Plan Review Details - Permit 21021175
Plan Review Stops For Permit 21021175
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-06-08 Cont ID  
Sent By lcrespo Date 2021-06-08 Time 17:05 Rev Time 0.00
Received By lcrespo Date 2021-06-08 Time 17:05 Sent To  
Notes
2021-06-08 17:05:4306/08/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-26 Cont ID  
Sent By lcrespo Date 2021-02-26 Time 14:44 Rev Time 0.00
Received By lcrespo Date 2021-02-26 Time 14:44 Sent To  
Notes
2021-03-02 12:36:1203/02/21 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS. A COMPLETE EVALUATION OF ALL GAS
 EQUIPMENT WILL BE DONE AT THE FIELD; IF NOT TO CODE, IT
 MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT THE
 OWNER'S EXPENSE.
  
 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. PLEASE PROVIDE THE TYPE OF GAS (LP OR NATURAL) PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 7. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR PER THE 2020 FBC RES. SEC.
 G2420.4.
  
 8. THIS TANKLESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED
 FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC.
 G2421.1.
  
 9. ARE THERE ANY OTHER GAS APPLIANCES ARE? IF SO?
 PLEASE LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC
 RES. SEC. G2413.
  
 10. PLEASE PROVIDE THE DISTANCE FROM THE POINT OF
 DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE 2020 FBC RES. SEC. G2413.4.1.
  
 11. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) OF THE
 SYSTEM ON THE PLAN PER THE 2020 FBC RES. SEC. G2413.2.
  
 12. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL ( IF APPLICABLE RANGE,
 DRYER, BBQ GRILL) FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 13. ALL GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 14. PLEASE INDICATE ON THE PLAN IF THE GRILL IS LOCATED
 UNDER A ROOF PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1.
  
 15. IF THE GAS GRILL IS LABELED FOR OUTDOOR USE AND IT
 WILL BE IN A COVERED PATIO, IF THIS IS SO, PLEASE
 PROVIDE MANUFACTURES RECOMMENDATION FOR A VENTILATION
 HOOD PER THE 2017 FG 305.1 OR 2017 FBC RES. SEC.
 G2408.1.
  
 16. PLEASE SUBMIT A COPY OF THE SIZING TABLE USED IN
 THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH
 SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES
 OR ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM
 PER THE 2020 FBC RES. SEC. G2413.3.
  
 17. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE, SHUTOFF VALVES, AND DRIP
 LEG PER THE 2020 FBC RES. SEC G2421.2.
  
 18. PLEASE SUBMIT A HOUSE PLAN THAT SHOWS THE TANK-LESS
 WATER HEATER'S LOCATION AND THE LOCATION AND DISTANCE
 OF ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE
 WATER HEATER. THE LOCATION OF THE WATER HEATER SHALL
 COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 19. IF GAS TANKLESS UNITS REQUIRE CONDENSATEDRAIN IT
 WILL NEED TO BE 1' AWAY FROM STRUCTURE PER THE 2020 FBC
 SEC R318.5.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-08 Cont ID  
Sent By lcrespo Date 2021-06-08 Time 17:05 Rev Time 0.00
Received By lcrespo Date 2021-06-03 Time 07:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-02 Cont ID  
Sent By lcrespo Date 2021-03-02 Time 12:42 Rev Time 0.00
Received By lcrespo Date 2021-02-24 Time 12:49 Sent To  
Notes
2021-03-02 12:11:11 
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-08 Cont ID  
Sent By lcrespo Date 2021-06-08 Time 17:04 Rev Time 0.00
Received By lcrespo Date 2021-06-08 Time 17:04 Sent To  
Notes
2021-06-08 17:04:5106/08/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-02 Cont ID  
Sent By lcrespo Date 2021-03-02 Time 12:10 Rev Time 0.00
Received By lcrespo Date 2021-03-01 Time 08:47 Sent To  
Notes
2021-03-02 12:17:0603/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS SCOPE OF WORK IS NOT CLEAR. THE CONTRACT HAS
 VERBIAGE THAT IS NOT ON PLAN AND WILL REQUIRE
 ADDITIONAL PERMITS. THIS PERMIT WILL NEED TO BE CHANGED
 TO AN INTERIOR RENOVATION WITH A NEW BUILDING
 APPLICATION AS A MASTER WITH PLUMBING, GAS, MECHANICAL,
 AND ELECTRICAL AS SUBS. PLEASE GET WITH THE PERMIT
 LIBRARIAN TO MAKE THESE CHANGES.
  
 2. THE CONTRACT STATES A KITCHEN HOOK UP. PLEASE
 SPECIFY IF THIS IS AN OUTSIDE KITCHENETTE. IT ALSO SAYS
 AN OUTDOOR SHOWER; PLEASE PROVIDE A COMPLETE SET OF
 PLANS THAT SHOW THE WORK SCOPE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. THE WASHING MACHINE THAT WILL BE INSTALLED USALLY
 COMES WITH A DRYER. THESE ITEMS REQUIRE ELECTRICAL AND
 MECAHINAL HOOK UP; PLEASE PROVIDE A COMPLETE SET OF
 PLANS THAT SHOW THE SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. HOT WATER PIPES NOT IN CONDITION SPACE OR OUTSIDE
 WILL NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE
 2017 FBC SEC. RE 403.5.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-08 Cont ID  
Sent By lcrespo Date 2021-06-08 Time 17:05 Rev Time 0.00
Received By lcrespo Date 2021-06-08 Time 17:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-02 Cont ID  
Sent By lcrespo Date 2021-03-02 Time 12:43 Rev Time 0.00
Received By lcrespo Date 2021-03-02 Time 12:43 Sent To  
Notes
2021-03-02 12:43:58PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.