Plan Review Stops For Permit 21010248 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2021-01-15 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-01-15 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-01-15 |
Time |
10:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2021-05-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-05-06 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-05-06 |
Time |
12:45 |
Sent To |
|
|
Notes |
2021-05-06 12:48:45 | AS NOTED ON THE COVER PAGE - WINDOW AND DOOR PRODUCT | | APPROVALS ARE DEFERRED - PRODUCT APPROVALS ARE IN | | PROJECTDOX AT THIS TIME BUT ARE LOCKED DOCUMENTS - WHEN | | SUBMITTING THE DEFERRED PRODUCT APPROVALS THEY WILL | | NEED TO BE MARKED APPROVED BY THE BUILDING DESIGNER OF | | RECORD. | | PERMIT FEE CALCULATED = AC SPACE 4464SQ.FT. X ICC RATE | | OF 144.00 PER SQ. FT. = $642,816.00 | | GARAGE = 464SQ.FT. X ICC RATE 63.00 PER SQ. FT. = | | $29,232.00 | | TOTAL JOB COST = 642,816.00 + 29,232.00 = $672,048.00 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2021-04-15 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-15 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-15 |
Time |
10:27 |
Sent To |
|
|
Notes |
2021-04-15 10:49:59 | NEW SFR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) 2ND FLOOR ELECTRICAL PLAN SHOWS ONLY CARBON MONOXIDE | | DETECTORS OUTSIDE THE BEDROOMS - A COMBINATION SMOKE | | AND CARBON MONOXIDE DETECTOR CAN BE SHOWN - R314.7.4 | | 2) SHEET 1 WAS NOT REVISED AS NOTED ON THE COMMENT | | DRAWING. PLEASE SHOW A BATH/TOILET ROOM DOOR WIDTH OF A | | CLEAR OPENING OF 29 INCHES ON THE FIRST FLOOR TO COMPLY | | WITH FBC R320.1.1 - FBC ACCESSIBILITY 404.2.3 CLEAR | | WIDTH. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS | | SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE | | STOP, WITH THE DOOR OPEN 90 DEGREES. | | 3) SHEET 1 WAS NOT REVISED AS NOTED ON THE COMMENT | | DRAWING. PLEASE SHOW THE GARAGE CEILING FIRE PROTECTION | | FROM HABITABLE ROOMS ABOVE THE GARAGE PER FBC R302.6 | | (5/8 TYPE X DRYWALL). | | 4) SHEET 1 WAS NOT REVISED AS NOTED ON THE COMMENT | | DRAWING. PLEASE SHOW THE REQUIRED DRYWALL UNDER THE | | ENCLOSED STAIR TO COMPLY WITH FBC R302.7 UNDER-STAIR | | PROTECTION. | | ENCLOSED SPACE UNDER STAIRS THAT IS ACCESSED BY A DOOR | | OR ACCESS PANEL SHALL HAVE WALLS, UNDER-STAIR SURFACE | | AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH | | 1/2-INCH (12.7 MM) GYPSUM BOARD. | | 5) WINDOW AND DOOR PRODUCT APPROVALS WILL BE DEFERRED | | AS PER NOTE ON THE DRAWINGS COVER PAGE. | | 6) PRODUCT APPROVAL PROVIDED FOR THE METAL ROOFING | | SYSTEM (-82.5) DOES NOT MEET THE REQUIRED WIND DESIGN | | PRESSURES FOR ROOF WIND ZONES 2R PER DRAWING MARKED | | COVER PAGE (-102.7) | | 7) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE | | ENGINEER. | | 8) NEED THE ORIGINAL SIGNED AND SEALED SOIL REPORT. | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. IF YOUR | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL | | 9) DRAWINGS SHOW THE ROOFING AND WINDOW AND DOOR | | PRODUCT APPROVALS ARE TO BE DEFERRED - YET NEW PRODUCT | | APPROVALS HAVE BEEN SUBMITTED FOR THE ROOFING. IS THE | | ROOFING TO BE DEFERRED? ROOFING SYSTEM AND WINDOW AND | | DOOR PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY | | LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION | | DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE | | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE | | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT | | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE | | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A | | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL | | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION | | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | OFFICIAL. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-03-29 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-03-29 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-03-29 |
Time |
11:05 |
Sent To |
|
|
Notes |
2021-03-29 11:06:15 | NEW SFR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | NO CHANGES SINCE THE LAST REVIEW | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW CARBON MONOXIDE DETECTOR LOCATION TO | | COMPLY WITH FBC R315.1 CARBON MONOXIDE PROTECTION. | | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING | | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS | | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR | | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER | | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE | | AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL | | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH | | ROOM USED FOR SLEEPING PURPOSES. | | 2) PLEASE SHOW SMOKE ALARM LOCATIONS TO COMPLY WITH FBC | | R314.3 (SHOW SMOKE ALARM OUTSIDE OF MASTER RETREAT IN | | THE MASTER RETREAT VESTIBULE - SMOKE ALARM SHOULD NOT | | BE IN THE MASTER RETREAT BATH ROOM. | | 3) PLEASE SHOW A BATH/TOILET ROOM DOOR WIDTH OF A CLEAR | | OPENING OF 29 INCHES ON THE FIRST FLOOR TO COMPLY WITH | | FBC R320.1.1 - FBC ACCESSIBILITY 404.2.3 CLEAR WIDTH. | | CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE | | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, | | WITH THE DOOR OPEN 90 DEGREES. | | 4) PLEASE SHOW THE GARAGE CEILING FIRE PROTECTION FROM | | HABITABLE ROOMS ABOVE THE GARAGE PER FBC R302.6 (5/8 | | TYPE X DRYWALL). | | 5) PLEASE SHOW THE REQUIRED DRYWALL UNDER THE ENCLOSED | | STAIR TO COMPLY WITH FBC R302.7 UNDER-STAIR PROTECTION. | | ENCLOSED SPACE UNDER STAIRS THAT IS ACCESSED BY A DOOR | | OR ACCESS PANEL SHALL HAVE WALLS, UNDER-STAIR SURFACE | | AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH | | 1/2-INCH (12.7 MM) GYPSUM BOARD. | | 6) PLEASE SHOW THE CEILING/FLOOR ASSEMBLY DRAFT | | STOPPING TO COMPLY WITH FBC R302.12 DRAFTSTOPPING. | | IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE | | BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A | | FLOOR-CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED | | SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED | | 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE | | THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. | | WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE | | ABOVE AND A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL | | BE PROVIDED IN FLOOR-CEILING ASSEMBLIES UNDER THE | | FOLLOWING CIRCUMSTANCES: | | 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. | | 2.FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB | | OR PERFORATED MEMBERS. | | 7) PLEASE SHOW THE FLAT ROOF FRAMING DETAILS - JOIST | | SIZE, SPACING AND ATTACHMENTS, STRAPPING ETC. | | 8) ALL PRODUCT APPROVALS PROVIDED NEED TO BE REVIEWED | | AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD | | OR BE LISTED BY PRODUCT APPROVAL NUMBER ON THE | | DRAWINGS. | | 9) PRODUCT APPROVAL PROVIDED FOR THE METAL ROOFING | | SYSTEM (-89.4) DOES NOT MEET THE REQUIRED WIND DESIGN | | PRESSURES FOR ROOF WIND ZONES 3 (-99.22) - ROOF | | CLADDING DESIGN PRESSURES ARE NOT SHOWN ON THE DRAWINGS | | - WIND PRESSURES ARE BASED ON FBC TABLER301.2(2) | | 10) PLEASE PROVIDE A MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE | | CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT | | APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED | | ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR | | ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A | | HIGHER WIND PRESSURE - SEE NOTES ON THE PRODUCT | | APPROVAL. | | 11) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL | | FRONT PAGES FOR (DOOR - FL17347 AND METAL ROOF - | | FL11560.4). THE INSTALLATION INSTRUCTIONS HAVE BEEN | | PROVIDED. | | 12) ROOFING SYSTEM AND WINDOW AND DOOR PRODUCT | | APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS | | TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR | | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING | | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED | | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE | | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. | | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED | | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN | | APPROVED BY THE BUILDING OFFICIAL. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-02-03 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-02-03 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-02-03 |
Time |
08:53 |
Sent To |
|
|
Notes |
2021-02-03 13:07:58 | NEW SFR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW CARBON MONOXIDE DETECTOR LOCATION TO | | COMPLY WITH FBC R315.1 CARBON MONOXIDE PROTECTION. | | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING | | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS | | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR | | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER | | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE | | AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL | | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH | | ROOM USED FOR SLEEPING PURPOSES. | | 2) PLEASE SHOW SMOKE ALARM LOCATIONS TO COMPLY WITH FBC | | R314.3 (SHOW SMOKE ALARM OUTSIDE OF MASTER RETREAT IN | | THE MASTER RETREAT VESTIBULE - SMOKE ALARM SHOULD NOT | | BE IN THE MASTER RETREAT BATH ROOM. | | 3) PLEASE SHOW A BATH/TOILET ROOM DOOR WIDTH OF A CLEAR | | OPENING OF 29 INCHES ON THE FIRST FLOOR TO COMPLY WITH | | FBC R320.1.1 - FBC ACCESSIBILITY 404.2.3 CLEAR WIDTH. | | CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE | | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, | | WITH THE DOOR OPEN 90 DEGREES. | | 4) PLEASE SHOW THE GARAGE CEILING FIRE PROTECTION FROM | | HABITABLE ROOMS ABOVE THE GARAGE PER FBC R302.6 (5/8 | | TYPE X DRYWALL). | | 5) PLEASE SHOW THE REQUIRED DRYWALL UNDER THE ENCLOSED | | STAIR TO COMPLY WITH FBC R302.7 UNDER-STAIR PROTECTION. | | ENCLOSED SPACE UNDER STAIRS THAT IS ACCESSED BY A DOOR | | OR ACCESS PANEL SHALL HAVE WALLS, UNDER-STAIR SURFACE | | AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH | | 1/2-INCH (12.7 MM) GYPSUM BOARD. | | 6) PLEASE SHOW THE CEILING/FLOOR ASSEMBLY DRAFT | | STOPPING TO COMPLY WITH FBC R302.12 DRAFTSTOPPING. | | IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE | | BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A | | FLOOR-CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED | | SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED | | 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE | | THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. | | WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE | | ABOVE AND A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL | | BE PROVIDED IN FLOOR-CEILING ASSEMBLIES UNDER THE | | FOLLOWING CIRCUMSTANCES: | | 1.CEILING IS SUSPENDED UNDER THE FLOOR FRAMING. | | 2.FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB | | OR PERFORATED MEMBERS. | | 7) PLEASE SHOW THE FLAT ROOF FRAMING DETAILS - JOIST | | SIZE, SPACING AND ATTACHMENTS, STRAPPING ETC. | | 8) ALL PRODUCT APPROVALS PROVIDED NEED TO BE REVIEWED | | AND MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD | | OR BE LISTED BY PRODUCT APPROVAL NUMBER ON THE | | DRAWINGS. | | 9) PRODUCT APPROVAL PROVIDED FOR THE METAL ROOFING | | SYSTEM (-89.4) DOES NOT MEET THE REQUIRED WIND DESIGN | | PRESSURES FOR ROOF WIND ZONES 3 (-99.22) - ROOF | | CLADDING DESIGN PRESSURES ARE NOT SHOWN ON THE DRAWINGS | | - WIND PRESSURES ARE BASED ON FBC TABLER301.2(2) | | 10) PLEASE PROVIDE A MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE | | CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT | | APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED | | ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR | | ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A | | HIGHER WIND PRESSURE - SEE NOTES ON THE PRODUCT | | APPROVAL. | | 11) PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL | | FRONT PAGES FOR (DOOR - FL17347 AND METAL ROOF - | | FL11560.4). THE INSTALLATION INSTRUCTIONS HAVE BEEN | | PROVIDED. | | 12) ROOFING SYSTEM AND WINDOW AND DOOR PRODUCT | | APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS | | TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR | | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING | | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED | | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE | | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. | | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED | | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN | | APPROVED BY THE BUILDING OFFICIAL. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2021-05-05 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-05-05 |
Time |
17:03 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-05-05 |
Time |
17:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2021-04-20 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-04-20 |
Time |
17:08 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-04-20 |
Time |
16:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2021-03-18 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-03-18 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-03-18 |
Time |
08:54 |
Sent To |
|
|
Notes |
2021-03-18 09:30:26 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | RISER DIAGRAM DOES NOT SHOW GENERATOR, GAS PLAN | | REVIEWER STATING THAT THE WATER HEATER IS A TANKLESS | | (GAS), DRYER IS GAS, AND THAT THERE IS A GENERATOR | | SHOWN ON HIS PLAN. PLEASE COORDINATE WITH OTHER TRADES. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-01-27 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-01-27 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-01-27 |
Time |
14:51 |
Sent To |
|
|
Notes |
2021-01-27 15:02:31 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NO RISER DIAGRAM SHOWN 215.5 | | | | NO LOAD CALCULATION SHOWN 220 | | | | NO PANEL SCHEDULE SHOWN | | PROVIDE PANEL SCHEDULE INDICATING NEW CIRCUITS, THE | | WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR | | GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. | | NEC 210.8, 210.12, 215.5, 408.4 | | | | ALL RECPTACLES INSTALLED OUTSIDE AT 120 VOLTS 15 AND 20 | | A TO BR GFCI PROTECTED PER 210.8(A) | | | | |
|
|
Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
Rev No |
3 |
Status |
P |
Date |
2021-12-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-12-28 |
Time |
11:41 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-12-28 |
Time |
11:41 |
Sent To |
|
|
Notes |
2021-12-28 11:42:08 | CENTRAL VAC SYSTEM JLEAHY |
|
|
Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
Rev No |
2 |
Status |
P |
Date |
2021-04-20 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-04-20 |
Time |
17:08 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-04-20 |
Time |
17:08 |
Sent To |
|
|
Notes |
2021-04-20 17:09:19 | VOICE DATA AND TV JLEAHY |
|
|
Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
Rev No |
1 |
Status |
P |
Date |
2021-03-18 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-03-18 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-03-18 |
Time |
09:09 |
Sent To |
|
|
Notes |
2021-03-18 09:09:54 | DATA VOICE TV JLEAHY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2021-05-06 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-05-06 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-29 |
Time |
16:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2021-04-21 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-21 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-09 |
Time |
12:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-04-02 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2021-04-02 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2021-04-01 |
Time |
15:00 |
Sent To |
|
|
Notes |
2021-04-02 11:08:21 | RESUBMITTAL DROPPEED OFF 04/01 FOR 21010248 BUT AS PER | | ME DOCUMENTS BELONG WITH ASSOCIATED PERMIT#21030167 AO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-03-29 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-03-29 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-03-10 |
Time |
18:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-03-02 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-03-02 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-01-14 |
Time |
18:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2021-05-24 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-05-24 |
Time |
09:18 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-05-06 |
Time |
16:19 |
Sent To |
|
|
Notes |
2021-05-21 07:41:04 | RECEIPT MU-2021-24642 - $2404.37 - PAID | 2021-05-06 16:19:38 | 5/6/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2021-02-03 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-02-03 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-02-03 |
Time |
13:08 |
Sent To |
|
|
Notes |
2021-02-03 13:09:46 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] . | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2021-05-07 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-05-07 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-05-07 |
Time |
14:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2021-05-05 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-05-05 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-05-05 |
Time |
16:39 |
Sent To |
|
|
Notes |
2021-05-05 16:40:40 | 4TH REVIEW FBC-2020 MECHANICAL | | PERMIT-21010248 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE UNDERSTAND THAT THE PERSON THAT PREPARED THE | | MECHANICAL EQUIPMENT SIZING CALCULATIONS MUST BE EITHER | | A FLORIDA LICENSED ENGINEER OR A FLORIDA LICENSED | | MECHANICAL CONTRACTOR WHO HOLDS THE PERMIT TO INSTALL | | THE MECHANICAL SYSTEM FOR THIS PROJECT. AN ENGINEER | | MUST SIGN AND SEALED THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS ALONG WITH THE MECHANICAL DESIGN DRAWINGS | | OR THE MECHANICAL CONTRACTOR HOLDING THE PERMIT FOR | | THIS SYSTEM CAN PRINT THEIR NAME AND SIGN THEIR NAME ON | | EACH MECHANICAL DRAWING AND THE EQUIPMENT SIZING | | CALCULATIONS. FS 471.003 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2021-04-16 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-04-16 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-04-16 |
Time |
10:40 |
Sent To |
|
|
Notes |
2021-04-16 10:41:52 | 3RD REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1) A MECHANICAL SUB-PERMIT IS REQUIRED. | | | | 2) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN | | MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE | | MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE | | SPECIFIC PROJECT WHICH HE OR SHE INSTALLS. | | PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A | | SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING | | CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING, | | OR | | THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL | | PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE | | COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER | | PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO | | THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1. | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2021-03-24 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-24 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-24 |
Time |
15:12 |
Sent To |
|
|
Notes |
2021-03-24 15:38:16 | PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | AND MECHANICAL SYSTEM DESIGN DRAWINGS FROM A STATE | | LICENSED ENGINEER OR A STATE LICENSED MECHNAICAL | | CONTRACTOR WITH THEIR PERMIT APPLICATION FOR THIS | | PROJECT. GS 471.003 (H) |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2021-01-15 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-01-15 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-01-15 |
Time |
16:13 |
Sent To |
|
|
Notes |
2021-01-15 16:14:02 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21010248 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2020 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2020 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE A MECHANICAL DRAWING FOR THIS | | PROJECT. FBC 107.2.1 | | | | 2) PLEASE PROVIDE ENERGY CALCULATIONS. FBC EC 101.5.1.1 | | | | 3) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. FBC EC R403.7.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-03-18 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2021-03-18 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2021-03-18 |
Time |
14:59 |
Sent To |
|
|
Notes |
2021-03-18 16:38:07 | 21010248 216 ASHWORTH ST | | | | IN ACCORDANCE WITH WPB FBC 107.3.4.3 AND 107.2.1, A | | PAPER PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE | | BUILDING DEPARTMENT PRIOR TO PERMIT ISSUANCE. | | | | PLUMBING COMMENTS: APPROVED W/PROVISOS | | | | 1.ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | INSPECTOR'S APPROVAL | | 2.SEE ARCHITECTURAL 1 FLOOR PLAN REGARDING THE WATER | | HEATER: | | PROVIDE DEFERRED SUBMITTAL; SEE BELOW | | 1. THE WATER HEATER SHOWN ON THIS PLAN SHEET IS NOT | | REPRESENTATIVE OF THE GAS TANKLESS WATER HEATER | | INDICATED IN THE GAS DRAWINGS AND SUBMITTALS (SEE | | PERMIT 21030167). THEREFOR PER WPB FBC 107.2.1 AND WPB | | FBC 107.3.4.1, PROVIDE AS A DEFERRED SUBMITTAL | | MANUFACTURER?S SPECIFICATION AND INSTALLATION GUIDE FOR | | THE GAS TANKLESS WATER HEATER. ADDITIONALLY, SHOW | | CORRECT LOCATION OF UNIT AND PROVIDE DETAIL FOR | | INSTALLATION, COMPLYING WITH MANUFACTURER?S | | RECOMMENDATIONS. DOCUMENTS SHALL BE SUBMITTED, APPROVED | | AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR | | OWN RISK. | | | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | MOBILE 561-243-0882 | | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND | | THURSDAYS | | | | 21010248 216 ASHWORTH ST |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-01-21 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-01-21 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-01-21 |
Time |
13:11 |
Sent To |
|
|
Notes |
2021-01-21 13:15:25 | 01/21/21 PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM | | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) | | RESIDENTIAL PLUMBING. | | | | 2. PLEASE SHOW SOURCE OF HOW WATER AND A DETAIL OF THE | | HEATER PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
4 |
Status |
P |
Date |
2021-05-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-05-06 |
Time |
12:49 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-05-06 |
Time |
12:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
F |
Date |
2021-04-15 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-15 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-15 |
Time |
10:58 |
Sent To |
|
|
Notes |
2021-04-15 10:59:20 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2021-03-29 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-03-29 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-03-29 |
Time |
11:06 |
Sent To |
|
|
Notes |
2021-03-29 11:06:42 | SEE BUILDING PLAN REVIEW - A BUILDING PERMIT | | APPLICATION MARKED "ROOFING" IS REQUIRED TO BE FILLED | | OUT |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-02-03 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-02-03 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-02-03 |
Time |
13:09 |
Sent To |
|
|
Notes |
2021-02-03 13:10:31 | SEE BUILDING PLAN REVIEW - A BUILDING PERMIT | | APPLICATION MARKED "ROOFING" IS REQUIRED TO BE FILLED | | OUT |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
5 |
Status |
P |
Date |
2021-05-07 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-05-07 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-05-07 |
Time |
14:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2021-05-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-05-06 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-05-06 |
Time |
12:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2021-04-15 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-15 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-04-15 |
Time |
10:58 |
Sent To |
|
|
Notes |
2021-04-15 10:58:41 | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-03-29 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-03-29 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-03-29 |
Time |
11:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2021-01-15 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-01-15 |
Time |
16:20 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-01-15 |
Time |
16:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2021-03-01 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2021-03-01 |
Time |
|
Rev Time |
|
Received By |
rthermid |
Date |
2021-03-01 |
Time |
|
Sent To |
I |
|
Notes |
|
|