2021-02-23 11:22:40 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21020545 |
| 2/23/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE GAS RISER IS INCOMPLETE. PLEASE PROVIDE THE |
| FOLLOWING LIST OF ITEMS ON THE DRAWING IN COMPLIANCE |
| WITH FBC- 2020 RES. FUEL GAS CODE: |
| |
| A) LABEL THE METER AS EITHER NEW OR EXISTING AND SHOW |
| THE DELIVERY PRESSURE- SECTION G2413.2. |
| |
| B) DELIVERY PRESSURE AT REGULATOR- G2413.3 & G2421.1. |
| |
| C) COPPER PIPE SIZES- MAIN SUPPLY PIPE AT METER AND |
| BRANCHES- G2413.4.1 & G2413.4.2. |
| |
| D) PROVIDE THE CORRECT BTUH OF THE TANKLESS WATER |
| HEATER. THE SUBMITTED SPECS HAS A HIGHLIGHT INDICATING |
| 150,000 BTUH HOWEVER THE RISER INDICATES 199,000 BTUH. |
| |
| E) PLEASE LABEL THE APPLIANCES AS NEW OR EXISTING. THE |
| RISER SHOWS A POOL HEATER NOT INCLUDED IN THE PERMIT |
| APPLICATION- SECTION 107.2.1 WPB. PLEASE NOTE THAT A |
| COMPLETE RISER DRAWING FOR THE SYSTEM SHALL BE |
| SUBMITTED THAT INCLUDES ALL EXISTING PIPING AND |
| APPLIANCES IN ORDER TO ENSURE A SAFER OPERATING SYSTEM- |
| PLEASE SEE SECTIONS G2412.3 & G2412.4 FBC RES. |
| |
| F) PIPE SIZING TABLES USED- FBC RES. FUEL GAS- 2020 7TH |
| EDITION, OR FBC- 2020 7TH EDITION FUEL GAS. PLEASE NOTE |
| THE SUBMITTED PIPE SIZING TABLE IS FROM THE OUTDATED |
| 2017 CODE- SECTION G2413.3. |
| |
| G) SHOW THE LOCATIONS OF SHUT OFF VALVES AND |
| REGULATORSD AT APPLIANCES- SECTIONS 2420.1 & 2421.1 FBC |
| RES. GAS. |
| |
| 2) THE RISER AND THE FLAT LINE GAS DRAWING SHALL EACH |
| BEAR THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR |
| OR QUALIFIER OF RECORD, AND SHALL ALSO INDICATE THE |
| PROJECT ADDRESS- SECTION 107.2.1 WPB. |
| |
| 3) SUBMIT SPECS FOR THE NEW RANGE AND POOL HEATER- |
| SECTION G2431.1 FBC RES.GAS. |
| |
| 4) SUBMIT THE CORRECT OUTLET AND INLET PRESSURE TABLE |
| FOR THE B42 REGULATOR. THE TABLE IN THE SUBMITTAL IS |
| FOR AN OUT PRESSURE OF 2 PSI. YOU SHOULD BE DROPPING |
| PRESSURE FROM 2 PSI TO A LOW- PRESSURE SYSTEM. PLEASE |
| NOTE THE NAVIEN WH SPECS INDICATE AN INLET PRESSURE OF |
| 10.5 IN/WC- SECTION 2421.1 FBC RES.GAS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |