Plan Review Details - Permit 21010564
Plan Review Stops For Permit 21010564
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-20 Cont ID  
Sent By jwitmer Date 2021-01-20 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2021-01-20 Time 10:45 Sent To  
Notes
2021-01-20 11:15:37WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21010564
 ADD: 300 S. AUSTRALIAN AVE. # 204
 CONT: TREND WEST
 TEL: 561-358-8817
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 20TH/ 2021
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION IS REQUIRED. NO FLOOR PLAN
 WAS SUBMITTED. MINIMUM SCALE IS 1/8TH. 107.2.1.3.
 QUALITY OF PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 1/8TH INCH SCALE ON SUBSTANTIAL PAPER. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT POLICY OTHER
 STANDARDS FOR THE PLANS AND SPECIFICATIONS IN ORDER TO
 PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 2) 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 FLOOR PLAN WITH SQUARE FOOTAGE OF WORK TO BE COMPLETED
 FOR FLOOR.
 FLOOR DETAIL OF SHOWER PAN, IS THIS AN EXISTING SHOWER
 OR TUB CONVERSION
 TYPE OF MATERIALS USED IN MAKING THE SHOWER CURB AND
 PAN
 IS THE EXISTING DRAIN LOCATION TO BE MOVED
 WALL BACKING MATERIAL OF SHOWER
 HEIGHT OF THE TILE IN THE SHOWER
  
 3) CERTIFICATION BY CONTRACTOR. FOR EACH TRADE THE
 CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE
 LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND
 LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY
 ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A
 BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT
 ALL THESE TRADES UNDER ONE SHEET.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 4) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 5) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 6) FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD
 THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR
 ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 6A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 6B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 6C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-01-27 Time   Rev Time 0.00
Received By lmarchan Date 2021-01-15 Time 15:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-27 Cont ID  
Sent By ccole Date 2021-01-27 Time 09:05 Rev Time 0.00
Received By ccole Date 2021-01-27 Time 07:16 Sent To  
Notes
2021-01-27 09:05:331ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21010564
 1/27/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DESCRIPTIONS OF WORK SHOWN ON THE APPLICATIONS
 STATING REPLACING THE SHOWER PAN DOES NOT MATCH THE
 PLAN WHICH SHOWS A TUB CONVERSION TO A SHOWER. PLEASE
 NOTE THAT THE CONDOMINIUM BUILDING AND BATHROOMS
 CONSTRUCTED UNDER PERMIT- 04110961 APPEAR TO BE HAVE
 BEEN CONSTRUCTED IN ACCORDANCE WITH THE FAIR HOUSING
 ACT AND THE GUIDELINES OF THE FAIR HOUSING ACT DESIGN
 MANUAL. PLEASE REFER TO PAGES 7.34- 7.59 OF THE MANUAL
 FOR REQUIRED TUB CONVERSION COMPLIANCE INFORMATION.
  
 BASED ON THE FLOOR PLAN IT APPEARS THAT THE MASTER BATH
 WAS CONSTRUCTED UNDER SPECIFICATION B BECAUSE OF THE
 FULL 30 X 48 IN. UNOBSTRUCTED CLEAR FLOOR SPACE
 PROVIDED FOR THE FIXTURE, AS OPPOSED TO THE OBSTRUCTED
 CLEAR FLOOR SPACE PROVIDED AT THE SHOWER IN THE COMMON
 BATHROOM- SEE EXAMPLES A & B ON PAGES 7.36 & 7.37.
 UNDER SPECIFICATION B WHICH REQUIRED ONLY ONE BATHROOM
 AND ONE BATHING FIXTURE TO MEET COMPLIANCE IN THE UNIT,
 THE NEW SHOWER SHALL BE IN COMPLIANCE UNDER
 SPECIFICATION B. PLEASE REFER TO PAGES 7.56- 7.59 AND
 REVISE THE DRAWINGS TO SHOW:
  
 A) LENGTH AND WIDTH DIMENSIONS OF THE NEW SHOWER.
  
 B) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 NEW SHOWER.
  
 C) REQUIRED GRAB BAR REINFORCEMENT AND REINFORCEMENT
 LOCATIONS AS INDICATED ON PAGE 7.56 AND THE FIGURES
 SHOWN ON PAGES 6.12 AND 6.13.
  
 AS AN ALTERNATIVE TO MEETING THE GUIDELINES FOR THE
 BATH ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR
 THE PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED
 AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE
 PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO
 REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO
 COMPLIANCE AT TIME OF SALE IF REQUESTED BY THE BUYER.
 IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL TO
 [email protected] AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT.
  
 2) PROVIDE A SHOWER PAN DETAIL ION COMPLIANCE WITH
 SECTION 421.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-27 Cont ID  
Sent By ccole Date 2021-01-27 Time 09:08 Rev Time 0.00
Received By ccole Date 2021-01-27 Time 09:08 Sent To  
Notes
2021-01-27 09:14:351ST SIGNATURE REVIEW
 1/27/2021
  
 1) THE SUBMITTED FLOOR PLAN APPEARS TO HAVE BEEN
 SUIBMITTED BY THE CONTRACTOR. PLEASE NOTE THAT ALL
 PLANS SUBMITTED BY CONTRACTORS SHALL BEAR THE PRINTED
 NAME AND SIGNATURE OF THE CONTRACTOR OR QUALIFIER WHO
 IS MAKING APPLICATION AND PERFORMING THE WORK- SECTION
 107.2.1 WPB & FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  