Plan Review Details - Permit 21020405
Plan Review Stops For Permit 21020405
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-02-21 Cont ID  
Sent By cpuell Date 2021-02-21 Time 09:54 Rev Time 0.00
Received By cpuell Date 2021-02-21 Time 09:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-19 Cont ID  
Sent By rmcdouga Date 2021-04-19 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2021-04-19 Time 09:54 Sent To  
Notes
2021-04-19 10:00:35BUILDING PROVISO
  
 THE PLANS SPECIFY THE SWING DOOR AS FL17184.7 AND +/-
 65 PSF AND THE PRODUCT APPROVAL SUBMITTED IS FOR
 FL17184.9 AND +/- 50 PSF. SUBMIT THE PRODUCT APPROVAL
 SPECIFIED ON THE PLANS FOR APPROVAL BEFORE
 INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-01 Cont ID  
Sent By rmcdouga Date 2021-04-01 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2021-04-01 Time 15:03 Sent To  
Notes
2021-04-01 14:38:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT
 MATCH THE IMPACT RATED ONES SPECIFIED BY THE DESIGNER
 OF RECORD IN THE WINDOW AND DOOR SCHEDULES ON THE
 PLANS. THE ROOFING PRODUCT APPROVALS ARE ALSO
 DIFFERENT. SUBMIT THE ONES THAT ARE APPROVED BY THE
 DESIGNER OF RECORD AND LISTED ON THE PLANS. CIRCLE OR
 HI-LIGHT THE SPECIFIC ITEMS AND DESIGN PRESSURES IN THE
 PRODUCT APPROVALS. FBC AMENDMENTS 107.3.4 - PROVIDE TWO
 SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW
 (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR
 TYPES. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 2) THE SURFACE WATER DRAINAGE PLAN DOES NOT ADEQUATELY
 SHOW THAT THE SURFACE WATER WILL BE CONTAINED ON THE
 LOT AND HAS A 6 INCH FALL AWAY FROM THE BUILDING.
 PROVIDE A MORE DETAILED DRAINAGE PLAN.
 FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED
 TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM). EXCEPTION:
 WHERE LOT LINES, WALLS, SLOPES OR OTHER PHYSICAL
 BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL WITHIN 10
 FEET (3048 MM), DRAINS OR SWALES SHALL BE CONSTRUCTED
 TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. IMPERVIOUS
 SURFACES WITHIN 10 FEET (3048 MM) OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 PERCENT AWAY
 FROM THE BUILDING.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-09 Cont ID  
Sent By rmcdouga Date 2021-03-09 Time 13:14 Rev Time 0.00
Received By rmcdouga Date 2021-03-09 Time 09:23 Sent To  
Notes
2021-03-09 13:29:27PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON PAGE 004, 3-4 THE FOUNDATION PLAN IS MISSING SOME
 OF THE FILLED CELLS AT THE EAST WALL OF THE DINING
 ROOM. FBC 107.2.1
  
 2) THE PRODUCT APPROVALS FOR THE WINDOWS AND DOORS HAVE
 MULTIPLE TYPES OF WINDOWS AND DOORS LISTED IN THE
 PRODUCT APPROVALS WITH DIFFERENT DESIGN PRESSURES, ETC.
 CIRCLE OR HI-LIGHT THE ITEMS THAT ARE SPECIFIC TO THIS
 PROJECT. FBC 107.2.1
  
 3) THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE THE PRODUCT APPROVALS IN WRITING. FBC 107.3.4 -
 PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS,
 WINDOW (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR
 DOOR TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 4) THE PRODUCT APPROVALS FOR THE WINDOWS AND SLIDING
 GLASS DOOR ARE NOT IMPACT RATED. SUBMIT A KEY PLAN, AN
 INSTALLATION SCHEDULE AND PRODUCT APPROVALS FOR THE
 REQUIRED IMPACT PROTECTION DEVICES. FBC 107.2.1
  
 5) PROVIDE A SURFACE WATER DRAINAGE PLAN FOR THE SITE
 THAT SHOWS COMPLIANCE WITH FBC-R401.3 DRAINAGE. SURFACE
 DRAINAGE SHALL BE DIVERTED TO A STORM SEWER CONVEYANCE
 OR OTHER APPROVED POINT OF COLLECTION THAT DOES NOT
 CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN SURFACE
 WATER AWAY FROM FOUNDATION WALLS. THE GRADE SHALL FALL
 A MINIMUM OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET
 (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-02-17 Cont ID  
Sent By fgiaquin Date 2021-02-17 Time 20:21 Rev Time 0.00
Received By fgiaquin Date 2021-02-17 Time 19:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-19 Cont ID  
Sent By rmcdouga Date 2021-04-19 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2021-04-06 Time 06:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-01 Cont ID  
Sent By rmcdouga Date 2021-04-01 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2021-03-17 Time 18:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-09 Cont ID  
Sent By rmcdouga Date 2021-03-09 Time 13:29 Rev Time 0.00
Received By rmcdouga Date 2021-02-08 Time 17:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-05-04 Cont ID  
Sent By lmarchan Date 2021-05-04 Time 09:03 Rev Time 0.00
Received By lmarchan Date 2021-04-26 Time 16:26 Sent To  
Notes
2021-05-04 09:03:23RECEIPT MU-2021-20851 - $0.00 DUE
2021-04-26 16:27:064/26/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-03-09 Cont ID  
Sent By rmcdouga Date 2021-03-09 Time 09:24 Rev Time 0.00
Received By rmcdouga Date 2021-03-09 Time 09:23 Sent To  
Notes
2021-03-09 09:29:08PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-02-18 Cont ID  
Sent By hmoser Date 2021-02-18 Time 11:05 Rev Time 0.00
Received By hmoser Date 2021-02-18 Time 10:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-02-23 Cont ID  
Sent By cthroop Date 2021-02-23 Time 14:40 Rev Time 0.00
Received By cthroop Date 2021-02-23 Time 11:03 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2021-04-19 Cont ID  
Sent By rmcdouga Date 2021-04-19 Time 09:51 Rev Time 0.00
Received By rmcdouga Date 2021-04-19 Time 09:51 Sent To  
Notes
2021-04-19 09:54:16ASPHALT SHINGLES: FL18355.1
 UNDERLAYMENT: FL12328.1

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-04-01 Cont ID  
Sent By rmcdouga Date 2021-04-01 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2021-04-01 Time 15:04 Sent To  
Notes
2021-04-01 15:05:42THE PRODUCT APPROVAL FOR THE ROOF SHINGLES LISTED ON
 THE PLANS IS NOT THE ONE THAT WAS SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2021-03-09 Cont ID  
Sent By rmcdouga Date 2021-03-09 Time 13:14 Rev Time 0.00
Received By rmcdouga Date 2021-03-09 Time 13:14 Sent To  
Notes
2021-03-09 13:16:12ASPHALT SHINGLES - FL10124-R28

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-06 Cont ID  
Sent By medwards Date 2021-04-06 Time 16:57 Rev Time 0.00
Received By medwards Date 2021-04-06 Time 16:55 Sent To  
Notes
2021-04-06 16:58:02ORIGINAL SIGNED AND SEALED PAPER DRAWING ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-18 Cont ID  
Sent By medwards Date 2021-03-18 Time 11:08 Rev Time 0.00
Received By medwards Date   Time   Sent To  
Notes
2021-03-18 11:09:08ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-19 Cont ID  
Sent By equinone Date 2021-02-09 Time 16:42 Rev Time 0.00
Received By shill Date 2021-02-09 Time 16:42 Sent To  
Notes
2021-02-19 17:59:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLEASE HAVE LILLIAN GONZALEZ, PE REVIEW FAC
 61G15-22.001(C)(3):
  
 BEGINNING WITH THE FIFTH EDITION OF THE FLORIDA
 BUILDING CODE, ALL LICENSEES ACTIVELY PARTICIPATING IN
 THE DESIGN OF ENGINEERING WORKS OR SYSTEMS IN
 CONNECTION WITH BUILDINGS, STRUCTURES, OR FACILITIES
 AND SYSTEMS COVERED BY THE FLORIDA BUILDING CODE, AS
 IDENTIFIED WITHIN SECTION 553.73(1)(A), F.S., SHALL:
 (A) COMPLETE AT LEAST ONE (1) ADVANCED FLORIDA BUILDING
 CODE COURSE WITHIN TWELVE (12) MONTHS OF EACH EDITION
 OF THE FLORIDA BUILDING CODE EFFECTIVE DATE,
 (B) PROVIDE THE BOARD WITH A COPY OF A CERTIFICATE OF
 COMPLETION WHICH SHOWS: COURSE NUMBER, COURSE HOURS,
 CODE EDITION YEAR, AND CODE OR COURSE FOCUS. THIS
 COURSE MAY ALSO COUNT TOWARDS THE AREA OF PRACTICE
 REQUIREMENT FOR CONTINUING EDUCATION SET FORTH IN RULE
 61G15-22.001, F.A.C.
  
 ALTHOUGH THE RULE STATES THAT ENGINEERS HAVE A YEAR TO
 COMPLETE THE COURSE, FBPE HAS CONTACTED US TO ADVISE
 THAT, IF AN ENGINEER IS DESIGNING TO FBC2020, THEY
 SHOULD HAVE TAKEN THE COURSE PRIOR TO DESIGN SO THEY
 KNOW WHAT CHANGED.
  
 IF YOU HAVE QUESTIONS, PLEASE CONTACT FBPE DIRECTLY. IF
 THE COURSE IS NOT TAKEN AND THE WEBSITE
 MYFLORIDALICENSE.COM UPDATED PRIOR TO THE TIME THAT
 THIS PERMIT IS READY FOR ISSUANCE, PLEASE CONTACT ME.
  
  
  
  
2021-02-09 16:42:51ORIGINAL PAPER DRAWINGS WITH SIGNATURE AND SEAL. ROUTED
 TO STORAGE.

Review Stop Z ZONING
Rev No 1 Status P Date 2021-03-08 Cont ID  
Sent By rthermid Date 2021-03-08 Time 22:29 Rev Time 0.00
Received By kalexand Date 2021-03-08 Time 22:29 Sent To  
Notes
***NONE***