Plan Review Stops For Permit 21010326 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2022-03-16 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-03-16 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-03-16 |
Time |
11:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2022-02-01 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-02-01 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-02-01 |
Time |
13:02 |
Sent To |
|
|
Notes |
2022-02-01 13:06:56 | OFFICE/WAREHOUSE RENO | | SFR ADDITION- | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | SUBSTANTIAL IMPROVEMENT- | | | | ADDITION IS CLOSE TO THE FEMA FLOOD ZONE AE 14 - UNABLE | | TO DETERMINE IF THE ADDITION WILL FALL INTO THE AE14 | | FLOOD ZONE. | | | | PLEASE SHOW THE BUILDING ADDITION ON A SURVEY ALONG | | WITH THE FLOOD ZONE DELINATION LINES TO SHOW IF THE | | BUILDING ADDITION FALLS IN THE AE14 OR X ZONES. | | | | IF THE ADDITION FALLS IN THE FLOOD ZONE AE 14 THE | | ENTIRE HOUSE WILL NEED TO BE RAISED TO MEET THE DESIGN | | FLOOD ELEVATION OF 16.00 NAVD | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2022-01-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-01-10 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-01-10 |
Time |
09:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2021-10-18 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-10-18 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-10-18 |
Time |
11:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-06-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-06-23 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-06-23 |
Time |
09:08 |
Sent To |
|
|
Notes |
2021-06-23 09:09:11 | SFR ADDITION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) THE DESIGN CRITERIA FOR THE TRUSS DRAWINGS SHOWN ON | | THE TRUSS ENGINEERING ( FROM SPEC TRUSS) NEEDS TO BE | | REVISED TO REFLECT THE CODE IN EFFECT (2020 FBC AND | | ASCE 7-16) - WIND SPEED NEEDS TO MATCH THE DRAWINGS S-2 | | SHOWS 180 MPH WIND SPEED DESIGN. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-03-01 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-02-26 |
Time |
14:33 |
Sent To |
|
|
Notes |
2021-03-01 09:05:44 | SFR ADDITION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE | | THE DRAWINGS TO SHOW THE DESIGN CRITERIA BASED ON THE | | CODE IN EFFECT (2020 FBC AND ASCE 7-16) | | 2) PLEASE SHOW THE SMOKE ALARM LOCATIONS THROUGH OUT | | THE EXISTING HOUSE TO COMPLY WITH FBC R314.2.2 | | ALTERATIONS, REPAIRS AND ADDITIONS. | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | 3) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG | | WINDOWS (02-1120.03) HAS EXPIRED - PLEASE PROVIDE AN | | UPDATED VERSION. | | 4) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE | | ROOFING SYSTEM. | | 5) ALL PRODUCT APPROVALS AND SHOP DRAWINGS NEED TO BE | | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER | | OF RECORD. | | 6) THE DESIGN CRITERIA FOR THE TRUSS DRAWINGS SHOWN ON | | THE TRUSS ENGINEERING NEEDS TO BE REVISED TO REFLECT | | THE CODE IN EFFECT (2021 FBC AND ASCE 7-16) | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-06-16 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-06-16 |
Time |
20:20 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-06-16 |
Time |
19:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-02-15 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-02-15 |
Time |
18:15 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-02-15 |
Time |
17:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2022-03-22 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2022-03-22 |
Time |
08:26 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-03-11 |
Time |
14:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2022-02-01 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-02-01 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-01-21 |
Time |
07:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2022-01-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-01-10 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-01-05 |
Time |
11:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2021-10-20 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-10-09 |
Time |
17:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-07-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-07-22 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-06-09 |
Time |
11:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-03-01 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-03-01 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-02-02 |
Time |
12:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2022-05-02 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-05-02 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-04-25 |
Time |
15:08 |
Sent To |
|
|
Notes |
2022-04-29 16:01:42 | RECEIPT MU-2022-018733 - $546.52 PAID | 2022-04-25 15:08:26 | 4/25/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-03-01 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-03-01 |
Time |
09:07 |
Sent To |
|
|
Notes |
2021-03-01 09:08:09 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2021-10-14 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-10-14 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-10-14 |
Time |
10:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2021-06-16 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-06-16 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-06-16 |
Time |
16:07 |
Sent To |
|
|
Notes |
2021-06-16 16:09:02 | PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. FBC EC R403.7 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2021-02-09 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-02-09 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-02-09 |
Time |
13:56 |
Sent To |
|
|
Notes |
2021-02-09 14:13:18 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21010326 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2020 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2020 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS FOR THE NEW SYSTEM. FBC EC R403.7.1 | | | | 2) PLEASE PROVIDE A CODE COMPLIANT MECHANICAL DRAWING | | FOR THIS ADDITION. FBC 107.2.1 | | | | 3) PLEASE SHOW THE ANCHORAGE DETAILS FOR THE CONDENSING | | UNIT. FBC RES M1307.2 | | | | 4) PLEASE SHOW THE CONDENSATE DRAIN AND TERMINATION | | LOCATION. FBC RES M1411.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
4 |
Status |
N |
Date |
2022-03-16 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-03-16 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-03-16 |
Time |
11:08 |
Sent To |
|
|
Notes |
2022-03-16 11:10:26 | SURVEY PROVIDED - MILLER LAND SURVEYING - SHOWS THAT | | THE PROPOSED ADDITION AND EXISTING HOUSE IS NOT IN THE | | FLOOD ZONE. |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
3 |
Status |
F |
Date |
2022-02-01 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-02-01 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-02-01 |
Time |
13:07 |
Sent To |
|
|
Notes |
2022-02-01 13:07:22 | SUBSTANTIAL IMPROVEMENT- | | | | ADDITION IS CLOSE TO THE FEMA FLOOD ZONE AE 14 - UNABLE | | TO DETERMINE IF THE ADDITION WILL FALL INTO THE AE14 | | FLOOD ZONE. | | | | PLEASE SHOW THE BUILDING ADDITION ON A SURVEY ALONG | | WITH THE FLOOD ZONE DELINATION LINES TO SHOW IF THE | | BUILDING ADDITION FALLS IN THE AE14 OR X ZONES. | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
2 |
Status |
F |
Date |
2022-01-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2022-01-10 |
Time |
09:29 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2022-01-10 |
Time |
09:29 |
Sent To |
|
|
Notes |
2022-01-10 09:30:13 | SUBSTANTIAL IMPROVEMENT- | | | | ADDITION IS CLOSE TO THE FEMA FLOOD ZONE AE 14 - UNABLE | | TO DETERMINE IF THE ADDITION WILL FALL INTO THE AE14 | | FLOOD ZONE. | | | | PLEASE SHOW THE BUILDING ADDITION ON A SURVEY ALONG | | WITH THE FLOOD ZONE DELINATION LINES TO SHOW IF THE | | BUILDING ADDITION FALLS IN THE AE14 OR X ZONES. | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
F |
Date |
2021-10-18 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-10-18 |
Time |
12:17 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-10-18 |
Time |
12:17 |
Sent To |
|
|
Notes |
2021-10-18 12:17:46 | ADDITION IS CLOSE TO THE FEMA FLOOD ZONE AE 14 - UNABLE | | TO DETERMINE IF THE ADDITION WILL FALL INTO THE AE14 | | FLOOD ZONE. | | | | PLEASE SHOW THE BUILDING ADDITION ON A SURVEY ALONG | | WITH THE FLOOD ZONE DELINATION LINES TO SHOW IF THE | | BUILDING ADDITION FALLS IN THE AE14 OR X ZONES. | | OR | | IF THE BUILDINGS LOWEST FLOOR ELEVATION IS 2 FOOT ABOVE | | AE 14.00 - PROVIDE A SURVEY SHOWING THE "LOWEST FLOOR" | | ELEVATION OF THE EXISTING LIVING SPACE. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2021-10-20 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-10-20 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-10-20 |
Time |
14:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2021-06-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-06-17 |
Time |
13:14 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-06-17 |
Time |
11:57 |
Sent To |
|
|
Notes |
2021-06-17 13:15:05 | 2ND REVIEW FBC-2020 RES.PLUMBING | | PERMIT- 21010326 | | 6/17/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE CORRECT THE ENERGY EFFICIENCY FORM R405-2017 | | WHICH IS INDICATING A TANKLESS WATER HEATER. THE | | REVISED PLUMBING PLANS SHOW AN EXISTING 40-GALLON | | STORAGE TANK IN THE GARAGE- TABLE C404.2 FBC EC. PLEASE | | NOTE THE 2017 FORM APPEARS TO BE OUTDATED. THE FBC- | | 2020 BUILDING CODES WENT INTO EFFECT ON 12/31/20- | | SECTION- R101.5 FBC EC. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-02-12 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-02-12 |
Time |
18:55 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-02-12 |
Time |
16:51 |
Sent To |
|
|
Notes |
2021-02-12 18:55:22 | 1ST REVIEW FBC-2020 RES. | | PERMIT- 21010326 | | 2/12/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHOW THE LOCATION OF THE NEW TANKLESS WATER HEATER | | AND PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN | | INDICATING THE MAKE AND MODEL AND EFFICIENCY RATING- | | TABLE C404.2 FBC EC. SUBMIT MANUFACTURER?S | | SPECIFICATIONS- SECTION P2801.1 & P2801.3 FBC RES. | | | | 2) PROVIDE A PLUMBING LAYOUT PLAN SHOWING THE ADDITION | | SANITARY AND WATER SUPPLY CONNECTIONS TO THE EXISTING | | SYSTEMS- SECTION 107.2.1 WPB. | | | | 3) PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 & | | P2709.2 FBC RES. | | | | 4) PROVIDE SPECIFICATIONS FOR THE SHOWER VALVE AND | | BATHTUB FAUCET- SECTIONS P2708.4 & P2713.3 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2021-06-23 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-06-23 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-06-23 |
Time |
09:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-03-01 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-03-01 |
Time |
09:08 |
Sent To |
|
|
Notes |
2021-03-01 09:09:20 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-06-16 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-06-16 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-06-16 |
Time |
16:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2021-02-09 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-02-09 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-02-09 |
Time |
14:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2022-03-21 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2022-03-21 |
Time |
12:14 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2022-03-21 |
Time |
12:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2021-07-21 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2021-07-21 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2021-07-21 |
Time |
14:40 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2021-02-26 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2021-02-26 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2021-02-26 |
Time |
09:01 |
Sent To |
|
|
Notes |
|
|