Plan Review Details - Permit 21020829
Plan Review Stops For Permit 21020829
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-03 Cont ID  
Sent By jgomez Date 2021-03-03 Time 13:21 Rev Time 0.00
Received By jgomez Date 2021-03-03 Time 13:21 Sent To  
Notes
2021-03-03 13:23:21PROVISO:
  
 FLAT ROOF (BONDED INSULATION OR MEMBRANE)
 GENERAL NOTE #12 OF PRODUCT APPROVAL SUBMITTED REQUIRES
 THAT: "FOR BONDED INSULATION OR MEMBRANE OVER EXISTING
 SUBSTRATES IN A RE-ROOF (TEAR OFF) OR RECOVER
 INSTALLATION, THE EXISTING DECK OR EXISTING ROOF
 SURFACE SHALL BE EXAMINED FOR COMPATIBILITY WITH THE
 ADHESIVE TO BE INSTALLED. IF ANY SURFACE CONDITIONS
 EXIST THAT BRING SYSTEM PERFORMANCE INTO QUESTION,
 FIELD UPLIFT TESTING IN ACCORDANCE SHALL BE CONDUCTED
 ON MOCK-UPS OF THE PROPOSED NEW ROOF ASSEMBLY. FOR
 BONDED INSULATION OR MEMBRANE OVER EXISTING SUBSTRATES
 IN A RECOVER INSTALLATION, THE EXISTING ROOF SYSTEM
 SHALL BE CAPABLE OF RESISTING PROJECT DESIGN PRESSURES
 ON ITS OWN MERIT TO THE SATISFACTION OF THE AUTHORITY
 HAVING JURISDICTION, AS DOCUMENTED THROUGH FIELD UPLIFT
 TESTING. FIELD UPLIFT TESTING SHALL BE IN ACCORDANCE
 WITH ASTM E907, FM LOSS PREVENTION DATA SHEET 1-52 OR
 TESTING APPLICATION STANDARD TS 124."
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-02 Cont ID  
Sent By jgomez Date 2021-03-02 Time 18:00 Rev Time 0.00
Received By jgomez Date 2021-03-02 Time 17:48 Sent To  
Notes
2021-03-02 18:01:00RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
  
 PERMIT #21020829
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL4930-R14
 SUBMITTED IS FOR THE 2017 CODE VERSION. AS OF DECEMBER
 31, 2020, THE CURRENT CODE IS THE 2020 VERSION (SEC.
 553 F.S.). PROVIDE PRODUCT APPROVAL FOR THE CURRENT
 CODE VERSION AND CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609.1 FBC-BUILDING.
  
 2- NOTE: SEPARATE PERMIT FOR MECHANICAL ROOFING
 EQUIPMENT MAY BE REQUIRED.
 SEC. 102.8 CITY AMENDMENTS: EXISTING MECHANICAL
 EQUIPMENT. AN AGENCY OR LOCAL GOVERNMENT MAY NOT
 REQUIRE THAT EXISTING MECHANICAL EQUIPMENT LOCATED ON
 OR ABOVE THE SURFACE OF A ROOF BE INSTALLED IN
 COMPLIANCE WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE EXCEPT DURING REROOFING WHEN THE
 EQUIPMENT IS BEING REPLACED OR MOVED AND IS NOT IN
 COMPLIANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE RELATING TO ROOF-MOUNTED MECHANICAL UNITS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-03 Cont ID  
Sent By jgomez Date 2021-03-03 Time 13:23 Rev Time 0.00
Received By jgomez Date 2021-03-03 Time 13:21 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-02 Cont ID  
Sent By jgomez Date 2021-03-02 Time 18:02 Rev Time 0.00
Received By jgomez Date 2021-02-25 Time 16:33 Sent To I
Notes
***NONE***