Plan Review Details - Permit 21010035
Plan Review Stops For Permit 21010035
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-22 Cont ID  
Sent By cpuell Date 2021-01-22 Time 11:24 Rev Time 0.00
Received By cpuell Date 2021-01-22 Time 11:24 Sent To  
Notes
2021-01-22 11:24:20SUITE 801 ESTABLISHED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-01-05 Cont ID  
Sent By cpuell Date 2021-01-05 Time 12:35 Rev Time 0.00
Received By cpuell Date 2021-01-05 Time 12:35 Sent To  
Notes
2021-01-05 12:36:30SUITE 801 IS NOT CURRENLT A LEGAL ADDRESS, PLEASE EMAIL
 [email protected] A FLOOR PLAN FOR THE ENTIRE FLOOR THIS
 SUITE WILL BE ON, WHAT FLOOR IS THE PROJECT ON, HAS
 THERE BEEN A TENANT IN THAT SPACE PREVIOUSLY?

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-01-21 Cont ID  
Sent By jwitmer Date 2021-01-21 Time 13:49 Rev Time 0.00
Received By jwitmer Date 2021-01-21 Time 13:48 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-01-19 Cont ID  
Sent By jwitmer Date 2021-01-19 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2021-01-19 Time 08:08 Sent To  
Notes
2021-01-19 10:05:16COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-02-17 Cont ID  
Sent By jwitmer Date 2021-02-17 Time 08:56 Rev Time 0.00
Received By jwitmer Date 2021-02-17 Time 08:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2021-02-02 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2021-02-02 Time 09:31 Sent To  
Notes
2021-02-02 09:54:47WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21010035
 ADD: 515 N. FLAGLER DR. SUITE: 801
 CONT: FINE LINE CONSTRUCTION
 TEL: 561-582-7880
 E-MAIL: ASTEINBORG@FINELINE CONTRACTORS.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 1ST REVIEW
 DATE: TUES. JAN. 19TH/2021
 ACTION: DENIED
  
 1) SEMI-COMPLIED. LIFE SAFETY PLAN CORRECTED. SHEETS
 A1, A2, A3, A4, E1, E2, M1 & P1 NOT CORRECTED.
 DISCREPANCY IN PLANS.
 PLEASE CORRECT THE LABELING OF KITCHENS AND STORAGE
 ROOM. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 1ST ROUND OF COMMENTS. THE LIFE SAFETY SHEET SHOWS
 TRAVEL DISTANCES IN THE WORK WHERE THE NEW WORK IS
 PROPOSED, BUT NOT ON THE OTHER SIDE OF THE NEW WALL
 (EXISTING KITCHEN) THAT CREATES DEAD END CORRIDORS &
 EGRESS THROUGH A KITCHEN AND CLOSET. NOTE THE EXISTING
 KITCHEN HAS AN EXISTING STORAGE ROOM. THIS ROUTE CANNOT
 BE USED AS AN EXIT ACCESS POINT SINCE YOU WOULD BE
 REQUIRED TO GO THROUGH A STORAGE ROOM.
 2020 EXISTING BUILDING CODE LEVEL II 801.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
 2017 FBC-B 1016.2 EGRESS THROUGH INTERVENING SPACES.
 1016.2.5. EGRESS SHALL NOT PASS THROUGH KITCHENS,
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES.
  
 2) SEMI-COMPLIED. LIFE SAFETY PLAN CORRECTED. SHEETS
 A1, A2, A3, A4, E1, E2, M1 & P1 NOT CORRECTED.
 DISCREPANCY IN PLANS.
 PLEASE CORRECT THE LABELING OF KITCHENS AND STORAGE
 ROOM. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 1ST ROUND OF COMMENTS. THE LIFE SAFETY PLAN ALSO SHOWS
 A CODE NON-CONFORMITY IN THE EXISTING KITCHEN, THE
 ENTRY DOOR INTO THE EXISTING KITCHEN DOES NOT HAVE 18
 INCHES MANEUVERING CLEARANCES ON THE LATCH SIDE OF THE
 DOOR. IN THE 2020 EXISTING BUILDING CODE IN LEVEL 2
 ALTERATIONS FOR ACCESSIBILITY ISSUES YOU BACK TO THE
 2020 ACCESSIBILITY CODE SECTION 202.4.1.
 DISPROPORTIONATE COST. FLORIDA ACCESSIBILITY CODE
 SECTION: DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW
 HOW YOU ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS (50,000.00 DOLLARS)
 LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT
 AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE.
  
 3) COMPLIED.
  
 4) COMPLIED. NOTICE TO THE DESIGNER OF RECORD.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
  
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-01-19 Time 10:01 Rev Time  
Received By   Date 2021-01-19 Time 08:03 Sent To  
Notes
2021-01-19 10:04:252017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21010035
 ADD: 515 N. FLAGLER DR. SUITE: 801
 CONT: FINE LINE CONSTRUCTION
 TEL: 561-582-7880
 E-MAIL: ASTEINBORG@FINELINE CONTRACTORS.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 1ST REVIEW
 DATE: TUES. JAN. 19TH/2021
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET SHOWS TRAVEL DISTANCES IN THE
 WORK WHERE THE NEW WORK IS PROPOSED, BUT NOT ON THE
 OTHER SIDE OF THE NEW WALL (EXISTING KITCHEN) THAT
 CREATES DEAD END CORRIDORS & EGRESS THROUGH A KITCHEN
 AND CLOSET. NOTE THE EXISTING KITCHEN HAS AN EXISTING
 STORAGE ROOM. THIS ROUTE CAN NOT BE USED AS AN EXIT
 ACCESS POINT SINCE YOU WOULD BE REQUIRED TO GO THROUGH
 A STORAGE ROOM.
 2020 EXISTING BUILDING CODE LEVEL II 801.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
 2017 FBC-B 1016.2 EGRESS THROUGH INTERVENING SPACES.
 1016.2.5. EGRESS SHALL NOT PASS THROUGH KITCHENS,
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES.
  
 2) THE LIFE SAFETY PLAN ALSO SHOWS A CODE
 NON-CONFORMITY IN THE EXISTING KITCHEN, THE ENTRY DOOR
 INTO THE EXISTING KITCHEN DOES NOT HAVE 18 INCHES
 MANEUVERING CLEARANCES ON THE LATCH SIDE OF THE DOOR.
 IN THE 2020 EXISTING BUILDING CODE IN LEVEL 2
 ALTERATIONS FOR ACCESSIBILITY ISSUES YOU BACK TO THE
 2020 ACCESSIBILITY CODE SECTION 202.4.1.
 DISPROPORTIONATE COST. FLORIDA ACCESSIBILITY CODE
 SECTION: DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW
 HOW YOU ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS (50,000.00 DOLLARS)
 LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT
 AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2017 ACCESSIBILITY CODE.
 3) SHEET A5 DETAIL # 2 SHOWS A CONFERENCE ROOM CABINET,
 NORTH WALL AT A HEIGHT OF 34 INCHES.
 2020 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 ADVISORY 226.1. IN FACILITIES COVERED BY THE ADA, THIS
 REQUIREMENT DOES NOT APPLY TO WORK SURFACES USED ONLY
 BY EMPLOYEES. HOWEVER, THE ADA AND, WHERE APPLICABLE,
 SECTION 504 OF THE REHABILITATION ACT OF 1973, AS
 AMENDED, PROVIDE THAT EMPLOYEES ARE ENTITLED TO
 ?REASONABLE ACCOMMODATIONS.? WITH RESPECT TO WORK
 SURFACES, THIS MEANS THAT EMPLOYERS MAY NEED TO PROCURE
 OR ADJUST WORK STATIONS SUCH AS DESKS, LABORATORY AND
 WORK BENCHES, FUME HOODS, RECEPTION COUNTERS, TELLER
 WINDOWS, STUDY CARRELS, COMMERCIAL KITCHEN COUNTERS,
 AND CONFERENCE TABLES TO ACCOMMODATE THE INDIVIDUAL
 NEEDS OF EMPLOYEES WITH DISABILITIES ON AN ?AS NEEDED?
 BASIS. CONSIDER WORK SURFACES THAT ARE FLEXIBLE AND
 PERMIT INSTALLATION AT VARIABLE HEIGHTS AND CLEARANCES.
  
  
 4) NOTICE TO THE DESIGNER OF RECORD. SHEET A-6 SHOWS A
 ELEVATION VIEW OF THE NEW PROPOSED KITCHEN. ABOVE THE
 SINK AND BASE CABINETS THERE IS AN OPEN SHELF ABOVE THE
 REACH RANGES FOUND IN THE 2020 FBC-ACCESSIBILITY CODE.
 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
 NOTE THE ELECTRICAL SHEETS E2 & E3 SHOW ABOVE THE SHELF
 LEVEL THERE IS A 20 AMP. SMALL APPLIANCE CIRCUIT. IF
 BEFORE A CERTIFICATE OF COMPLETION IS GIVEN A MICROWAVE
 IS PLACED ON THIS SHELF IT WILL NOT BE IN COMPLIANCE
 WITH THE 2020 ACCESSIBILITY CODE SECTION 309 OPERABLE
 PARTS .
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
  
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-02-22 Cont ID  
Sent By jleahy Date 2021-02-22 Time 16:15 Rev Time 0.00
Received By jleahy Date 2021-02-22 Time 16:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-08 Cont ID  
Sent By jleahy Date 2021-02-08 Time 12:55 Rev Time 0.00
Received By jleahy Date 2021-02-08 Time 10:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-20 Cont ID  
Sent By jleahy Date 2021-01-20 Time 09:32 Rev Time 0.00
Received By jleahy Date 2021-01-20 Time 08:28 Sent To  
Notes
2021-01-20 10:05:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 "NEW 2017 NEC CODE CHANGES" #1, AND #2
  
 1) OUTLETS IN COMMON AREAS OF OFFICE AREAS TO BE TAMPER
 RESISTANT, SEE THE FOLLOWING SECTION OF ALL THE
 LOCATIONS FOR COMMERCIAL OCCUPANCIES.#5 AND #6
  
 406.12 TAMPER-RESISTANT RECEPTACLES. ALL 15- AND
 20-AMPERE, 125- AND 250-VOLT NONLOCKING-TYPE
 RECEPTACLES IN THE AREAS SPECIFIED IN 406.12(1) THROUGH
 (7) SHALL BE LISTED TAMPER-RESISTANT RECEPTACLES.
 (2) GUEST ROOMS AND GUEST SUITES OF HOTELS AND MOTELS
 (3) CHILD CARE FACILITIES
 (4) PRESCHOOLS AND ELEMENTARY EDUCATION FACILITIES
 (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE
 LIKE IN CLINICS, MEDICAL AND DENTAL OFFICES AND
 OUTPATIENT FACILITIES
 (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2
 TO INCLUDE PLACES OF WAITING TRANSPORTATION,
 GYMNASIUMS, SKATING RINKS, AND AUDITORIUMS
 (7) DORMITORIES
  
  
 2) MEETING ROOOM TO HAVE FLOOR RECEPTACLES INSTALLED TO
 MEET 210.71(B)
  
 210.71(B)(2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM
 THAT IS AT LEAST 3.7 M (12 FT) WIDE AND THAT HAS A
 FLOOR AREA OF AT LEAST 20 M2 (215 FT2) SHALL HAVE AT
 LEAST ONE RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A
 DISTANCE NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL
 FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR
 SPACE.
  
 3) RISER DIAGRAM SHOWS #4 TO TRANSFORMER BUT THE PANEL
 SCHEDULE "H" SHOWS #6 PLEASE FIX.

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2021-02-22 Cont ID  
Sent By jleahy Date 2021-02-22 Time 16:16 Rev Time 0.00
Received By jleahy Date 2021-02-22 Time 16:16 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-02-08 Cont ID  
Sent By jleahy Date 2021-02-08 Time 13:00 Rev Time 0.00
Received By jleahy Date 2021-02-08 Time 13:00 Sent To  
Notes
2021-02-08 13:00:53VOICE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-02-19 Cont ID  
Sent By pleduc Date 2021-02-19 Time   Rev Time 0.00
Received By pleduc Date 2021-02-19 Time 10:37 Sent To  
Notes
2021-02-19 10:46:52FRE PROVISO:
  
 ALL FIRE SPRINKLER AND FIRE ALARM WORK SHALL BE DONE
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS
  
 THE FS & FA SYTEMS SHALL BE MAINTAINED THROUGHOUT THE
 DEMO AND CONSTRUCTION PERIODS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-22 Cont ID  
Sent By jleahy Date 2021-02-22 Time 16:16 Rev Time 0.00
Received By jleahy Date 2021-02-10 Time 16:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-08 Cont ID  
Sent By jleahy Date 2021-02-08 Time 13:01 Rev Time 0.00
Received By jleahy Date 2021-01-28 Time 12:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-20 Cont ID  
Sent By jleahy Date 2021-01-20 Time 10:06 Rev Time 0.00
Received By jleahy Date 2021-01-06 Time 14:00 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-01-19 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2021-01-19 Time 08:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By medwards Date 2021-02-17 Time 13:25 Rev Time 0.00
Received By medwards Date 2021-02-17 Time 13:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-01-12 Cont ID  
Sent By medwards Date 2021-01-12 Time 17:03 Rev Time 0.00
Received By medwards Date 2021-01-12 Time 17:02 Sent To  
Notes
2021-01-12 17:18:35APPROVED WITH PRIVISO:
 THE CONFERENCE ROOM WILL REQUIRE 129 CFM OF OUTDOOR
 AIR. THIS WOULD BRING THE TOTAL OUTDOOR AIR TO 339 CFM.
 ME

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-02-19 Cont ID  
Sent By tklarge Date 2021-02-19 Time 12:44 Rev Time 0.00
Received By tklarge Date 2021-02-19 Time 12:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-01-09 Cont ID  
Sent By abelisle Date 2021-01-09 Time 18:33 Rev Time 0.00
Received By abelisle Date 2021-01-09 Time 18:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2021-02-17 Time 08:56 Rev Time 0.00
Received By jwitmer Date 2021-02-17 Time 08:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-02-02 Time 9:58 Rev Time 0.00
Received By jwitmer Date 2021-02-02 Time 09:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-12 Cont ID  
Sent By medwards Date 2021-01-12 Time 17:18 Rev Time 0.00
Received By medwards Date 2021-01-12 Time 17:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-01-13 Cont ID  
Sent By elevesqu Date 2021-01-13 Time 14:48 Rev Time 0.00
Received By elevesqu Date 2021-01-13 Time 14:48 Sent To  
Notes
***NONE***