINGS- PLEASE CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2021-05-12 Cont ID  
Sent By rgathrig Date 2021-05-12 Time 13:32 Rev Time 0.00
Received By rgathrig Date 2021-05-12 Time 13:32 Sent To  
Notes
2021-05-12 13:32:40ROOF REPAIR AROUND THE NEW AC CURB

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-06 Cont ID  
Sent By medwards Date 2021-04-06 Time 13:31 Rev Time 0.00
Received By medwards Date 2021-04-06 Time 13:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-30 Cont ID  
Sent By medwards Date 2021-03-30 Time 15:33 Rev Time 0.00
Received By medwards Date 2021-03-30 Time 15:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-16 Cont ID  
Sent By medwards Date 2021-03-16 Time 11:10 Rev Time 0.00
Received By medwards Date 2021-03-16 Time 11:10 Sent To  
Notes
***NONE***