Plan Review Details - Permit 21020231
Plan Review Stops For Permit 21020231
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2021-04-15 Cont ID  
Sent By rmcphers Date 2021-04-15 Time 11:18 Rev Time 0.00
Received By rmcphers Date 2021-04-15 Time 11:18 Sent To  
Notes
2021-04-15 11:19:16SEPARATE PERMIT REQUIRED FOR ALL BUILDING AND
 STRUCTURAL WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-06 Cont ID  
Sent By rmcphers Date 2021-04-06 Time 08:54 Rev Time 0.00
Received By rmcphers Date 2021-04-06 Time 08:53 Sent To  
Notes
2021-04-06 08:58:27RESTAURANT ALT.
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOF TOP EQUIPMENT IS SUBJECT TO GRAVITY AND WIND
 LOADS. FOR DRAWING S1- PLEASE PROVIDE STRUCTURAL
 CALCULATIONS FOR SUCH OR SIGNED AND SEALED STRUCTURAL
 MOUNTING DETAILS FROM AN ARCHITECT OR ENGINEER FBC
 1609. FBC EXISTING BUILDING 707.2ADDITION OR
 REPLACEMENT OF ROOFING OR REPLACEMENT OF EQUIPMENT.
 WHERE ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT
 OF EQUIPMENT RESULTS IN ADDITIONAL DEAD LOADS,
 STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING OR
 EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 2) FBC 1510.10 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By rmcphers Date 2021-02-25 Time 08:59 Rev Time 0.00
Received By rmcphers Date 2021-02-25 Time 07:39 Sent To  
Notes
2021-02-25 08:59:38RESTAURANT ALT.
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE
 THE DRAWINGS SHOWING THE DESIGN PER THE CODE IN EFFECT
 (2020 FBC AND ASCE 7-16)
 2) ROOF TOP EQUIPMENT IS SUBJECT TO GRAVITY AND WIND
 LOADS ? PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR SUCH
 OR SIGNED AND SEALED STRUCTURAL MOUNTING DETAILS FROM
 AN ARCHITECT OR ENGINEER FBC 1609 ? FBC EXISTING
 BUILDING 707.2ADDITION OR REPLACEMENT OF ROOFING OR
 REPLACEMENT OF EQUIPMENT.
 WHERE ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT
 OF EQUIPMENT RESULTS IN ADDITIONAL DEAD LOADS,
 STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING OR
 EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 3) PLEASE SHOW THE WIND DESIGN CRITERIA USED PER FBC
 1603.1.4
 4) FBC 1510.10 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10.
 5) A BUILDING PERMIT APPLICATION COMPLETED BY A
 CONTRACTOR LICENSED TO PERFORM THE STRUCTURAL WORK IS
 REQUIRED ? IF THE STRUCTURAL WORK IS ON A SEPARATE
 PERMIT PLEASE PROVIDE THE PERMIT NUMBER.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-02-25 Cont ID  
Sent By jleahy Date 2021-02-25 Time 09:46 Rev Time 0.00
Received By jleahy Date 2021-02-25 Time 09:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-02-25 Cont ID  
Sent By pleduc Date 2021-02-25 Time   Rev Time 0.00
Received By pleduc Date 2021-02-25 Time 11:46 Sent To  
Notes
2021-02-25 12:05:59FIRE PROVISO:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 7TH EDITION
 OF FLORIDA FIRE PREVENTION CODE WHICH INCLUDES THE 2018
 EDITION OF
 NFPA 1 AND NFPA 101.
  
 **PLEASE ENSURE COMPLIANCE WITH THE UPDATED EDITIONS(IT
 APPEARS THERE ARE NO CONCERNS),
 UPDATE YOUR RECORDS AND REVISE IF APPLICABLE ON ANY
 RESUBMISSION/REVISION.
  
  
 THE HOOD & SUPPRESSION SYSTMES SHALL BE INSTALLED UNDER
 SEPARATE
 PERMITS & SHOP DRAWINGS.
  
  
 **PLEASE ENSURE COMPLIANCE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-04-19 Cont ID  
Sent By abelisle Date 2021-04-19 Time 13:42 Rev Time 0.00
Received By abelisle Date 2021-04-19 Time 13:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-04-08 Cont ID  
Sent By abelisle Date 2021-04-08 Time 14:24 Rev Time 0.00
Received By abelisle Date 2021-04-08 Time 14:24 Sent To  
Notes
2021-04-08 14:25:061ST REVIEW FBC-2017 GAS
 PERMIT-21020231
 1/4/2021
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS.
 10.4, 10.5 OF NFPA 96-08.
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC
 SEC.304.9.3 OR 2017 FBC R G2407.9.3. COMBINED
 COMBUSTION AIR AND VENTILATION AIR SYSTEM.
 3) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 2017 FBC FUEL GAS SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8,
 G2413.1, G2413.2, G2413.3.
 4) SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS SEC. 402.3 OR 2017 FBC FUEL
 GAS RES. SEC. G2413.3
 5) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 6) GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL
 GAS SEC. 402.2 AND 301.3 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.2 AND G2404.3.
 7) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2 OR 2017
 FBC FUEL GAS RES. SEC. G2413.2.
 8) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.4.1.
 9) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
 10) TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 11) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
 12) THE SUBMITED GAS RISER DRAWING, FLOOR PLAN AND GAS
 TABLE THAT ARE ILLEGIBLE. SUBMIT A CLEAR AND LEGIBLE
 SHEET THAT REFLECTS THE SCOPE OF WORK BEING DONE. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-04-06 Cont ID  
Sent By ccole Date 2021-04-06 Time 09:29 Rev Time 0.00
Received By ccole Date 2021-04-06 Time 07:30 Sent To  
Notes
2021-04-08 13:50:07PLAN REVIEW FOR GAS WAS DONE UNDER 21020231.
 THE PLANS WERE MOVED FO A MASTER PERMIT 20121263, BUT
 THE COMMENTS FOR GAS REVIEW THAT WAS COMPLETED WERE NOT
 MOVED.
 THE PLANS GOT REVIEWED AS IF NEW AND THE PREVIOUS
 REVIEWER HAS WORKED OUT ITEMS ALREADY AND ALSO DID A
 SITE VISIT TO CLARIFY THE GAS THAT WAS INSTALLED PRIOR
 TO PERMIT.
  
 FOR THE 3RD REVIEW ATELYO WILL PASTE HIS COMMENTS INTO
 THE NOTES AND HE WILL DO FINAL REVIEW UPON RESUBMITTAL.
2021-04-06 09:31:292ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21020231
 4/6/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS PRINTED BELOW FROM THE 1ST REVIEW WERE NOT
 ADDRESSED AND THERE WAS NO NARRATIVE RESPONSE PROVIDED.
 PLEASE COMPLY WITH THE COMMENTS. BASED ON THE SCOPE OF
 WORK SHOWN ON THE PLANS THE $5500.00 VALUE FOR THE
 PROJECT APPEARS LOW. PLEASE PROVIDE COPIES OF CONTRACTS
 AND/OR COPIES OF ESTIMATES AND INVOICES FOR THE ENTIRE
 SCOPE OF WORK INCLUDING LABOR, MATERIAL, FIXTURES,
 APPLIANCES, EQUIPMENT, DESIGN FEES AND SITE WORK-
 SECTION 109.3 WPB.
  
 1) GAS RISER: THE TOTAL 930,000 BTU LOAD IS INCORRECT.
 TOTAL LOAD SHOWN ON THE RISER INCLUDING THE FUTURE WH
 IS 1,130,000 BTU- SECTION 402.2 FBC FG.
  
 2) GAS RISER: SHOW THE PIPE SIZING TABLE USED. THE LOW-
 PRESSURE TABLE 402.4(2) WITH A PRESSURE DROP OF 0.5
 IN.WC SHOWS AN 1-1/2 IN. MAIN SUPPLY PIPE FROM THE
 METER IS UNDERSIZED FOR 1,130,000 GAS LOAD AT 41 FT.
 TOTAL LENGTH.
  
 3) GAS RISER: SHOW REQUIRED REGULATORS AT EACH
 APPLIANCE CONNECTION TO DROP PRESSURE FROM 12 IN.WC-
 SECTION 410.1.
  
 4) GAS RISER: SHOW THE AUTOMATIC SHUT OFF VALVE FOR THE
 COOKING LINE GAS SUPPLY- SECTION 10.4.1 NFPA 96.
  
 5) A1: SHOW THE LOCATION OF THE NEW FUTURE WATER
 HEATER- SECTION 624.1 FBC FG.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCE- SECTION 623.1 FBC FG.
  
 7) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING
 APPLIANCES AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SECTION 304.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By ccole Date 2021-02-25 Time 15:18 Rev Time 0.00
Received By ccole Date 2021-02-25 Time 12:40 Sent To  
Notes
2021-02-25 15:18:501ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21020231
 2/25/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: THE TOTAL 930,000 BTU LOAD IS INCORRECT.
 TOTAL LOAD SHOWN ON THE RISER INCLUDING THE FUTURE WH
 IS 1,130,000 BTU- SECTION 402.2 FBC FG.
  
 2) GAS RISER: SHOW THE PIPE SIZING TABLE USED. THE LOW-
 PRESSURE TABLE 402.4(2) WITH A PRESSURE DROP OF 0.5
 IN.WC SHOWS AN 1-1/2 IN. MAIN SUPPLY PIPE FROM THE
 METER IS UNDERSIZED FOR 1,130,000 GAS LOAD AT 41 FT.
 TOTAL LENGTH.
  
 3) GAS RISER: SHOW REQUIRED REGULATORS AT EACH
 APPLIANCE CONNECTION TO DROP PRESSURE FROM 12 IN.WC-
 SECTION 410.1.
  
 4) GAS RISER: SHOW THE AUTOMATIC SHUT OFF VALVE FOR THE
 COOKING LINE GAS SUPPLY- SECTION 10.4.1 NFPA 96.
  
 5) A1: SHOW THE LOCATION OF THE NEW FUTURE WATER
 HEATER- SECTION 624.1 FBC FG.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCE- SECTION 623.1 FBC FG.
  
 7) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING
 APPLIANCES AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SECTION 304.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
2021-02-25 15:18:331ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21020231
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
 1) GAS RISER: THE TOTAL 930,000 BTU LOAD IS INCORRECT.
 TOTAL LOAD SHOWN ON THE RISER INCLUDING THE FUTURE WH
 IS 1,130,000 BTU- SECTION 402.2 FBC FG.
 2) GAS RISER: SHOW THE PIPE SIZING TABLE USED. THE LOW-
 PRESSURE TABLE 402.4(2) WITH A PRESSURE DROP OF 0.5
 IN.WC SHOWS AN 1-1/2 IN. MAIN SUPPLY PIPE FROM THE
 METER IS UNDERSIZED FOR 1,130,000 GAS LOAD AT 41 FT.
 TOTAL LENGTH.
 3) GAS RISER: SHOW REQUIRED REGULATORS AT EACH
 APPLIANCE CONNECTION TO DROP PRESSURE FROM 12 IN.WC-
 SECTION 410.1.
 4) GAS RISER: SHOW THE AUTOMATIC SHUT OFF VALVE FOR THE
 COOKING LINE GAS SUPPLY- SECTION 10.4.1 NFPA 96.
 5) A1: SHOW THE LOCATION OF THE NEW FUTURE WATER
 HEATER- SECTION 624.1 FBC FG.
 6) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE COOKING
 APPLIANCE- SECTION 623.1 FBC FG.
 7) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING
 APPLIANCES AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SECTION 304.1 FBC FG.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-04-19 Time   Rev Time 0.00
Received By aoliver Date 2021-04-14 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-04-06 Time   Rev Time 0.00
Received By aoliver Date 2021-04-01 Time 11:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-25 Cont ID  
Sent By dbattles Date 2021-02-25 Time 16:42 Rev Time 0.00
Received By dbattles Date 2021-02-04 Time 16:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-02-25 Cont ID  
Sent By medwards Date 2021-02-25 Time 09:38 Rev Time 0.00
Received By medwards Date 2021-02-25 Time 07:21 Sent To  
Notes
2021-02-25 09:38:44 
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-04-21 Cont ID  
Sent By ccole Date 2021-04-19 Time 16:31 Rev Time 0.00
Received By ccole Date 2021-04-19 Time 10:29 Sent To  
Notes
2021-04-19 16:32:15 
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-04-06 Cont ID  
Sent By ccole Date 2021-04-06 Time 09:24 Rev Time 0.00
Received By ccole Date 2021-04-06 Time 07:30 Sent To  
Notes
2021-04-06 09:24:422ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21020231
 4/6/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1 & P0.1: GREASE INTERCEPTOR:
  
 A) THE GREASE WASTE CALCULATIONS SHOW 30 SEATS HOWEVER
 THE ARCHITECTURAL FLOOR PLAN SHOWS 36 SEATS.
  
 B) THE CALCULATIONS ARE USING A FACTOR OF 10 GALLONS
 PER SEAT WHICH IS FOR SINGLE SERVICE ARTICLE
 RESTAURANTS. THE PB BRISKET AND BBQ HAS A FULL DINNER,
 DESSERT, SALAD, SIDES, AND DRINKS MENU WHICH REQUIRES A
 FACTOR OF 25 GALLONS PER SEAT. PLEASE SEE SECTION
 64E-6.010 FAC.
  
 C) P0.1: PLEASE CLARIFY WHICH OF THE TWO GB-75 SCHIER
 GREASE INTERCEPTORS IS THE EXISTING ONE- THE LEGACY OR
 THE NEW GREAT BASIN? PLEASE NOTE: THE 653 LB. CAPACITY
 OF THE LEGACY IS UNDERSIZED BASED ON THE CURRENT
 CALCULATIONS, AND THE NEW GREAT BASIN HAS A RECENT
 DESIGN DATE OF JULY 2020. I AM NOT ABLE TO FIND A
 RECENT PERMIT RECORD FOR A NEW GREASE INTERCEPTOR AT
 801 VILLAGE BLVD # 307.IT APPEARS THAT THE EXISTING
 INTERCEPTOR IS THE UNDERSIZED LEGACY.
  
 2) P3.1: PLEASE CORRECT NOTE #2 WHICH INDICATES AN
 EXISTING GAS SYSTEM. PLEASE REFER TO SHEET A-1 WHICH
 SHOWS A NEW GAS METER AND PIPING SYSTEM, AND TO THE
 RISER DRAWING SUBMITTED BY HI-TECH GAS CONTRACTOR-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By ccole Date 2021-02-25 Time 14:43 Rev Time 0.00
Received By ccole Date 2021-02-25 Time 12:40 Sent To  
Notes
2021-02-25 14:43:161ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21020231
 2/25/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: PROVIDE AN INDIRECT WASTE DETAIL FOR THE
 NEW 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P. SHOW
 EACH WELL OF THE SINK DISCHARGING INDEPENDENTLY TO A
 WASTE RECEPTOR- SECTION 802.4 FBC P.
  
 2) A1 & NEW COOKING APPLIANCES ARE BEING INSTALLED
 WHICH WILL CREATE GREASE LADEN DRAINAGE FROM THE SINK.
 PROVIDE A GREASE INTERCEPTOR IN COMPLIANCE WITH SECTION
 1003.3.1 FBC P. REVISE THE PLANS TO SHOW THE LOCATION
 AND PROVIDE GREASE WASTE CALCULATIONS, PLUMBING PIPING
 LAYOUT AND ISOMETRIC DRAWING- SECTION 107.3.5.1.3 WPB.
  
 3) A1: PLEASE PROVIDE A SCOPE OF WORK FOR A PLUMBING
 DEMOLITION AND ALTERATIONS- SECTION 107.2.1 WPB. THE
 PREVIOUS ICE CREAM SHOP RECORD DRAWINGS UNDER PERMIT
 04031091 SHOW 4 FLOOR SINKS AND 1 FLOOR DRAIN IN THE
 SERVING AREA WHICH ARE NOT SHOWN ON THE PLAN. ARE THESE
 FIXTURES TO REMAIN IN USE? THE NEW PLAN ALSO SHOWS 2
 EXISTING HAND SINKS IN THE SERVING AREA BUT THE RECORD
 DRAWINGS SHOW ONLY ONE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-15 Cont ID  
Sent By rmcphers Date 2021-04-15 Time 11:29 Rev Time 0.00
Received By rmcphers Date 2021-04-15 Time 11:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-04-06 Cont ID  
Sent By rmcphers Date 2021-04-06 Time 09:19 Rev Time 0.00
Received By rmcphers Date 2021-04-06 Time 09:19 Sent To  
Notes
2021-04-06 09:19:45SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By rmcphers Date 2021-02-25 Time 09:01 Rev Time 0.00
Received By rmcphers Date 2021-02-25 Time 09:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-04-01 Cont ID  
Sent By eschneid Date 2021-04-01 Time 15:50 Rev Time 0.25
Received By eschneid Date 2021-04-01 Time 15:50 Sent To  
Notes
2021-04-01 15:51:42PASSED W/PROVISO
  
 NEW ROOFTOP EQUIPMENT IS TO BE SCREENED PRIOR TO FINAL
 104 INSPECTION. ANY PHYSICAL SCREENING REQUIRES A
 PERMIT PRIOR TO INSTALLATION.
  
 DISCUSSED WITH TOM HIND ON 4/1/21

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-30 Cont ID  
Sent By eschneid Date 2021-02-25 Time 16:42 Rev Time 0.25
Received By eschneid Date 2021-02-25 Time 16:42 Sent To  
Notes
2021-03-30 11:24:56FAILED
  
 1) THE PLANS SHOW A NEW EXHAUST FAN AND A NEW MAKE UP
 AIR FAN ON THE ROOF. THE VILLAGE COMMONS DEVELOPMENT
 REGULATIONS REQUIRE THAT NEW ROOFTOP MECHANICAL
 EQUIPMENT BE SCREENED FROM VIEW OF THE PUBLIC. PROVIDE
 DIMENSIONED DRAWINGS WHICH VERIFY THAT THE FULL HEIGHT
 OF THE EQUIPMENT (INCLUDING CURBS) IS SCREENED FROM
 VIEW TO THE FRONT AND REAR OF THE BUILDING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  