Plan Review Details - Permit 21010453
Plan Review Stops For Permit 21010453
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-01-20 Cont ID  
Sent By cpuell Date 2021-01-20 Time 09:21 Rev Time 0.00
Received By cpuell Date 2021-01-20 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-03 Cont ID  
Sent By rmcphers Date 2021-02-03 Time 08:22 Rev Time 0.00
Received By rmcphers Date 2021-02-03 Time 08:18 Sent To  
Notes
2021-02-03 08:22:23SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE
 THE DRAWINGS TO REFLECT THE DESIGN PER THE CODE IN
 EFFECT (FBC 2020 AND ASCE 7-16)
 2) SIGN (ENGINEERING) MOUNTING DRAWINGS SHOULD SHOW THE
 ADDRESS OF THE SIGN.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-29 Cont ID  
Sent By jleahy Date 2021-01-29 Time 07:13 Rev Time 0.00
Received By jleahy Date 2021-01-29 Time 07:11 Sent To  
Notes
2021-01-29 07:21:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) DISCONNECT REQUIRED BY 600.6 NOT SHOWN ON PLANS
  
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 2) CONTROL OF SIGN NOT SHOWN ON PLANS.
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-EC 405.2.4
  
 3) VALUE OF SIGN IS LOW (2300) PLEASE SUBMIT A SIGNED
 CONTRACT FOR SIGN.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-16 Cont ID  
Sent By cthroop Date 2021-04-16 Time 10:51 Rev Time 0.00
Received By cthroop Date 2021-01-15 Time 16:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-03 Cont ID  
Sent By rmcphers Date 2021-02-03 Time 08:22 Rev Time 0.00
Received By rmcphers Date 2021-02-03 Time 08:22 Sent To  
Notes
2021-02-03 08:23:36SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 1 Status P Date 2021-04-15 Cont ID  
Sent By awooten Date 2021-04-15 Time   Rev Time  
Received By awooten Date 2021-04-15 Time   Sent To  
Notes
***NONE***