Plan Review Details - Permit 21020498
Plan Review Stops For Permit 21020498
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-17 Cont ID  
Sent By cthroop Date 2021-06-17 Time 17:08 Rev Time 0.00
Received By cthroop Date 2021-06-17 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-11 Cont ID  
Sent By rmcdouga Date 2021-03-11 Time 13:59 Rev Time 0.00
Received By rmcdouga Date 2021-03-11 Time 13:59 Sent To  
Notes
2021-03-11 14:01:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PLEASE REVISE NOTES ON THE SURVEY. THE GENERATOR
 EXHAUST SHALL BE LOCATED 10 FEET FROM ANY OPENINGS INTO
 A BUILDING. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL
 AND GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE
 LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-17 Cont ID  
Sent By cthroop Date 2021-06-17 Time 17:18 Rev Time 0.00
Received By cthroop Date 2021-06-17 Time 17:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-15 Cont ID  
Sent By cthroop Date 2021-03-15 Time 15:50 Rev Time 0.00
Received By cthroop Date 2021-03-15 Time 15:38 Sent To  
Notes
2021-03-15 15:54:39PLAN REVIEW GENERATOR / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ATS
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-06-15 Cont ID  
Sent By lmarchan Date 2021-06-15 Time 09:31 Rev Time 0.00
Received By lmarchan Date 2021-06-15 Time 09:31 Sent To  
Notes
2021-06-15 09:31:25GAS APPLIED FOR SEPARATELY

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-05 Cont ID  
Sent By ccole Date 2021-04-05 Time 13:40 Rev Time 0.00
Received By ccole Date 2021-04-05 Time 12:25 Sent To  
Notes
2021-04-05 13:40:331ST REVIEW FBC-2020 RES.
 PERMIT- 21020498
 4/5/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 BOTH THE NEW AND EXISTING GAS PIPING AND APPLIANCES AT
 THE RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER
 TO FBC RES. CHAPTER 24 FUEL GAS.
  
 2) PLEASE CORRECT THE 864,000 BTU GENERATOR LOAD TO
 756,000 AS LISTED IN THE SUBMITTED GENERATOR SPECS-
 SECTION 107.2.1 WPB.
  
 3) SURVEY: PLEASE CORRECT THE 5' GENERATOR DISTANCE
 FROM OPENINGS TO 10' IN COMPLIANCE WITH R305.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-22 Cont ID  
Sent By pvalenti Date 2021-06-22 Time 07:31 Rev Time 0.00
Received By pvalenti Date 2021-06-15 Time 13:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-05 Cont ID  
Sent By ccarvaja Date 2021-04-05 Time 18:21 Rev Time 0.00
Received By ccarvaja Date 2021-03-10 Time 18:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-05 Cont ID  
Sent By ccole Date 2021-04-05 Time 13:41 Rev Time 0.00
Received By ccole Date 2021-04-05 Time 12:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-17 Cont ID  
Sent By cthroop Date 2021-06-17 Time 17:07 Rev Time 0.00
Received By cthroop Date 2021-06-17 Time 17:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-11 Cont ID  
Sent By rmcdouga Date 2021-03-11 Time 13:59 Rev Time 0.00
Received By rmcdouga Date 2021-03-11 Time 13:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-06-21 Cont ID  
Sent By rthermid Date 2021-06-21 Time   Rev Time 0.00
Received By rthermid Date 2021-06-21 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By rthermid Date 2021-03-24 Time   Rev Time  
Received By rthermid Date 2021-03-24 Time   Sent To I
Notes
2021-03-24 11:31:45ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 3/24/2021
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ADDRESS BUILDING/STRUCTURAL COMMENTS. PER THE
 FLORIDA BUILDING CODE, MECHANICAL EQUIPMENT MUST BE
 SETBACK A MINIMUM OF 10 FEET FROM ANY DOOR WINDOWS AND
 OPENINGS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved