2021-01-08 15:55:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THE PLAN SHEETS INDICATES A CITY ADDRESS OF RIVIERA |
| BEACH. |
| |
| PLEASE REVIEW AND CORRECT OR SEND PERMIT TO RIVIERA |
| BEACH |
| |
| |
| |
| 2) THERE IS NO INDICATION OF COMPLIANCE WITH NFPA 101, |
| CH 7, MEANS OF EGRESS. |
| |
| 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR |
| ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF |
| EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT |
| ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| AFFIXED TO THE DOOR LEAF. |
| (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. |
| (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| HAND IN THE DIRECTION OF EGRESS. |
| (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE |
| DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE |
| DIRECTION OF EGRESS. |
| (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS |
| CONTROL SYSTEM UNITS. |
| |
| |
| PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT TO |
| COMPLY. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |