Plan Review Details - Permit 21010247
Plan Review Stops For Permit 21010247
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-03-22 Cont ID  
Sent By cpuell Date 2021-03-22 Time 15:25 Rev Time 0.00
Received By cpuell Date 2021-03-22 Time 15:25 Sent To  
Notes
2021-03-22 15:24:58PARCEL SPLIT - LOTS 286-288 (PCN 74434410220002860) BE
 237 DESOTA RD AND LOTS 289-291 (PCN 74434410220002890)
 BE 233 DESOTA RD. THE WORK FOR THIS PERMIT IS ON
 74434410220002890

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By cpuell Date 2021-03-09 Time 12:48 Rev Time 0.00
Received By cpuell Date 2021-03-09 Time 12:48 Sent To  
Notes
2021-03-09 12:48:58ADDRESSING COMMENTS NOT ADDRESSED: IT APPEARS THAT PCN
 74434410220002860 LOT RANGE IS 286-291 HOWEVER FOR THIS
 PERMIT IT SEEMS THAT THE LOT IS BEING SUBDIVIDED. FOR
 THIS PERMIT LOTS 289-291 ARE IDENTIFIED, WE WILL NEED
 THE NEW PCN THAT THE COUNTY WILL PROVIDE YOU WITH, YOU
 WILL ALSO NEED A NEW ADDRESS. PLEASE CONTACT
 [email protected] TO DISCUSS ADDRESSING OPTIONS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By cpuell Date 2021-02-18 Time 13:22 Rev Time 0.00
Received By cpuell Date 2021-02-18 Time 13:22 Sent To  
Notes
2021-02-18 13:26:42IT APPEARS THAT PCN 74434410220002860 LOT RANGE IS
 286-291 HOWEVER FOR THIS PERMIT IT SEEMS THAT THE LOT
 IS BEING SUBDIVIDED. FOR THIS PERMIT LOTS 289-291 ARE
 IDENTIFIED, WE WILL NEED THE NEW PCN THAT THE COUNTY
 WILL PROVIDE YOU WITH, YOU WILL ALSO NEED A NEW
 ADDRESS. PLEASE CONTACT [email protected] TO DISCUSS
 ADDRESSING OPTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-05-12 Cont ID  
Sent By cthroop Date 2021-05-12 Time 08:39 Rev Time 0.00
Received By cthroop Date 2021-05-12 Time 08:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-05-06 Cont ID  
Sent By cthroop Date 2021-05-06 Time 08:43 Rev Time 0.00
Received By cthroop Date 2021-05-05 Time 13:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-29 Cont ID  
Sent By cthroop Date 2021-04-29 Time 12:57 Rev Time 0.00
Received By cthroop Date 2021-04-29 Time 10:22 Sent To  
Notes
2021-04-29 13:06:54PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. REF. PLAN PAGE 1.CORRECT BLDG. DESIGN PARAMETERS TO
 2020 FBC 7TH ED AND ASCE 7-16. (ASCE 7-10 IS STILL
 REFERENCED ON PLAN PAGE 1).
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. REF. PLAN PAGE 3. PROVIDE PRODUCT APPROVALS FL
 17347.7 AND NOA 20-0922.23. (SEE NEW COMMENTS BELOW)
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. PROVIDE A SITE DRAINAGE PLAN. CORRECTED
  
  
 4. PROVIDE A SOILS REPORT. CORRECTED
  
 NEW COMMENTS:
  
 5. PER COMMENT # 2 ABOVE, FL17347.7 HAS NOT BEEN
 SUBMITTED FOR REVIEW. NOA 20-0901.11 FOR FRENCH DOORS
 HAS BEEN SUBMITTED. IF YOU PLAN ON USING THIS NOA,
 CHANGE THE REFENCE TO FL17347.7 ON PLAN PAGE 3.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-31 Cont ID  
Sent By cthroop Date 2021-03-31 Time 08:24 Rev Time 0.00
Received By cthroop Date 2021-03-30 Time 08:18 Sent To  
Notes
2021-03-31 08:31:54PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REF. PLAN PAGE 1.CORRECT BLDG. DESIGN PARAMETERS TO
 2020 FBC 7TH ED AND ASCE 7-16.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. REF. PLAN PAGE 3. PROVIDE PRODUCT APPROVALS FL
 17347.7 AND NOA 20-0922.23.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. PROVIDE A SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 4. PROVIDE A SOILS REPORT.
 1803.2 INVESTIGATIONS REQUIRED.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN
 ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5.
 EXCEPTION: THE BUILDING OFFICIAL SHALL BE PERMITTED TO
 WAIVE THE REQUIREMENT FOR A GEOTECHNICAL INVESTIGATION
 WHERE SATISFACTORY DATA FROM ADJACENT AREAS IS
 AVAILABLE THAT DEMONSTRATES AN INVESTIGATION IS NOT
 NECESSARY FOR ANY OF THE CONDITIONS IN SECTIONS
 1803.5.1 THROUGH 1803.5.6 AND SECTIONS 1803.5.10 AND
 1803.5.11
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-13 Cont ID  
Sent By fgiaquin Date 2021-03-13 Time 22:38 Rev Time 0.00
Received By fgiaquin Date 2021-03-13 Time 21:40 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-12-28 Cont ID  
Sent By jleahy Date 2021-12-28 Time 11:40 Rev Time 0.00
Received By jleahy Date 2021-12-28 Time 11:40 Sent To  
Notes
2021-12-28 11:41:10CENTRAL VAC SYSTEM JLEAHY

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-03-22 Cont ID  
Sent By lcrespo Date 2021-03-22 Time 17:01 Rev Time 0.00
Received By lcrespo Date 2021-03-22 Time 17:01 Sent To  
Notes
2021-03-22 17:02:06GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-05-13 Cont ID  
Sent By lmarchan Date 2021-05-13 Time 15:20 Rev Time 0.00
Received By lmarchan Date 2021-05-05 Time 11:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-29 Cont ID  
Sent By cthroop Date 2021-04-29 Time 13:12 Rev Time 0.00
Received By cthroop Date 2021-04-09 Time 12:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-02 Cont ID  
Sent By pvalenti Date 2021-04-02 Time 10:08 Rev Time 0.00
Received By pvalenti Date 2021-04-01 Time 15:32 Sent To  
Notes
2021-04-02 10:11:14RESUBMITTAL DOCUMENTS WERE SUBMITTED UNDER THE
 ASSOCIATED MASTER PERMIT #21010247. THIS SUBMITTAL WAS
 MEANT TO BE SUBMITTED UNDER THE GAS PERMIT #21030166.
 PV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-31 Cont ID  
Sent By cthroop Date 2021-03-31 Time 08:31 Rev Time 0.00
Received By cthroop Date 2021-03-09 Time 12:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-22 Cont ID  
Sent By ccarvaja Date 2021-02-19 Time 05:22 Rev Time 0.00
Received By ccarvaja Date 2021-02-17 Time 12:20 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-05-20 Cont ID  
Sent By lmarchan Date 2021-05-20 Time 15:20 Rev Time 0.00
Received By lmarchan Date 2021-05-07 Time 11:40 Sent To  
Notes
2021-05-20 15:20:55NO FEES DUE $0.00
2021-05-07 11:40:475/7/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-03-30 Cont ID  
Sent By cthroop Date 2021-03-30 Time 10:02 Rev Time 0.00
Received By cthroop Date 2021-03-30 Time 10:02 Sent To  
Notes
2021-03-30 10:03:27PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-04-27 Cont ID  
Sent By medwards Date 2021-04-27 Time 11:01 Rev Time 0.00
Received By medwards Date 2021-04-27 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-04-23 Cont ID  
Sent By hmoser Date 2021-04-23 Time 11:13 Rev Time 0.00
Received By medwards Date 2021-04-23 Time 11:13 Sent To  
Notes
2021-04-23 11:38:26THE NEWEST MECHANICAL DRAWING DOES NOT HAVE THE SECON
 FLOOR OR THE AC UNIT DETAILS LIKE THE PREVIOUS SHEET
 HAD. PLEASE PROVIDE A COMPLETE MECHANICAL DRAWING FOR
 THE ENTIRE HOUSE. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-04-20 Cont ID  
Sent By hmoser Date 2021-04-20 Time 08:58 Rev Time 0.00
Received By hmoser Date 2021-04-20 Time 08:53 Sent To  
Notes
2021-04-20 08:58:08DENIED NO PLAN SUBMITTED. HM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By hmoser Date 2021-03-19 Time 10:42 Rev Time 0.00
Received By hmoser Date 2021-03-19 Time 09:39 Sent To  
Notes
2021-03-19 10:42:36PLAN DENIED
 1) REFER TO SECTION107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNORE OF THE PERSON
 RESPONSIBLE FOR THE
 DESIGN. FBC 2020.
 2) REFER TO SECTION 107 WEST PALM BEACH CITY
 AMENDMENTS.
 PROVIDE RETURN AIR CAN SIZE FOR A/C 1 AND 2., PROVIDE
 EQUIPMENT
 SCHEDULE ON THE PLAN.
 3) REFER TO SECTION M1503.4 MAKEUP AIR REQUIRED PROVIDE
 MANUFACTURER'S INSTRUCTIONS FOR RANGE HOOD AT FIRST
 MECHANICAL
 INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6776
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-03-22 Cont ID  
Sent By lcrespo Date 2021-03-22 Time 17:00 Rev Time 0.00
Received By lcrespo Date 2021-03-22 Time 16:43 Sent To  
Notes
2021-03-22 17:01:1103/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2021-05-06 Cont ID  
Sent By cthroop Date 2021-05-06 Time 08:37 Rev Time 0.00
Received By cthroop Date 2021-05-05 Time 13:47 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-04-29 Cont ID  
Sent By cthroop Date 2021-04-29 Time 13:06 Rev Time 0.00
Received By cthroop Date 2021-04-29 Time 10:21 Sent To  
Notes
2021-04-29 13:12:03PLAN REVIEW / ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS C2396-4 AND 17-0614.22 PER
 PLAN PAGE 3. (SEE NEW COMMENT BELOW)
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 NEW COMMENT:
  
 2. PLANS CALL FOR A METAL ROOF. NOA 19-1021.08
 SUBMITTED FOR REVIEW IS FOR CONCRETE TILE. SUBMIT
 CURRENT COPY OF A MIAMI-DADE NOA OR FLORIDA PRODUCT
 APPROVAL FOR THE PROPOSED METAL ROOFING.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-03-31 Cont ID  
Sent By cthroop Date 2021-03-31 Time 08:20 Rev Time 0.00
Received By cthroop Date 2021-03-30 Time 08:18 Sent To  
Notes
2021-03-31 08:24:23PLAN REVIEW / ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS C2396-4 AND 17-0614.22 PER
 PLAN PAGE 3.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-05-06 Cont ID  
Sent By cthroop Date 2021-05-06 Time 08:43 Rev Time 0.00
Received By cthroop Date 2021-05-05 Time 13:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-04-27 Cont ID  
Sent By medwards Date 2021-04-27 Time 11:01 Rev Time 0.00
Received By medwards Date 2021-04-27 Time 11:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-04-23 Cont ID  
Sent By medwards Date 2021-04-23 Time 11:38 Rev Time 0.00
Received By medwards Date 2021-04-23 Time 11:14 Sent To  
Notes
2021-04-23 11:39:40LATEST DRAWINGS MUST BE DIGITALLY SIGNED AND SEALED BY
 THE DESIGNER.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-04-02 Cont ID  
Sent By medwards Date 2021-04-02 Time 06:27 Rev Time 0.00
Received By medwards Date 2021-04-02 Time 06:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-31 Cont ID  
Sent By cthroop Date 2021-03-30 Time 15:33 Rev Time 0.00
Received By cthroop Date 2021-03-30 Time 08:18 Sent To  
Notes
2021-03-31 08:37:20ADDRESS COMMENTS FROM 1ST REVIEW. SEE BELOW.
  
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLEASE HAVE WILLIAM BENZ, PE REVIEW FAC
 61G15-22.001(C)(3):
  
 BEGINNING WITH THE FIFTH EDITION OF THE FLORIDA
 BUILDING CODE, ALL LICENSEES ACTIVELY PARTICIPATING IN
 THE DESIGN OF ENGINEERING WORKS OR SYSTEMS IN
 CONNECTION WITH BUILDINGS, STRUCTURES, OR FACILITIES
 AND SYSTEMS COVERED BY THE FLORIDA BUILDING CODE, AS
 IDENTIFIED WITHIN SECTION 553.73(1)(A), F.S., SHALL:
 (A) COMPLETE AT LEAST ONE (1) ADVANCED FLORIDA BUILDING
 CODE COURSE WITHIN TWELVE (12) MONTHS OF EACH EDITION
 OF THE FLORIDA BUILDING CODE EFFECTIVE DATE,
 (B) PROVIDE THE BOARD WITH A COPY OF A CERTIFICATE OF
 COMPLETION WHICH SHOWS: COURSE NUMBER, COURSE HOURS,
 CODE EDITION YEAR, AND CODE OR COURSE FOCUS. THIS
 COURSE MAY ALSO COUNT TOWARDS THE AREA OF PRACTICE
 REQUIREMENT FOR CONTINUING EDUCATION SET FORTH IN RULE
 61G15-22.001, F.A.C.
  
 ALTHOUGH THE RULE STATES THAT ENGINEERS HAVE A YEAR TO
 COMPLETE THE COURSE, FBPE HAS CONTACTED US TO ADVISE
 THAT, IF AN ENGINEER IS DESIGNING TO FBC2020, THEY
 SHOULD HAVE TAKEN THE COURSE PRIOR TO DESIGN SO THEY
 KNOW WHAT CHANGED.
  
 IF YOU HAVE QUESTIONS, PLEASE CONTACT FBPE DIRECTLY. IF
 THE COURSE IS NOT TAKEN AND THE WEBSITE
 MYFLORIDALICENSE.COM UPDATED PRIOR TO THE TIME THAT
 THIS PERMIT IS READY FOR ISSUANCE, PLEASE CONTACT ME.
 DIGITAL SIGNATURES OK.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-19 Cont ID  
Sent By shill Date 2021-02-19 Time 18:06 Rev Time 0.00
Received By shill Date 2021-02-19 Time 18:06 Sent To  
Notes
2021-02-19 18:07:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLEASE HAVE WILLIAM BENZ, PE REVIEW FAC
 61G15-22.001(C)(3):
  
 BEGINNING WITH THE FIFTH EDITION OF THE FLORIDA
 BUILDING CODE, ALL LICENSEES ACTIVELY PARTICIPATING IN
 THE DESIGN OF ENGINEERING WORKS OR SYSTEMS IN
 CONNECTION WITH BUILDINGS, STRUCTURES, OR FACILITIES
 AND SYSTEMS COVERED BY THE FLORIDA BUILDING CODE, AS
 IDENTIFIED WITHIN SECTION 553.73(1)(A), F.S., SHALL:
 (A) COMPLETE AT LEAST ONE (1) ADVANCED FLORIDA BUILDING
 CODE COURSE WITHIN TWELVE (12) MONTHS OF EACH EDITION
 OF THE FLORIDA BUILDING CODE EFFECTIVE DATE,
 (B) PROVIDE THE BOARD WITH A COPY OF A CERTIFICATE OF
 COMPLETION WHICH SHOWS: COURSE NUMBER, COURSE HOURS,
 CODE EDITION YEAR, AND CODE OR COURSE FOCUS. THIS
 COURSE MAY ALSO COUNT TOWARDS THE AREA OF PRACTICE
 REQUIREMENT FOR CONTINUING EDUCATION SET FORTH IN RULE
 61G15-22.001, F.A.C.
  
 ALTHOUGH THE RULE STATES THAT ENGINEERS HAVE A YEAR TO
 COMPLETE THE COURSE, FBPE HAS CONTACTED US TO ADVISE
 THAT, IF AN ENGINEER IS DESIGNING TO FBC2020, THEY
 SHOULD HAVE TAKEN THE COURSE PRIOR TO DESIGN SO THEY
 KNOW WHAT CHANGED.
  
 IF YOU HAVE QUESTIONS, PLEASE CONTACT FBPE DIRECTLY. IF
 THE COURSE IS NOT TAKEN AND THE WEBSITE
 MYFLORIDALICENSE.COM UPDATED PRIOR TO THE TIME THAT
 THIS PERMIT IS READY FOR ISSUANCE, PLEASE CONTACT ME.
  
 DIGITAL SIGNATURES OK.
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-05-13 Cont ID  
Sent By llouie Date 2021-05-13 Time   Rev Time 0.00
Received By llouie Date 2021-05-13 Time   Sent To  
Notes
2021-05-13 12:56:06SEPARATE PERMIT REQUIRED FOR SWIMMING POOL.

Review Stop Z ZONING
Rev No 2 Status F Date 2021-04-22 Cont ID  
Sent By llouie Date 2021-04-22 Time   Rev Time 0.00
Received By llouie Date 2021-04-22 Time   Sent To  
Notes
2021-04-22 10:46:23** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE SURVEY SUBMITTED WITH THE APPLICATION SHALL BE
 SIGNED AND SEALED BY THE SURVEYOR. [3/22/21 REPEAT
 COMMENT: NOT ADDRESSED. NO SURVEY WAS PROVIDED WITH THE
 RESUBMITTAL.]
  
 2.) THE SITE PLAN SHOWS A 5 FT. WIDE UTILITY EASEMENT
 AT THE REAR OF THE PROPERTY. THE UTILITY EASEMENT SEEMS
 TO ENCROACH 2.5 FT. WITHIN THE REAR PROPERTY LINE.
 ACCORDING TO THE SITE PLAN, THE POOL DECK SEEMS TO
 ENCROACH INTO THE EASEMENT, WHICH IS NOT PERMITTED.
 PLEASE ADDRESS. IT IS ALSO NECESSARY TO VERIFY THE
 LOCATION AND DIMENSIONS OF THE UTILITY EASEMENT WITH
 THE SUBMITTAL OF THE SURVEY FOR THE PROPERTY.
  
 3.) THE SITE PLAN (SHEET 1) NOTES A CHAIN LINK FENCE
 ALONG THE EAST PROPERTY LINE, BUT IT DOES NOT PROVIDE
 ANY ADDITIONAL INFORMATION, SUCH AS THE EXTENT OF THE
 FENCE ALONG THE PROPERTY LINE AND HOW TALL THE FENCE
 WILL BE. ALTHOUGH A SEPARATE FENCE PERMIT IS REQUIRED,
 INFORMATION ON THE PROPOSED FENCE SHALL BE PROVIDED ON
 THE MASTER AT THIS TIME. [3/22/21 MODIFIED/REPEAT
 COMMENT: PARTIALLY SATISFIED. MORE INFORMATION NEEDS TO
 BE PROVIDED IN THE SITE PLAN REGARDING THE PROPOSED
 STRUCTURES.]
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: SWIMMING POOL,
 DRIVEWAY, FENCES/WALLS, ETC.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  
 * REFERENCE: PB CASE NO. 1864 (LOT SPLIT) - APPROVED
 10/21/2020.
  
 * REFERENCE: LANDSCAPE PERMIT #21040537.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-22 Cont ID  
Sent By llouie Date 2021-03-22 Time   Rev Time  
Received By llouie Date 2021-03-22 Time   Sent To  
Notes
2021-03-22 10:23:44** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE SURVEY SUBMITTED WITH THE APPLICATION SHALL BE
 SIGNED AND SEALED BY THE SURVEYOR.
  
 2.) THE PROPERTY APPRAISER'S WEBSITE SEEMS TO INDICATE
 THAT THE PROPERTY IS COMPRISED OF LOTS 286 THROUGH 291.
 THE SURVEY AND SITE PLAN SEEMS TO INDICATE THAT THE
 PROPOSED DEVELOPMENT AND PROPERTY LINES IS FOR LOTS 289
 THROUGH 291 ONLY. PLEASE ADDRESS, AS THERE MUST BE
 CONSISTENCY WITH THE INFORMATION. ALSO, A LOT SPLIT
 APPLICATION SHALL BE SUBMITTED TO THE PLANNING DIVISION
 FOR REVIEW AND APPROVAL IF THE INTENT IS TO SPLIT THE
 LOTS. PLEASE CONTACT PLANNING DIVISION STAFF.
  
 3.) ALL STRUCTURAL ELEMENTS PROPOSED FOR THE PROPERTY
 (I.E. FENCES/WALLS AROUND THE POOL AND/OR PROPERTY,
 ETC.) SHALL BE SHOWN IN THE SITE PLAN AT THIS TIME.
  
 4.) SHOW SETBACK DISTANCE FROM THE A/C COMPRESSOR UNIT
 PADS TO THE SIDE PROPERTY LINE IN THE SITE PLAN. PLEASE
 NOTE THAT THE PAD(S) MAY NOT ENCROACH MORE THAN 4 FT.
 INTO THE SIDE SETBACK. [ZLDR S.94-305(B)(4)]
  
 5.) PROVIDE AND ILLUSTRATE THE CALCULATIONS FOR
 LANDSCAPED AREA WITHIN THE REQUIRED FRONT YARD (AREA
 WITHIN THE FIRST 25 FEET OF THE FRONT PROPERTY LINE).
 PLEASE NOTE THAT THE PROJECT SHALL CONTAIN A MINIMUM OF
 1,000 SQUARE FEET OF LANDSCAPED AREA WITH LIVING PLANT
 MATERIAL (I.E. GRASS, GROUND COVER, SHRUBS, HEDGES,
 VINES OR TREES, ETC.) WITHIN THE REQUIRED FRONT
 SETBACK. [ZLDR S.94-482(A)]
  
 6.) SHOW SETBACK DISTANCE FROM THE EDGES OF THE
 PROPOSED NEW CIRCULAR DRIVE TO THE SIDE PROPERTY LINES.
 [ZLDR S.94-482(D)]
  
 7.) SEPARATE PERMIT REQUIRED FOR LANDSCAPING. LANDSCAPE
 PERMIT SHALL BE SUBMITTED PRIOR TO ZONING APPROVAL OF
 THIS PERMIT. [NOTE: A LANDSCAPE PLAN HAS BEEN PROVIDED
 WITH THIS PERMIT SUBMITTAL; HOWEVER, LANDSCAPING MUST
 BE ADDRESSED AS A SEPARATE PERMIT.]
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, SWIMMING
 POOL, DRIVEWAY, FENCES/WALLS, ETC.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  