Plan Review Details - Permit 21010798
Plan Review Stops For Permit 21010798
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 08:21 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 07:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-02-17 Cont ID  
Sent By ccole Date 2021-02-17 Time 15:33 Rev Time 0.00
Received By ccole Date 2021-02-17 Time 13:15 Sent To  
Notes
2021-02-17 15:45:512ND GAS REVIEW FBC-2020
 PERMIT- 21010798
 2/17/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) R & R CONSTRUCTION AND CONSULTING SERVICES LLC IS
 THE GENERAL CONTRACTOR FOR THE MAIN PROJECT, IS NOT A
 LICENSED ENGINEER, AND IS NOT PROVIDED WITH THE
 EXEMPTION UNDER FL. STATUTE 471.003(2)(H) TO PREPARE
 GAS PIPING DRAWINGS. THIS IS A SEPARATE PERMIT
 SPECIFICALLY FOR THE GAS PIPING INSTALLATION. ACCORDING
 TO THE STATUTE, THE PLUMBING CONTRACTOR OF RECORD-
 PHILIP ECHOLS OF RENCO PLUMBING- IS PERMITTED TO
 PREPARE THE DRAWINGS HOWEVER HE MUST PROVIDE HIS TITLE
 BLOCK AND SIGNATURE ON THE PLANS- SECTION 107.2.1 WPB
 AND FL. STATUTE 471.003(2)(H). AS AN ALTERNATE PLEASE
 PROVIDE A FL. LICENSED ENGINEER TO DESIGN THE SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-01-27 Cont ID  
Sent By ccole Date 2021-01-27 Time 10:37 Rev Time 0.00
Received By ccole Date 2021-01-27 Time 09:20 Sent To  
Notes
2021-01-27 10:38:031ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21010798
 1/27/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A01: PLEASE INDICATE THE GAS METER AS EITHER
 NEW OR EXISTING AND PROVIDE THE GAS DELIVERY PRESSURE.
 IS THIS A 2 PSI SYSTEM OR LOW-PRESSURE SYSTEM? SECTION
 G2412.1 FBC RES.
  
 2) A01: PROVIDE THE PIPE SIZING METHOD OR SIZING TABLES
 USED IN ACCORDANCE WITH SECTION- G2413.3 FBC RES.
  
 3) A01: PROVIDE THE TOTAL DEVELOPED LENGTH OF THE
 SYSTEM FROM THE METER TO THE RANGE. THE ISO APPEARS TO
 INDICATE 44 FT.- G2413.4.1.
  
 4) A01: CSST PIPE SIZING IS BY EHD NOT INCHES- PLEASE
 PROVIDE THE EHD OF THE 3/4 IN. PIPING- G2415.2
  
 5) A01: PROVIDE AN ENLARGED GAS MANIFOLD DETAIL AND
 SUBMIT A PRODUCT SPECIFICATION IF THIS IS A
 MANUFACTURED AND LISTED PIPE CONNECTOR- SECTION
 G2415.17.2.
  
 6) A01: SHOW THE TYPE OF PIPING FOR THE FUTURE
 GENERATOR AND SHOW A GAS TIGHT CAP WILL BE INSTALLED-
 G2414.1 & G2415.15. PLEASE NOTE THAT THE FUTURE
 GENERATOR SHALL BE INSTALLED A MINIMUM OF 10 FT. FROM
 MECHANICAL AND NATURAL AIR INTAKE OPENINGS INTO THE
 BUILDING INCLUDING DOORS AND OPERABLE WINDOWS- SECTION
 R303.5.1 FBC RES.
  
 7) SUBMIT PRODUCT DATA SHEETS FOR THE WATER HEATER AND
 THE RANGE WITH MARKINGS TO SHOW THE BTUH CAPACITIES AND
 GAS INPUT PRESSURES- G2408.1 & G2448.1. PLEASE NOTE
 THAT REGULATORS MAY BE REQUIRED BASED ON THE PRESSURE
 OF THE SYSTEM AND INPUT PRESSURES OF THE APPLIANCES.
  
 8) WHERE REGULATORS ARE REQUIRED, THEY SHALL BE SHOWN
 ON THE RISER WITH INPUT AND OUTPUT PRESSURES NOTED, AND
 MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED-
 G2421.
  
 9) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR THE
 NEW RANGE AND PROVIDE A CALCULATION IF INDOOR AIR IS TO
 BE USED- G2407.1, G2407.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-02-24 Time   Rev Time 0.00
Received By lmarchan Date 2021-02-19 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-17 Cont ID  
Sent By ccole Date 2021-02-17 Time 15:50 Rev Time 0.00
Received By ccole Date 2021-02-10 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-01-27 Time   Rev Time 0.00
Received By lmarchan Date 2021-01-22 Time 12:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 08:23 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 07:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-02-17 Cont ID  
Sent By ccole Date 2021-02-17 Time 15:50 Rev Time 0.00
Received By ccole Date 2021-02-17 Time 13:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-01-27 Cont ID  
Sent By ccole Date 2021-01-27 Time 10:39 Rev Time 0.00
Received By ccole Date 2021-01-27 Time 09:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 08:21 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 07:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-02-17 Cont ID  
Sent By ccole Date 2021-02-17 Time 15:33 Rev Time 0.00
Received By ccole Date 2021-02-17 Time 13:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-27 Cont ID  
Sent By ccole Date 2021-01-27 Time 10:39 Rev Time 0.00
Received By ccole Date 2021-01-27 Time 09:20 Sent To  
Notes
2021-01-27 10:40:281ST REVIEW FBC-2020 SIGNATURE
 PERMIT- 21010798
 1/27/2021
  
 CODES IN EFFECT:
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  