2021-05-12 12:04:19 | 05/12/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| |
| 1. PLEASE PROVIDE THE PHYSICAL ADDRESS OF THE |
| RESIDENCE; IT MUST BE ON PLANS IN FULL, NUMBER, STREET, |
| CITY, STATE, AND ZIP CODE PER THE WPB AMENDMENTS TO THE |
| FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.1 GENERAL. |
| |
| 3. PLEASE PROVIDE A RISER DIAGRAM REQUIRED PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL |
| GAS. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, |
| ALL PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE). IN |
| ADDITION, SHOW ON THE ISOMETRIC DRAWING THE LENGTH OF |
| ALL CUT SECTIONS OF PIPE PER 2020 FBC RES. SECS. |
| G2413.4.1, G2413.4.2. |
| |
| 4. THIS TANKLESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED |
| FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC. |
| G2421.1. |
| |
| 5. PLEASE LIST THE TOTAL BTU LOAD ON THE SYSTEM. REFER |
| TO THE 2020 FBC RES. SEC. G2413. PLEASE SHOW THE BTU |
| LOAD FOR THE FUTURE GENERATOR ON THIS LIST FOR SIZING |
| CALCULATION, AND YOU MAY USE THE HIGHEST POSSIBLE LOAD |
| AND SIZE OF PIPE. |
| |
| 6. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| RES. SEC. G2413.4.1. |
| |
| 7. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| REGULATOR 1' OF EITHER SIDE, DRIP LEG, AND SHUTOFF |
| VALVE PER THE 2020 FBC RES. SEC G2421.2. |
| |
| 8. THE FUTURE GENERATOR NEEDS TO SHOW A SHUTOFF VALVE |
| AND HARD CAP FOR THE FUTURE ON GAS ISOMERIC PER THE |
| 2020 FBC RES. SEC. G2401.1.3. |
| |
| 9. VALVES SHALL BE READILY ACCESSIBLE WITHOUT MOVING |
| THE APPLIANCE, THAT WHICH ENABLES A DEVICE, APPLIANCE, |
| OR EQUIPMENT TO BE REACHED BY READY ACCESS OR BY A |
| MEANS THAT FIRST REQUIRES THE REMOVAL OR MOVEMENT OF A |
| PANEL, DOOR, OR SIMILAR OBSTRUCTION (SEE ALSO "READY |
| ACCESS") PER THE 2020 FBC RES GAS DEFINITIONS. |
| |
| 10. ON-HOUSE PLANS, PLEASE SHOW THE LOCATION OF THE |
| TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF |
| ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER |
| THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION |
| ON CONSTRUCTION DOCUMENTS. |
| |
| 11. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| OF IGNITION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 105.1. |
| |
| 12. PIPES OUTDOORS AND NOT IN CONDITION SPACE NEED TO |
| BE INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. |
| RE 403.5.3. PLEASE PLACE NOT ON PLANS. |
| |
| 13. THIS UNIT HAS CONDENSATE AND NEEDS TO BE 1' AWAY |
| FROM THE STRUCTURE PER THE 2020 FBC SEC. R318.5. PLEASE |
| PLACE NOT ON PLANS. |
| |