Plan Review Details - Permit 21010110
Plan Review Stops For Permit 21010110
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-12 Cont ID  
Sent By rmcdouga Date 2021-04-12 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2021-04-12 Time 15:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-12 Cont ID  
Sent By rmcdouga Date 2021-02-12 Time 09:06 Rev Time 0.00
Received By rmcdouga Date 2021-02-12 Time 09:06 Sent To  
Notes
2021-02-12 09:08:11PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 THE COMMENT WAS NOT ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REVISE NOTE ON SURVEY TO REQUIRE THAT GENERATOR
 EXHAUST IS TO BE 10' FROM ANY OPENINGS. FBC-R303.5.1
 INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR
 INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET
 (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-11 Cont ID  
Sent By rmcdouga Date 2021-01-11 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2021-01-11 Time 07:54 Sent To  
Notes
2021-01-11 08:01:35PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REVISE NOTE ON SURVEY TO REQUIRE THAT GENERATOR
 EXHAUST IS TO BE 10' FROM ANY OPENINGS. FBC-R303.5.1
 INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR
 INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET
 (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-15 Cont ID  
Sent By cthroop Date 2021-01-15 Time 13:43 Rev Time 0.00
Received By cthroop Date 2021-01-15 Time 13:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-01-21 Cont ID  
Sent By abelisle Date 2021-01-21 Time 14:28 Rev Time 0.00
Received By abelisle Date 2021-01-19 Time 18:34 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-12 Cont ID  
Sent By rmcdouga Date 2021-04-12 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2021-04-07 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-12 Cont ID  
Sent By rmcdouga Date 2021-02-12 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2021-02-07 Time 23:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-21 Cont ID  
Sent By lmarchan Date 2021-01-21 Time 16:18 Rev Time 0.00
Received By lmarchan Date 2021-01-06 Time 08:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-01-21 Cont ID  
Sent By abelisle Date 2021-01-21 Time 14:28 Rev Time 0.00
Received By abelisle Date 2021-01-21 Time 14:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-12 Cont ID  
Sent By rmcdouga Date 2021-04-12 Time 15:43 Rev Time 0.00
Received By rmcdouga Date 2021-04-12 Time 15:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-02-12 Cont ID  
Sent By rmcdouga Date 2021-02-12 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2021-02-12 Time 09:11 Sent To  
Notes
2021-02-12 09:11:10THE PREVIOUS COMMENT HAS NOT BEEN ADDRESSED. THE
 GENERATOR PAD ENGINEERING SHOULD BE UPLOADED AS A
 SEPARATE FILE WITH A VALID DIGITAL SIGNATURE.
  
 I WAS NOT ABLE TO VERIFY THE ENGINEER'S DIGITAL
 SIGNATURE ON THE PRE-FAB GENERATOR PAD DRAWING. IT IS
 THE LAST PAGE OF THE GENERATOR SPECS. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-11 Cont ID  
Sent By rmcdouga Date 2021-01-11 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2021-01-11 Time 07:54 Sent To  
Notes
2021-01-11 07:57:41I WAS NOT ABLE TO VERIFY THE ENGINEER'S DIGITAL
 SIGNATURE ON THE PRE-FAB GENERATOR PAD DRAWING. IT IS
 THE LAST PAGE OF THE GENERATOR SPECS. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2021-01-19 Cont ID  
Sent By rthermid Date 2021-01-19 Time   Rev Time  
Received By rthermid Date 2021-01-19 Time   Sent To I
Notes
***NONE***