2021-02-08 12:20:23THE FOLLOWING COMMENTS WERE SUBMITTED BY LIEUTENANT
 BRIAN DOLAN, BUREAU OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE:
  
 WHERE ADDITION OR MODIFICATION IS MADE TO AN EXISTING
 SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE NEW
 PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS THAN
 200 PSI (13.8 BAR) FOR 2 HOURS.
  
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED. SYSTEM WILL BE
 PLACED IN REGULAR SERVICE PRIOR TO LEAVING SITE FOR THE
 EVENING.
  
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-17 Cont ID  
Sent By medwards Date 2021-02-17 Time 11:03 Rev Time 0.00
Received By medwards Date 2021-02-05 Time 11:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-02-17 Cont ID  
Sent By medwards Date 2021-02-17 Time 11:03 Rev Time 0.00
Received By medwards Date 2021-02-17 Time 11:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-19 Cont ID  
Sent By jgomez Date 2021-02-19 Time 09:24 Rev Time 0.00
Received By jgomez Date 2021-02-19 Time 08:57 Sent To  
Notes
2021-02-19 09:25:44SHEET FP1 OF 1 WITH ENGINEER'S ORIGINAL SEAL/SIGNATURE
 MATCHES APPROVED ONE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-05 Cont ID  
Sent By medwards Date 2021-02-05 Time 14:16 Rev Time 0.00
Received By medwards Date 2021-02-05 Time 14:16 Sent To  
Notes
2021-02-05 14:16:51PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  