Plan Review Details - Permit 21020105
Plan Review Stops For Permit 21020105
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-03-16 Cont ID  
Sent By jwitmer Date 2021-03-16 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2021-03-16 Time 10:16 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-02-17 Cont ID  
Sent By jwitmer Date 2021-02-17 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2021-02-17 Time 08:59 Sent To  
Notes
2021-02-17 10:22:39COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-16 Cont ID  
Sent By jwitmer Date 2021-03-16 Time 10:33 Rev Time 0.00
Received By jwitmer Date 2021-03-16 Time 10:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-17 Cont ID  
Sent By jwitmer Date 2021-02-17 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2021-02-17 Time 08:59 Sent To  
Notes
2021-02-17 08:59:58WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2021 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020105
 ADD: 515 N FLAGLER DR. SUITE: 600
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] CONTACT: DARA NUNEZ
  
 2021 FLORIDA BUILDING CODE W 2021 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2021 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 17TH/2021
 ACTION: DENIED
  
 1) SHEET A0.01 GENERAL INFORMATION.
 1A) UNDER THE HEADING APPLICABLE CODES LIST THE FLORIDA
 FAMILY OF CODES AS THE FLORIDA BUILDING CODE 6TH
 EDITION. PLEASE UPDATE ALL PLANS THAT MAKE REFERENCE TO
 THE 2017 6TH EDITION OF THE FLORIDA FAMILY OF CODES.
 DEC. 31ST/ 2020 FLORIDA ADOPTED STATEWIDE THE 7TH
 EDITION OF THE 2020 FLORIDA FAMILY OF CODES.
  
 1B) UNDER THE HEADING PROJECT INFORMATION THE PLANS
 STATE THE SQUARE FOOT AREA OF 3,348 SQ. FT. OF WORK
 AREA BUT THE PLANS ARE SILENT AS TO THE OCCUPANT LOAD.
 PLEASE REFER TO THE 2020 FBC-BUILDING TABLE
 1004.1.2.CODE CHANGE FOR BUSINESS OCCUPANCY, THE
 OCCUPANT LOAD FACTOR IS NOW 150 GROSS NO LONGER 100
 GROSS. PLEASE PROVIDE THE OCCUPANT LOAD FOR THE 2020
 FBC-BUILDING THIS WILL HELP YOU IN THIS CASE.
  
 1C) PLEASE PROVIDE COMPLIANCE WITH THE 2020 FBC-B
 SECTION/ TABLE 1006.2.1 MAXIMUM COMMON PATH OF TRAVEL
 ON THE SHEET A0.01 AND SHOW THE MAXIMUM COMMON PATH OF
 TRAVEL FROM THE FURTHEST POINT (BREAK ROOM AREA) IN THE
 NEWLY FORMED TENANT SPACE ON THE LIFE SAFETY SHEET.
  
 2) SHEET A1.12 SHOWS THE FRONT ENTRY PAIR OF DOORS AS
 OUTSWING DOORS IDENTIFIED AS DOOR # 001. THERE ARE A
 PAIR OF DOORS WITHIN 3 FEET OF THE FRONT ENTRY DOORS
 THAT HELP CREATE THE REQUIRED ELEVATOR LOBBY. THE
 ARCHITECTURAL AND ELECTRICAL SHEETS ARE SILENT IF THESE
 DOORS ARE ON MAGNETIC HOLD OPEN DEVICES. WE ARE TRYING
 TO ACHIEVE COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY
 CODE SECTION ACCESS. CODE 404.2.6 DOORS IN SERIES. THE
 DISTANCE BETWEEN 2 HINGED DOORS OR PIVOTED DOORS IN
 SERIES SHALL BE 48 INCHES MINIMUM PLUS THE WIDTH OF
 DOORS SWINGING INTO THE SPACE. SEE FIGURE 404.2.6. IF
 THE ELEVATOR LOBBY DOORS ARE ON MAGNETIC HOLD OPEN
 DEVICES WHEN THE FIRE ALARM GOES OFF THE ELEVATOR DOORS
 WILL AUTOMATICALLY CLOSE AND ANYONE IN A WHEEL CHAIR
 WOULD GO TO THE STAIRWELL FOR THE AREA OF RESCUE
 ASSISTANCE, NOT TRAVEL INTO THE ELEVATOR LOBBY. PLEASE
 MAKE A NOTATION IF THE ELEVATOR LOBBY DOORS ARE ON
 MAGNETIC HOLD OPEN DEVICES.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-25 Cont ID  
Sent By jleahy Date 2021-03-25 Time 10:12 Rev Time 0.00
Received By jleahy Date 2021-03-25 Time 10:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-16 Cont ID  
Sent By fgiaquin Date 2021-02-16 Time 21:22 Rev Time 0.00
Received By fgiaquin Date 2021-02-16 Time 20:26 Sent To  
Notes
2021-02-16 21:22:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FIRE ALARM SHOWN ON PLAN IS REQUIRED TO BE SUBMITTED
 AS A SEPARATE STAND ALONE PERMIT W/ SEPARATE PLANS.
 REMOVE FA SHOWN FROM PLAN. FBC 107.2.1 FBC 105.1
  
 2. PROVIDE NOTE ON PLAN THAT LOW VOLTAGE/DATE SHOWN
 REQUIRES A SEPARATE LOW VOLTAGE PERMIT. FBC 107.2.1 FBC
 105.1
  
 3. PROVIDE NOTE ON PLAN THAT ACCESS CONTROL SHOWN
 REQUIRES A SEPARATE ACCESS CONTROL PERMIT. FBC 107.2.1
 FBC 105.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-02-10 Cont ID  
Sent By pleduc Date 2021-02-10 Time   Rev Time 0.00
Received By pleduc Date 2021-02-10 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-25 Cont ID  
Sent By jleahy Date 2021-03-25 Time 11:07 Rev Time 0.00
Received By jleahy Date 2021-03-12 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-02-24 Time   Rev Time 0.00
Received By ccarvaja Date 2021-02-09 Time 11:03 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-02-17 Cont ID  
Sent By jwitmer Date 2021-02-17 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2021-02-17 Time 10:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-02-22 Cont ID  
Sent By medwards Date 2021-02-22 Time 15:32 Rev Time 0.00
Received By medwards Date 2021-02-22 Time 15:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-03-23 Cont ID  
Sent By ccole Date 2021-03-23 Time 10:53 Rev Time 0.00
Received By ccole Date 2021-03-23 Time 10:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 15:27 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 14:38 Sent To  
Notes
2021-02-24 15:27:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21020105
 2/24/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P6.1: THE COLD WATER INLET FOR THE WATER
 HEATER SHALL HAVE A VALVE THAT SERVES ONLY THE WATER
 HEATER- SECTION 503.1 FBC P. A FULL OPEN VALVE IS
 REQUIRED- SECTION 606.1(8).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-25 Cont ID  
Sent By jleahy Date 2021-03-25 Time 11:07 Rev Time 0.00
Received By jleahy Date 2021-03-25 Time 11:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-22 Cont ID  
Sent By medwards Date 2021-02-22 Time 16:06 Rev Time 0.00
Received By medwards Date 2021-02-22 Time 16:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-02-12 Cont ID  
Sent By elevesqu Date 2021-02-12 Time 17:04 Rev Time 0.00
Received By elevesqu Date 2021-02-12 Time 17:04 Sent To  
Notes
***NONE***