Plan Review Details - Permit 21020874
Plan Review Stops For Permit 21020874
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-08-03 Cont ID  
Sent By rmcphers Date 2021-08-03 Time 10:11 Rev Time 0.00
Received By rmcphers Date 2021-08-03 Time 10:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-23 Cont ID  
Sent By rmcphers Date 2021-06-23 Time 15:16 Rev Time 0.00
Received By rmcphers Date 2021-06-23 Time 15:16 Sent To  
Notes
2021-06-23 15:28:17INTERIOR STAIR SHOP DRAWING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) SHOP DRAWINGS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE ARCHITECT (YATES).
 2) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS THAT THE
 GUARD RAIL GLAZING WILL COMPLY WITH FBC R308.3.1 IMPACT
 TEST.
 WHERE REQUIRED BY OTHER SECTIONS OF THE CODE, GLAZING
 SHALL BE TESTED IN ACCORDANCE WITH CPSC 16 CFR 1201.
 GLAZING SHALL COMPLY WITH THE TEST CRITERIA FOR
 CATEGORY II
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By rmcphers Date 2021-04-21 Time 13:51 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 12:55 Sent To  
Notes
2021-04-21 13:51:33STAIR SHOP DRAWINGS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) EXTERIOR STAIR IS SUBJECT TO WIND LOADS- PLEASE SHOW
 THE WIND DESIGN CRITERIA TO COMPLY WITH FBC 1603.1.4
 2) PLEASE PROVIDE THE STRUCTURAL CALCULATIONS FOR THE
 STAIR DESIGN OR HAVE THE DRAWINGS SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL. FBC 107.2.1.2
 3) DRAWINGS NEED TO BE SIGNED BY THE DESIGNER AND SHOW
 THE PRINTED NAME FBC 107.2.1 - FBC 107.1
 4) INTERIOR STAIR DRAWING NEEDS TO SHOW THE ATTACHMENTS
 TO THE STRUCTURE. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2021-04-13 Cont ID  
Sent By ccarvaja Date 2021-04-13 Time 10:46 Rev Time 0.00
Received By ccarvaja Date 2021-03-01 Time 20:41 Sent To  
Notes
2021-04-13 10:47:06ENTERED BY FG, NOT REQUIRED, CC

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-09-23 Time   Rev Time 0.00
Received By aoliver Date 2021-09-22 Time 07:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-03 Cont ID  
Sent By rmcphers Date 2021-08-03 Time 10:13 Rev Time 0.00
Received By rmcphers Date 2021-08-02 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-23 Cont ID  
Sent By rmcphers Date 2021-06-23 Time 15:30 Rev Time 0.00
Received By rmcphers Date 2021-06-21 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-22 Cont ID  
Sent By lmarchan Date 2021-04-22 Time 11:32 Rev Time 0.00
Received By lmarchan Date 2021-04-12 Time 10:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-09-24 Cont ID  
Sent By ccole Date 2021-09-24 Time 16:10 Rev Time 0.00
Received By ccole Date 2021-09-24 Time 16:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-09-23 Cont ID  
Sent By ccole Date 2021-09-23 Time 17:06 Rev Time 0.00
Received By ccole Date 2021-09-23 Time 16:54 Sent To  
Notes
2021-09-23 17:07:454TH ELECTRONIC SIGNATURE REVIEW
 PERMIT- 21020874
 9/23/21
  
 FAILED- COMMENT # 1 FROM THE 3RD REVIEW LISTED BELOW
 STILL EXISTS- PLEASE COMPLY.
  
 1) DRAWINGS LABELED "COMMENT 4 _ ENGINEERING - INTERIOR
 STAIRCASE.PDF" DOES NOT SHOW AS ELECTRONICALLY SIGNED
 IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC
 PLAN REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 2) NEW COMMENT: CALCULATIONS TITLED STAIR #7, THE
 CRYSTAL CONDO ARE NOT DIGITALLY SIGNED AND SEALED BY
 THE T ENGINEER OF RECORD XUAN CHEN. CALCULATIONS
 PREPARED BY A FL. LICENSED ENGINEER THAT ARE
 TRANSMITTED ELECTRONICALLY SHALL BEAR THE DIGITAL SEAL
 SIGNATURE OF THE ENGINEER- FL. STATUTE 471.025, AND
 SECTION 61G15-23.005 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 AS AN ALTERNATIVE TO PROVIDING DIGITALLY SIGNED AND
 SEALED CALCULATIONS, SIGNED AND SEALED ENGINEERING IN
 PAPER FORM CAN BE BROUGHT INTO THE WPB BUILDING
 DEPARTMENT WITH A COMPLETED PLAN REVIEW REQUEST FORM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-08-03 Cont ID  
Sent By rmcphers Date 2021-08-03 Time 10:11 Rev Time 0.00
Received By rmcphers Date 2021-08-03 Time 10:11 Sent To  
Notes
2021-08-03 10:13:38SIGNATURE REVIEW
 DRAWINGS LABELED "COMMENT 4 _ ENGINEERING - INTERIOR
 STAIRCASE.PDF" DOES NOT SHOW AS ELECTRONICALLY SIGNED
 IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC
 PLAN REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
 COMMENT 4 _ ENGINEERING - INTERIOR STAIRCASE.PDF

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-23 Cont ID  
Sent By rmcphers Date 2021-06-23 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2021-06-23 Time 15:29 Sent To  
Notes
2021-06-23 15:30:32SIGNATURE REVIEW
 DRAWING (ST1) DOES NOT SHOW AS ELECTRONICALLY SIGNED IN
 ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE
 ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN
 REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES NOT
 HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP
 OFF THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 TO THE FRONT DESK IN THE BUILDING DIVISION AT THE CITY
 HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By rmcphers Date 2021-04-21 Time 13:52 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 13:52 Sent To  
Notes
2021-04-21 13:53:02SEE BUILDING PLAN REVIEW -
  
 FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN MAIL IN OR
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 1 Status P Date 2021-04-22 Cont ID  
Sent By llouie Date 2021-04-22 Time   Rev Time  
Received By llouie Date 2021-04-22 Time   Sent To  
Notes
2021-04-22 11:20:55* CHANGES TO THE STAIRWELLS WITHIN EXISTING BUILDING
 FOOTPRINT ONLY.