Plan Review Details - Permit 21020181
Plan Review Stops For Permit 21020181
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-02-11 Cont ID  
Sent By rmcdouga Date 2021-02-11 Time 11:48 Rev Time 0.00
Received By rmcdouga Date 2021-02-11 Time 11:48 Sent To  
Notes
2021-02-11 11:58:40SEPARATE SUB-PERMITS ARE REQUIRED FOR PLUMBING AND
 ELECTRIC.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-02-10 Cont ID  
Sent By ppetty Date 2021-02-10 Time 13:10 Rev Time 0.00
Received By ppetty Date 2021-02-10 Time 13:10 Sent To  
Notes
2021-02-10 13:13:16CHECK 680.8(A)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-05 Cont ID  
Sent By lcrespo Date 2021-03-05 Time 13:10 Rev Time 0.00
Received By lcrespo Date 2021-03-05 Time 13:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-18 Cont ID  
Sent By shill Date 2021-02-18 Time 10:10 Rev Time 0.00
Received By shill Date 2021-02-08 Time 12:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-03-05 Cont ID  
Sent By lcrespo Date 2021-03-05 Time 13:11 Rev Time 0.00
Received By lcrespo Date 2021-03-05 Time 13:11 Sent To  
Notes
2021-03-05 13:11:3603/05/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-09 Cont ID  
Sent By lcrespo Date 2021-02-09 Time 10:38 Rev Time 0.00
Received By lcrespo Date 2021-02-09 Time 10:23 Sent To  
Notes
2021-02-09 10:38:2102/09/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2. PLEASE PROVIDE THE POOL PUMP CURVE AND INDICATE THE
 PUMP CURVE, WHICH IS KEY FOR THE PUMP BEING INSTALLED
 ON THIS SYSTEM. THIS IS NEEDED TO CONFIRM THE MAXIMUM
 SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN AND THE PUMP, FILTER, AND CHLORINE GANARATORPER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-11 Cont ID  
Sent By rmcdouga Date 2021-02-11 Time 11:49 Rev Time 0.00
Received By rmcdouga Date 2021-02-11 Time 11:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-02-17 Cont ID  
Sent By rthermid Date 2021-02-17 Time   Rev Time  
Received By rthermid Date 2021-02-17 Time   Sent To I
Notes
***NONE***