Plan Review Details - Permit 21021246
Plan Review Stops For Permit 21021246
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By lcrespo Date 2021-06-22 Time 12:26 Rev Time 0.00
Received By lcrespo Date 2021-06-22 Time 12:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By lcrespo Date 2021-05-12 Time 12:03 Rev Time 0.00
Received By lcrespo Date 2021-05-12 Time 12:03 Sent To  
Notes
2021-05-12 12:04:1905/12/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. PLEASE PROVIDE THE PHYSICAL ADDRESS OF THE
 RESIDENCE; IT MUST BE ON PLANS IN FULL, NUMBER, STREET,
 CITY, STATE, AND ZIP CODE PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 3. PLEASE PROVIDE A RISER DIAGRAM REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 GAS. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED,
 ALL PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE). IN
 ADDITION, SHOW ON THE ISOMETRIC DRAWING THE LENGTH OF
 ALL CUT SECTIONS OF PIPE PER 2020 FBC RES. SECS.
 G2413.4.1, G2413.4.2.
  
 4. THIS TANKLESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED
 FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC.
 G2421.1.
  
 5. PLEASE LIST THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE 2020 FBC RES. SEC. G2413. PLEASE SHOW THE BTU
 LOAD FOR THE FUTURE GENERATOR ON THIS LIST FOR SIZING
 CALCULATION, AND YOU MAY USE THE HIGHEST POSSIBLE LOAD
 AND SIZE OF PIPE.
  
 6. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 7. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE, DRIP LEG, AND SHUTOFF
 VALVE PER THE 2020 FBC RES. SEC G2421.2.
  
 8. THE FUTURE GENERATOR NEEDS TO SHOW A SHUTOFF VALVE
 AND HARD CAP FOR THE FUTURE ON GAS ISOMERIC PER THE
 2020 FBC RES. SEC. G2401.1.3.
  
 9. VALVES SHALL BE READILY ACCESSIBLE WITHOUT MOVING
 THE APPLIANCE, THAT WHICH ENABLES A DEVICE, APPLIANCE,
 OR EQUIPMENT TO BE REACHED BY READY ACCESS OR BY A
 MEANS THAT FIRST REQUIRES THE REMOVAL OR MOVEMENT OF A
 PANEL, DOOR, OR SIMILAR OBSTRUCTION (SEE ALSO "READY
 ACCESS") PER THE 2020 FBC RES GAS DEFINITIONS.
  
 10. ON-HOUSE PLANS, PLEASE SHOW THE LOCATION OF THE
 TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF
 ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 11. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE
 OF IGNITION PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 12. PIPES OUTDOORS AND NOT IN CONDITION SPACE NEED TO
 BE INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC.
 RE 403.5.3. PLEASE PLACE NOT ON PLANS.
  
 13. THIS UNIT HAS CONDENSATE AND NEEDS TO BE 1' AWAY
 FROM THE STRUCTURE PER THE 2020 FBC SEC. R318.5. PLEASE
 PLACE NOT ON PLANS.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2021-05-17 Cont ID  
Sent By aborngra Date 2021-05-17 Time 11:38 Rev Time 0.00
Received By aborngra Date 2021-05-17 Time 11:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-22 Cont ID  
Sent By lcrespo Date 2021-06-22 Time 12:26 Rev Time 0.00
Received By lcrespo Date 2021-06-22 Time 12:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-18 Cont ID  
Sent By rmcphers Date 2021-05-18 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2021-05-06 Time 12:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-06-22 Cont ID  
Sent By lcrespo Date 2021-06-22 Time 12:26 Rev Time 0.00
Received By lcrespo Date 2021-06-22 Time 12:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-05-12 Cont ID  
Sent By lcrespo Date 2021-05-12 Time 12:00 Rev Time 0.00
Received By lcrespo Date 2021-05-12 Time 11:24 Sent To  
Notes
2021-05-12 12:00:51 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-05-18 Cont ID  
Sent By rmcphers Date 2021-05-18 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2021-05-18 Time 11:08 Sent To  
Notes
***NONE***