Plan Review Details - Permit 21010007
Plan Review Stops For Permit 21010007
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-01-13 Cont ID  
Sent By cpuell Date 2021-01-13 Time 16:37 Rev Time 0.00
Received By cpuell Date 2021-01-13 Time 16:37 Sent To  
Notes
2021-04-29 10:38:23THIS IS A PRIMARY ADDRESS FOR THE WHOLE PROJECT,
 INDIVIDUAL UNIT ADDRESSES NOT YET ESTABLISHED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2021-10-14 Cont ID  
Sent By rmcphers Date 2021-10-14 Time 16:24 Rev Time 0.00
Received By rmcphers Date 2021-10-14 Time 16:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2021-09-20 Cont ID  
Sent By rmcphers Date 2021-09-20 Time 15:04 Rev Time 0.00
Received By rmcphers Date 2021-09-20 Time 15:00 Sent To  
Notes
2021-09-20 15:04:15MASTER FOUNDATION ONLY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) DRAWING SP-4 NEEDS TO BE SIGNED BY THE DESIGNER -
 THE WORDS "NOT FOR CONSTRUCTION" CANNOT BE ON THE
 PROPOSED SITE PLAN.
  
 2) PLEASE PROVIDE A SURVEY.
  
 FOUNDATION PERMIT WILL ONLY BE ISSUED WITH BUILDING
 OFFICIAL APPROVAL - FBC WPB AMENDMENTS 105.13 PHASED
 PERMIT APPROVAL. AFTER SUBMITTAL OF THE APPROPRIATE
 CONSTRUCTION DOCUMENTS,
 THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT
 FOR THE CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER
 PART OF A BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION
 DOCUMENTS FOR THE WHOLE BUILDING OR STRUCTURE
 HAVE BEEN SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE
 FOUNDATION OR OTHER PARTS OF A
 BUILDING OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN
 RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE
 REQUIRED TO MEET THE REQUIREMENTS OF THE TECHNICAL
 CODES. THIS PROVISION IS ONLY FOR THE
 FLORIDA BUILDING CODE. ALL OTHER AGENCY APPROVALS
 NECESSARY FOR CONSTRUCTION MUST BE SECURED
 PRIOR TO THIS PROVISION BEING APPLIED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-08-12 Cont ID  
Sent By rmcphers Date 2021-08-12 Time 09:42 Rev Time 0.00
Received By rmcphers Date 2021-08-12 Time 09:34 Sent To  
Notes
2021-08-12 09:41:58MASTER FOUNDATION ONLY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 THE STRUCTURAL FOUNDATION DRAWINGS ARE IN THE
 "SIGNATURE" FOLDER - THEY NEED TO BE IN THE "DRAWINGS"
 FOLDER IN PROJECTDOX.
 UPDATED SITE PLAN HAS NOT BEEN PROVIDED
 REVISED SHEETS S3, S5 AND S6 HAVE NOT BEEN PROVIDED
 1) STRUCTURAL DRAWINGS (S-6) SHOW THE DESIGN PER FBC
 2017 AND ASCE 7-10 - PLEASE REVISE THE DRAWINGS TO SHOW
 THE DESIGN PER FBC 2020 AND ASCE 7-16
 2) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT.
 3) PLEASE SHOW THE SEPARATION DISTANCE BETWEEN EACH
 BUILDING AND FROM PROPERTY LINES FBC 602
  
 FOUNDATION PERMIT WILL ONLY BE ISSUED WITH BUILDING
 OFFICIAL APPROVAL - FBC WPB AMENDMENTS 105.13 PHASED
 PERMIT APPROVAL. AFTER SUBMITTAL OF THE APPROPRIATE
 CONSTRUCTION DOCUMENTS,
 THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT
 FOR THE CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER
 PART OF A BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION
 DOCUMENTS FOR THE WHOLE BUILDING OR STRUCTURE
 HAVE BEEN SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE
 FOUNDATION OR OTHER PARTS OF A
 BUILDING OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN
 RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE
 REQUIRED TO MEET THE REQUIREMENTS OF THE TECHNICAL
 CODES. THIS PROVISION IS ONLY FOR THE
 FLORIDA BUILDING CODE. ALL OTHER AGENCY APPROVALS
 NECESSARY FOR CONSTRUCTION MUST BE SECURED
 PRIOR TO THIS PROVISION BEING APPLIED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-07-02 Cont ID  
Sent By rmcphers Date 2021-07-02 Time 12:45 Rev Time 0.00
Received By rmcphers Date 2021-07-02 Time 12:33 Sent To  
Notes
2021-07-02 12:44:57FOUNDATION ONLY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 THE STRUCTURAL FOUNDATION DRAWINGS ARE IN THE
 "SIGNATURE" FOLDER - THEY NEED TO BE IN THE "DRAWINGS"
 FOLDER IN PROJECTDOX.
  
 1) STRUCTURAL DRAWINGS (S-6) SHOW THE DESIGN PER FBC
 2017 AND ASCE 7-10 - PLEASE REVISE THE DRAWINGS TO SHOW
 THE DESIGN PER FBC 2020 AND ASCE 7-16
 2) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT.
  
 UPDATED SITE PLAN HAS NOT BEEN PROVIDED
  
 3) SHOW WHICH BUILDING IS ADDRESS 2113
 4) PLEASE SHOW THE SEPARATION DISTANCE BETWEEN
 BUILDINGS AND FROM PROPERTY LINES FBC 602
 5) A SEPARATE BUILDING PERMIT WILL BE REQUIRED FOR EACH
 BUILDING - SHOWING ADDRESS AND JOB COST FOR EACH.
 6) JOB VALUE SHOWN ON THE BUILDING PERMIT FOR THE
 FOUNDATION ONLY PERMIT APPLICATION APPEARS TO BE LOW -
 PLEASE PROVIDE A COST BREAKDOWN. FBC WPB 109.3
  
  
 FOUNDATION PERMIT WILL ONLY BE ISSUED WITH BUILDING
 OFFICIAL APPROVAL - FBC WPB AMENDMENTS 105.13 PHASED
 PERMIT APPROVAL. AFTER SUBMITTAL OF THE APPROPRIATE
 CONSTRUCTION DOCUMENTS,
 THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT
 FOR THE CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER
 PART OF A BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION
 DOCUMENTS FOR THE WHOLE BUILDING OR STRUCTURE
 HAVE BEEN SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE
 FOUNDATION OR OTHER PARTS OF A
 BUILDING OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN
 RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE
 REQUIRED TO MEET THE REQUIREMENTS OF THE TECHNICAL
 CODES. THIS PROVISION IS ONLY FOR THE
 FLORIDA BUILDING CODE. ALL OTHER AGENCY APPROVALS
 NECESSARY FOR CONSTRUCTION MUST BE SECURED
 PRIOR TO THIS PROVISION BEING APPLIED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-13 Cont ID  
Sent By rmcphers Date 2021-05-13 Time 12:33 Rev Time 0.00
Received By rmcphers Date 2021-05-13 Time 12:20 Sent To  
Notes
2021-05-13 12:22:47FOUNDATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) STRUCTURAL DRAWINGS SHOW THE DESIGN PER ASCE 7-10 -
 PLEASE REVISE THE DRAWINGS TO SHOW THE DESIGN PER FBC
 2020 AND ASCE 7-16
 2) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT.
 3) SHOW WHICH BUILDING IS ADDRESS 2113
 4) PLEASE SHOW THE SEPARATION DISTANCE BETWEEN
 BUILDINGS AND FROM PROPERTY LINES FBC 602
 5) A SEPARATE BUILDING PERMIT WILL BE REQUIRED FOR EACH
 BUILDING - SHOWING ADDRESS AND JOB COST FOR EACH.
 6) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - PLEASE PROVIDE A COST BREAKDOWN.
 7) WHEN WILL YOU APPLY FOR THE COMPLETE BUILDING
 PERMIT?
  
 FOUNDATION PERMIT WILL ONLY BE ISSUED WITH BUILDING
 OFFICIAL APPROVAL - FBC WPB AMENDMENTS 105.13 PHASED
 PERMIT APPROVAL. AFTER SUBMITTAL OF THE APPROPRIATE
 CONSTRUCTION DOCUMENTS,
 THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT
 FOR THE CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER
 PART OF A BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION
 DOCUMENTS FOR THE WHOLE BUILDING OR STRUCTURE
 HAVE BEEN SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE
 FOUNDATION OR OTHER PARTS OF A
 BUILDING OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN
 RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE
 REQUIRED TO MEET THE REQUIREMENTS OF THE TECHNICAL
 CODES. THIS PROVISION IS ONLY FOR THE
 FLORIDA BUILDING CODE. ALL OTHER AGENCY APPROVALS
 NECESSARY FOR CONSTRUCTION MUST BE SECURED
 PRIOR TO THIS PROVISION BEING APPLIED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-29 Cont ID  
Sent By rmcphers Date 2021-01-29 Time 08:42 Rev Time 0.00
Received By rmcphers Date 2021-01-28 Time 15:15 Sent To  
Notes
2021-01-29 08:42:18FOUNDATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE
 THE DRAWINGS TO SHOW THE DESIGN PER FBC 2020 AND ASCE
 7-16
 2) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT.
 3) SHOW WHICH BUILDING IS ADDRESS 2113
 4) PLEASE SHOW THE SEPARATION DISTANCE BETWEEN
 BUILDINGS AND FROM PROPERTY LINES FBC 602
 5) A SEPARATE BUILDING PERMIT WILL BE REQUIRED FOR EACH
 BUILDING - SHOWING ADDRESS AND JOB COST FOR EACH.
 6) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - PLEASE PROVIDE A COST BREAKDOWN.
 7) WHEN WILL YOU APPLY FOR THE COMPLETE BUILDING
 PERMIT?
  
 FOUNDATION PERMIT WILL ONLY BE ISSUED WITH BUILDING
 OFFICIAL APPROVAL - FBC WPB AMENDMENTS 105.13 PHASED
 PERMIT APPROVAL. AFTER SUBMITTAL OF THE APPROPRIATE
 CONSTRUCTION DOCUMENTS,
 THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT
 FOR THE CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER
 PART OF A BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION
 DOCUMENTS FOR THE WHOLE BUILDING OR STRUCTURE
 HAVE BEEN SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE
 FOUNDATION OR OTHER PARTS OF A
 BUILDING OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN
 RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE
 REQUIRED TO MEET THE REQUIREMENTS OF THE TECHNICAL
 CODES. THIS PROVISION IS ONLY FOR THE
 FLORIDA BUILDING CODE. ALL OTHER AGENCY APPROVALS
 NECESSARY FOR CONSTRUCTION MUST BE SECURED
 PRIOR TO THIS PROVISION BEING APPLIED.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-10-28 Cont ID  
Sent By jleahy Date 2021-10-28 Time 16:39 Rev Time 0.00
Received By jleahy Date 2021-10-28 Time 16:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-08-13 Cont ID  
Sent By jleahy Date 2021-08-13 Time 14:01 Rev Time 0.00
Received By jleahy Date 2021-08-13 Time 13:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-29 Cont ID  
Sent By jleahy Date 2021-06-29 Time 15:34 Rev Time 0.00
Received By jleahy Date 2021-06-29 Time 14:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-05-14 Cont ID  
Sent By equinone Date 2021-05-14 Time 15:03 Rev Time 0.00
Received By equinone Date 2021-05-14 Time 15:03 Sent To  
Notes
2021-05-14 15:09:27CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) PLEASE CLARIFY IF ANY ELECTRICAL WORK (CONDUITS,
 EQUIPMENT) IS BEING DONE WITHIN THE SCOPE OF THIS
 PERMIT AND IF YES PLEASE PROVIDE DETAILS/SPECS. FBC 107
  
 -- ELECTRICAL DRAWINGS SUBMITTED ARE FOR THE ENTIRE
 CONSTRUCTION. PLEASE PROVIDE NOTES OR NARRATIVE
 INDICATING WHAT WILL BE COVERED UNDER THE FOUNDATION
 PERMIT.
 -- SUBELECTRICAL PERMIT REQUIRED TO COVER ANY
 ELECTRICAL RELATED WORK UNDER THE FOUNDATION PERMIT.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-26 Cont ID  
Sent By equinone Date 2021-01-26 Time 11:23 Rev Time 0.00
Received By equinone Date 2021-01-26 Time 11:23 Sent To  
Notes
2021-01-26 11:23:48CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) PLEASE CLARIFY IF ANY ELECTRICAL WORK (CONDUITS,
 EQUIPMENT) IS BEING DONE WITHIN THE SCOPE OF THIS
 PERMIT AND IF YES PLEASE PROVIDE DETAILS/SPECS. FBC 107
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2021-08-20 Cont ID  
Sent By rrossano Date 2021-08-20 Time   Rev Time 0.00
Received By rrossano Date 2021-08-20 Time   Sent To I
Notes
2021-12-09 07:27:28AT THIS TIME ENGINEERING AND PUBLIC UTILITIES ARE NOT
 SIGNING OFF ON ANY PERMITS UNTIL SUCH TIME THAT AN
 AGREEMENT HAS BEEN REACHED REGARDING LIFT STATION NO.
 77. THE VILLAS, PARCEL L2 AND THE HOTEL ARE ALL
 CONTRIBUTING FLOW. WE ARE WAITING ON THE COST ESTIMATE
 AND TIME LINE WHICH IS BEING PREPARED BY MOCK ROOS &
 ASSOC. UNDER CONTRACT WITH THE OWNERS.
  
 VINCENT J. NOEL, P.S.M.
 ENGINEERING LAND DEVELOPMENT MANAGER
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS ST., 4TH FLOOR
 WEST PALM BEACH, FL 33401
 PHONE: 561-494-1096
 FAX: 561-494-1116
 CELL 561-644-7288
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2021-06-21 Cont ID  
Sent By M Gonzal Date 2021-06-21 Time   Rev Time 1.00
Received By mgonzale Date 2021-06-21 Time   Sent To I
Notes
2021-06-21 14:55:49FOUNDATION

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-06-21 Cont ID  
Sent By mgonzale Date 2021-06-21 Time   Rev Time 0.00
Received By mgonzale Date 2021-06-21 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-02-16 Cont ID  
Sent By MGonzale Date 2021-02-16 Time   Rev Time 1.00
Received By mgonzale Date 2021-02-16 Time   Sent To I
Notes
2021-02-16 13:11:23PLEASE PROVIDE WATER AND SEWER PLAN SHOWING WATER
 METERS SERVICES AND SEWER SERVICES. [email protected]
 (561) 818-1322 ENGINEERING PROJECT COORDINATOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-08-05 Cont ID  
Sent By pleduc Date 2021-08-05 Time   Rev Time 0.00
Received By pleduc Date 2021-08-05 Time 10:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-05-13 Cont ID  
Sent By pleduc Date 2021-05-13 Time   Rev Time 0.00
Received By pleduc Date 2021-05-13 Time 15:55 Sent To  
Notes
2021-05-13 16:03:53THE PREVIOUS FIRE COMMENTS WERE NOT SPECIFICALLY
 ADDRESSED.
  
 THE PERMIT WILL BE APPROVED WITH THE PREVIOSU COMMENTS
 AS PROVISO THAT WILL REQUIRE A DETAILED RESPONSE, UNDER
 THE CONSTRUCTION SUBMITTAL OF THE STRUCTURE, TO EACH
 QUESTION ANDD/OR THE APPLICABLE SHEET PAGE THAT
 ADDRESSES THE COMMENT.
  
  
 THE PREVIOUS COMMENTS ARE LIST BELOW:
  
 FIRE HAS NO OBJECTION TO A FOUNDATION PERMIT; THE BELOW
 COMMENTS ARE MORE RELATED TO THE OCCUPANCY
 CLASSIFICATION AND IF A LIFE SAFETY REVIEW IS REQUIRED
 UNDER THE FLORIDA FIRE PREVENTION CODE.
  
 1) SHEET A000 - WITHIN THE SECTION TITLED DESIGN
 PARAMETERS, THERE IS AN INDICATION OF FBC GROUP R-1
 TWO-STORY DUPLEX.
  
 FOR CLARIFICATION PURPOSES, PER THE FLORIDA FIRE
 PREVENTION CODE ARE THESE CONSIDERED A TWO-FAMILY
 DWELLING PER NFPA 101 CH 24....OR ARE THEY ASSOCIATED
 WITH THE PROPOSED HOTEL AND BE RENTED OUT TO CLIENTS
 THUS COMPLYING WITH CH 28.
  
 3.3.145* HOTEL. A BUILDING OR GROUPS OF BUILDINGS UNDER
 THE SAME
 MANAGEMENT IN WHICH THERE ARE SLEEPING ACCOMMODATIONS
 FOR MORE
 THAN 16 PERSONS AND PRIMARILY USED BY TRANSIENTS FOR
 LODGING WITH OR
 WITHOUT MEALS.
  
 28.1.1.5 THE TERM HOTEL, WHEREVER USED IN THIS CODE,
 SHALL INCLUDE
 A HOTEL, AN INN, A CLUB, A MOTEL, A BED AND BREAKFAST,
 OR ANY OTHER
 STRUCTURE MEETING THE DEFINITION OF HOTEL.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
  
 2) SHOULD THIS BE CLASSIFIED AS AHOTEL OCCUPANCY A FIRE
 SPRINKLER SYTEM IS REQUIRED.
  
 28.3.5 EXTINGUISHMENT REQUIREMENTS.
 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH 28.3.5.3.
  
 PLEASE PROVIDE SPECIFIC DETAILS AND EOR DOCUMENTS PER
 F.A.C. 69G WITH THIS MASTER
  
  
  
 3) SHOULD THIS BE CLASSIFIED AS AHOTEL OCCUPANCY A FIRE
 ALARM SYTEM IS REQUIRED.
  
 28.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 28.3.4.1 GENERAL. A FIRE ALARM SYSTEM IN ACCORDANCE
 WITH SECTION
 9.6, EXCEPT AS MODIFIED BY 28.3.4.2 THROUGH 28.3.4.6,
 SHALL BE
 PROVIDED.
  
 PLEASE PROVIDE SPECIFIC DETAILS WITH THIS MASTER.
  
  
 4) SHOULD THIS BE CLASSIFIED AS A HOTEL OCCUPANCY AND
 WITH AN ATTACHED GARAGE
  
 28.3.4.6 CARBON MONOXIDE ALARMS AND CARBON MONOXIDE
 DETECTION SYSTEMS.
 28.3.4.6.1 CARBON MONOXIDE ALARMS OR CARBON MONOXIDE
 DETECTORS
 IN ACCORDANCE WITH SECTION 9.8 AND 28.3.4.6 SHALL BE
 PROVIDED IN
 NEW HOTELS AND DORMITORIES WHERE EITHER OF THE
 FOLLOWING
 CONDITIONS EXISTS:
 (1) GUEST ROOMS OR GUEST SUITES WITH COMMUNICATING
 ATTACHED
 GARAGES, UNLESS OTHERWISE EXEMPTED BY 28.3.4.6.3
 (2) GUEST ROOMS OR GUEST SUITES CONTAINING A
 PERMANENTLY
 INSTALLED FUEL-BURNING APPLIANCE OR FUEL-BURNING
 FIREPLACE
  
 PLEASE PROVIDE SPECIFIC DETAILS WITH THIS MASTER.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-01-14 Cont ID  
Sent By pleduc Date 2021-01-14 Time   Rev Time 0.00
Received By pleduc Date 2021-01-13 Time 14:15 Sent To  
Notes
2021-01-14 15:35:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 FIRE HAS NO OBJECTION TO A FOUNDATION PERMIT; THE BELOW
 COMMENTS ARE MORE RELATED TO THE OCCUPANCY
 CLASSIFICATION AND IF A LIFE SAFETY REVIEW IS REQUIRED
 UNDER THE FLORIDA FIRE PREVENTION CODE.
  
 1) SHEET A000 - WITHIN THE SECTION TITLED DESIGN
 PARAMETERS, THERE IS AN INDICATION OF FBC GROUP R-1
 TWO-STORY DUPLEX.
  
 FOR CLARIFICATION PURPOSES, PER THE FLORIDA FIRE
 PREVENTION CODE ARE THESE CONSIDERED A TWO-FAMILY
 DWELLING PER NFPA 101 CH 24....OR ARE THEY ASSOCIATED
 WITH THE PROPOSED HOTEL AND BE RENTED OUT TO CLIENTS
 THUS COMPLYING WITH CH 28.
  
 3.3.145* HOTEL. A BUILDING OR GROUPS OF BUILDINGS UNDER
 THE SAME
 MANAGEMENT IN WHICH THERE ARE SLEEPING ACCOMMODATIONS
 FOR MORE
 THAN 16 PERSONS AND PRIMARILY USED BY TRANSIENTS FOR
 LODGING WITH OR
 WITHOUT MEALS.
  
 28.1.1.5 THE TERM HOTEL, WHEREVER USED IN THIS CODE,
 SHALL INCLUDE
 A HOTEL, AN INN, A CLUB, A MOTEL, A BED AND BREAKFAST,
 OR ANY OTHER
 STRUCTURE MEETING THE DEFINITION OF HOTEL.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
  
 2) SHOULD THIS BE CLASSIFIED AS AHOTEL OCCUPANCY A FIRE
 SPRINKLER SYTEM IS REQUIRED.
  
 28.3.5 EXTINGUISHMENT REQUIREMENTS.
 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH 28.3.5.3.
  
 PLEASE PROVIDE SPECIFIC DETAILS AND EOR DOCUMENTS PER
 F.A.C. 69G WITH THIS MASTER
  
  
  
 3) SHOULD THIS BE CLASSIFIED AS AHOTEL OCCUPANCY A FIRE
 ALARM SYTEM IS REQUIRED.
  
 28.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 28.3.4.1 GENERAL. A FIRE ALARM SYSTEM IN ACCORDANCE
 WITH SECTION
 9.6, EXCEPT AS MODIFIED BY 28.3.4.2 THROUGH 28.3.4.6,
 SHALL BE
 PROVIDED.
  
 PLEASE PROVIDE SPECIFIC DETAILS WITH THIS MASTER.
  
  
 4) SHOULD THIS BE CLASSIFIED AS A HOTEL OCCUPANCY AND
 WITH AN ATTACHED GARAGE
  
 28.3.4.6 CARBON MONOXIDE ALARMS AND CARBON MONOXIDE
 DETECTION SYSTEMS.
 28.3.4.6.1 CARBON MONOXIDE ALARMS OR CARBON MONOXIDE
 DETECTORS
 IN ACCORDANCE WITH SECTION 9.8 AND 28.3.4.6 SHALL BE
 PROVIDED IN
 NEW HOTELS AND DORMITORIES WHERE EITHER OF THE
 FOLLOWING
 CONDITIONS EXISTS:
 (1) GUEST ROOMS OR GUEST SUITES WITH COMMUNICATING
 ATTACHED
 GARAGES, UNLESS OTHERWISE EXEMPTED BY 28.3.4.6.3
 (2) GUEST ROOMS OR GUEST SUITES CONTAINING A
 PERMANENTLY
 INSTALLED FUEL-BURNING APPLIANCE OR FUEL-BURNING
 FIREPLACE
  
 PLEASE PROVIDE SPECIFIC DETAILS WITH THIS MASTER.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
2021-01-13 14:18:45 
  
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2021-08-12 Cont ID  
Sent By ccole Date 2021-08-12 Time 13:36 Rev Time 0.00
Received By ccole Date 2021-08-12 Time 12:18 Sent To  
Notes
2021-08-12 13:38:28GAS REVIEW WAS NOT PERFORMED NOT UNDER THIS FOUNDATION
 ONLY PERMIT- 21010007. GAS SERVICE ENTRANCE WAS REMOVED
 FROM THE SCOPE OF WORK BY THE EOR.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-07-06 Cont ID  
Sent By ccole Date 2021-07-06 Time 11:16 Rev Time 0.00
Received By ccole Date 2021-07-06 Time 07:07 Sent To  
Notes
2021-07-06 11:19:562ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21010007
 7/6/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 DENIED,
 THIS IS THE 2ND REVIEW OF THE GAS SYSTEM FOR THE
 FOUNDATION PERMIT. COMMENTS FROM THE IST REVIEW ARE
 LISTED BELOW. THE REQUESTED NARRATIVE RESPONSE TO THE
 1ST REVIEW WAS NOT PROVIDED. ****PLEASE NOTE IF THERE
 WILL BE NO GAS PIPING PENETRATION OF THE NEW FOUNDATION
 SLAB OR RUN BELOW THE FOUNDATION THEN A GAS PIPING
 PERMIT WILL NOT BE REQUIRED FOR THE FOUNDATION ONLY
 PERMIT, AND ALL REVIEW COMMENTS SHALL BE ADDRESSED
 UNDER MASTER PERMIT- 21040185. PLEASE CONTACT ME IF YOU
 NEED FURTHER CLARIFICATION OR ADDITIONAL
 INFORMATION**** SOME COMMENTS HAVE BEEN REMOVED AND
 ADDITIONAL NOTES IN CAPS HAVE BEEN ADDED TO THE 1ST
 REVIEW COMMENTS BELOW.
  
 1ST GAS REVIEW.
 PLAN REVIEW RESULTS: DENIED. FOUNDATION REVIEW ONLY-
 SEPARATE PERMIT REQUIRED FOR NEW CONSTRUCTION OF THE
 VILLAS. A COMPLETE REVIEW OF THE GAS SYSTEM WILL NOT BE
 ACCOMPLISHED AT THIS TIME. BASED ON THE DRAWINGS IT IS
 NOT CLEAR AT THIS TIME IF A GAS PERMIT IS REQUIRED
 UNDER THE FOUNDATION PERMIT, HOWEVER PLEASE REVIEW THE
 COMMENTS BELOW AND PROVIDE A RESPONSE LETTER.
  
 1) SHEETS P401: REFERENCE IS MADE TO CIVIL PLAN SHOWING
 THE POINT OF CONNECTION TO THE METER/TANK. PLEASE
 PROVIDE THE PLAN- SECTION 107.2.1 WPB. NOT PROVIDED
 3) P401: THE GAS PIPING FLOOR PLAN AND THE GAS ISO DO
 NOT MATCH IN TERMS OF WHERE THE GAS PIPING IS MAKING
 PENETRATION INTO THE BUILDING. THE FLOOR PLAN APPEARS
 TO INDICATE THE PIPE COMING UP THROUGH THE FOUNDATION
 AND RUNNING UP THOUGH THE EXTERIOR BLOCK WALL. THE ISO
 APPEARS TO INDICATE A WALL PENETRATION FROM THE
 EXTERIOR TO THE INTERIOR USING A SLEEVE. PLEASE MATCH
 THE TWO DRAWINGS AND REFER TO SECTION 404.14 FBC FG
 PIPING UNDERGROUND BENEATH BUILDINGS. NOT ADDRESSED.
 PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS IS
 PROHIBITED EXCEPT WHERE THE PIPING IS ENCASED IN A
 CONDUIT OF WROUGHT IRON, PLASTIC PIPE, STEEL PIPE, A
 PIPING OR ENCASEMENT SYSTEM LISTED FOR INSTALLATION
 BENEATH BUILDINGS OR OTHER APPROVED CONDUIT MATERIAL
 DESIGNED TO WITHSTAND THE SUPERIMPOSED LOADS. THE
 CONDUIT SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE
 WITH SECTION 404.11 AND SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 404.14.1 OR 404.14.2.
 4) P401 GAS ISO: PROVIDE THE TOTAL BTU LOAD OF THE
 SYSTEM- SECTIONS 402.2 & 402.3 FBC FG. NOT PROVIDED.
 5) P401 GAS ISO: THE DRAWING DOES NOT PROPERLY INDICATE
 A RISER PIPE FROM THE UG PE TO THE REGULATOR AND
 SHUTOFF VALVE. PLEASE SEE SECTIONS 404.17.12 AND
 404.17.2 AND INDICATE THE RISER AND TYPE OF TRANSITION
 FITTINGS TO BE INSTALLED. PLEASE NOTE THE CURRENT
 DRAWING APPEARS TO INDICATE THE SHUTOFF VALVE IS
 UNDERGROUND. PLEASE IDENTIFY THE REGULATOR ON THE
 DRAWING. NOT PROVIDED.
 6) P401 GAS ISO: PLEASE IDENTIFY THE REGULATOR ON THE
 DRAWING- SECTION 410.2 FBC FG. NOT PROVIDED.
 7) P401 GAS ISO: REFER TO SECTION 404.8.1 FBC FG AND
 PROVIDE THE TYPE OF SLEEVE AND A VENT FOR THE SLEEVE.
 NOT PROVIDED
 8) P401 GAS ISO- ADVISORY: THE EHD 18 CSST PIPING
 SUPPLY 299 CFH IS UNDERSIZED BASED ON THE SIZING TABLE
 LISTED ON THE DRAWING- TABLE 402.4(16) FBC FG. A
 MINIMUM EHD 30 IS REQUIRED TO SUPPLY THE SYSTEM AND TO
 SUPPLY THE INDIVIDUAL 199 CFH WATER HEATER GAS LOAD.
 NOT PROVIDED.
 9) P401: INDICATE A TRACER WIRE WILL BE INSTALLED FOR
 THE UG PE- SECTION 404.17.3 FBC FG. NOT PROVIDED.
 A YELLOW INSULATED COPPER TRACER WIRE OR OTHER APPROVED
 CONDUCTOR, OR A PRODUCT SPECIFICALLY DESIGNED FOR THAT
 PURPOSE, SHALL BE INSTALLED ADJACENT TO UNDERGROUND
 NONMETALLIC PIPING. ACCESS SHALL BE PROVIDED TO THE
 TRACER WIRE OR THE TRACER WIRE SHALL TERMINATE ABOVE
 GROUND AT EACH END OF THE NONMETALLIC PIPING. THE
 TRACER WIRE SIZE SHALL BE NOT LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-05-14 Cont ID  
Sent By ccole Date 2021-05-14 Time 10:58 Rev Time 0.00
Received By ccole Date 2021-05-14 Time 09:26 Sent To  
Notes
2021-05-14 10:58:251ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21010007
 5/14/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FOUNDATION REVIEW ONLY-
 SEPARATE PERMIT REQUIRED FOR NEW CONSTRUCTION OF THE
 VILLAS. A COMPLETE REVIEW OF THE GAS SYSTEM WILL NOT BE
 ACCOMPLISHED AT THIS TIME. BASED ON THE DRAWINGS IT IS
 NOT CLEAR AT THIS TIME IF A GAS PERMIT IS REQUIRED
 UNDER THE FOUNDATION PERMIT, HOWEVER PLEASE REVIEW THE
 COMMENTS BELOW AND PROVIDE A RESPONSE LETTER.
  
 1) SHEETS P401: REFERENCE IS MADE TO CIVIL PLAN SHOWING
 THE POINT OF CONNECTION TO THE METER/TANK. PLEASE
 PROVIDE THE PLAN- SECTION 107.2.1 WPB.
  
 2) PLEASE REVIEW ZONING AND BUILDING COMMENTS REGARDING
 SITE PLANNING, ADDRESSING AND SEPARATE PERMITTING. A
 COMPLETE GAS REVIEW FOR THE VILLA FOUNDATIONS CANNOT BE
 COMPLETED AT THIS TIME- SECTION 107.2.1 WPB.
  
 3) P401: THE GAS PIPING FLOOR PLAN AND THE GAS ISO DO
 NOT MATCH IN TERMS OF WHERE THE GAS PIPING IS MAKING
 PENETRATION INTO THE BUILDING. THE FLOOR PLAN APPEARS
 TO INDICATE THE PIPE COMING UP THROUGH THE FOUNDATION
 AND RUNNING UP THOUGH THE EXTERIOR BLOCK WALL. THE ISO
 APPEARS TO INDICATE A WALL PENETRATION FROM THE
 EXTERIOR TO THE INTERIOR USING A SLEEVE. PLEASE MATCH
 THE TWO DRAWINGS AND REFER TO SECTION 404.14 FBC FG
 PIPING UNDERGROUND BENEATH BUILDINGS.
 PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS IS
 PROHIBITED EXCEPT WHERE THE PIPING IS ENCASED IN A
 CONDUIT OF WROUGHT IRON, PLASTIC PIPE, STEEL PIPE, A
 PIPING OR ENCASEMENT SYSTEM LISTED FOR INSTALLATION
 BENEATH BUILDINGS OR OTHER APPROVED CONDUIT MATERIAL
 DESIGNED TO WITHSTAND THE SUPERIMPOSED LOADS. THE
 CONDUIT SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE
 WITH SECTION 404.11 AND SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTION 404.14.1 OR 404.14.2.
  
 4) P401 GAS ISO: PROVIDE THE TOTAL BTU LOAD OF THE
 SYSTEM- SECTIONS 402.2 & 402.3 FBC FG.
  
 4) P401 GAS ISO: THE DRAWING DOES NOT PROPERLY INDICATE
 A RISER PIPE FROM THE UG PE TO THE REGULATOR AND
 SHUTOFF VALVE. PLEASE SEE SECTIONS 404.17.12 AND
 404.17.2 AND INDICATE THE RISER AND TYPE OF TRANSITION
 FITTINGS TO BE INSTALLED. PLEASE NOTE THE CURRENT
 DRAWING APPEARS TO INDICATE THE SHUTOFF VALVE IS
 UNDERGROUND. PLEASE IDENTIFY THE REGULATOR ON THE
 DRAWING.
  
 5) P401 GAS ISO: PLEASE IDENTIFY THE REGULATOR ON THE
 DRAWING- SECTION 410.2 FBC FG.
  
 6) P401 GAS ISO: REFER TO SECTION 404.8.1 FBC FG AND
 PROVIDE THE TYPE OF SLEEVE AND A VENT FOR THE SLEEVE.
  
 7) P401 GAS ISO- ADVISORY: THE EHD 18 CSST PIPING
 SUPPLY 299 CFH IS UNDERSIZED BASED ON THE SIZING TABLE
 LISTED ON THE DRAWING- TABLE 402.4(16) FBC FG. A
 MINIMUM EHD 30 IS REQUIRED TO SUPPLY THE SYSTEM AND TO
 SUPPLY THE INDIVIDUAL 199 CFH WATER HEATER GAS LOAD.
  
 8) P401: INDICATE A TRACER WIRE WILL BE INSTALLED FOR
 THE UG PE- SECTION 404.17.3 FBC FG.
 A YELLOW INSULATED COPPER TRACER WIRE OR OTHER APPROVED
 CONDUCTOR, OR A PRODUCT SPECIFICALLY DESIGNED FOR THAT
 PURPOSE, SHALL BE INSTALLED ADJACENT TO UNDERGROUND
 NONMETALLIC PIPING. ACCESS SHALL BE PROVIDED TO THE
 TRACER WIRE OR THE TRACER WIRE SHALL TERMINATE ABOVE
 GROUND AT EACH END OF THE NONMETALLIC PIPING. THE
 TRACER WIRE SIZE SHALL BE NOT LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2021-10-28 Cont ID  
Sent By jleahy Date 2021-10-28 Time 16:39 Rev Time 0.00
Received By jleahy Date 2021-10-04 Time 16:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-09-26 Cont ID  
Sent By lmarchan Date 2021-09-26 Time 08:09 Rev Time 0.00
Received By lmarchan Date 2021-08-31 Time 06:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status F Date 2021-08-26 Cont ID  
Sent By shill Date 2021-08-26 Time 06:39 Rev Time 0.00
Received By shill Date 2021-08-25 Time 15:59 Sent To  
Notes
2021-08-26 06:46:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THIS IS A DIGITAL PROJECT, REQUIRED FOR COMMERCIAL
 PROJECTS OVER 25 PAGES OR FOR MASTER PLANS. IT IS NOT
 CLEAR WHY SOMEONE SUBMITTED ONE PAPER PAGE TO THE
 BUILDING DIVISION AS A RESUBMITTAL. ALL PLANS SHOULD BE
 UPLOADED IN CADD PRODUCED PDF FORM DIRECTLY TO
 PROJECTDOX. CONTACT [email protected] AND HAVE
 THEM REMOVE THE SCANNED PAPER PLAN. SCANNED PAPER PLANS
 ARE NOT OF SUFFICIENT QUALITY FOR A LARGE COMMERCIAL
 PROJECT, FBC 107.
  
 2. BUILDING REVIEW REQUIRED THAT PAGES BE MOVED FROM
 SIGNATURE FOLDER (DOCUMENTS WHICH DO NOT GET STAMPED
 AND ISSUED) TO THE DRAWINGS FOLDER. I DO NOT SEE THAT
 HAS BEEN DONE. SEE ALL COMMENTS FOR ALL TRADES AND
 ADDRESS ALL COMMENTS. SINCE EACH REVIEW CYCLE TAKES
 WEEKS, THE LOGIC OF SUBMITTING ONE DOCUMENT AND NOT
 ADDRESSING ALL COMMENTS IS NOT CLEAR.
  
 3. APPLICANT HAS BEEN ADVISED THAT SEPARATE PERMITS FOR
 EACH BUILDING ARE REQUIRED. SUBMIT AT THIS TIME.
 PERMITS CANNOT BE ISSUED WITHOUT PERMIT APPLICATIONS
 AND A SEPARATE PERMIT FOR EACH STRUCTURE IS REQUIRED.
 NO FURTHER REVIEWS WILL BE DONE WITHOUT PERMIT
 APPLICATIONS. PROVIDE THE FOUNDATION VALUE FOR EACH
 PERMIT. THE FEES WILL BE MOVED FROM THIS MASTER PLAN
 REVIEW (WHICH IS ***NOT*** A PERMIT) TO THE PERMIT
 APPLICATIONS. EACH APPLICATION MUST BE ROUTED TO REVIEW
 WHEN THE MASTER PLAN IS CLOSE TO ISSUANCE.
  
 4. APPLICANT IS TO CORRECT NAMING CONVENTION ISSUES BY
 COORDINATING WITH THE PERMIT LIBRARIANS. FOR INSTANCE,
 THERE ARE TWO PAGES WITH THE PREFIX 18, BOTH NAMED ROOF
 FRAMING DETAILS. IT APPEARS THAT THE ONE UPLOADED ON
 4/9/21 WAS NOT NAMED CONSISTENTLY WITH THE OTHER PAGES,
 BUT THIS IS FOR THE APPLICANT TO DETERMINE WHICH PAGES
 SHOULD BE IN REVIEW. IF THE TWO PAGES ARE BOTH NEEDED,
 THEY SHOULD NOT BOTH BE NAMED WITH THE SAME PREFIX (CAN
 BE 18.1,1 18.2).
  
 5. A MASTER PLAN IS USED PRIMARILY TO ISSUE SINGLE
 FAMILY HOMES. THE INTENT FOR THIS "MASTER" IS NOT
 CLEAR. WILL THEY ALL BE BUILT CONCURRENTLY? PERMITTED
 AT DIFFERENT TIMES? PLEASE CONTACT ME TO DISCUSS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-08-24 Cont ID  
Sent By lcrespo Date 2021-08-24 Time 16:23 Rev Time 0.00
Received By lcrespo Date 2021-08-03 Time 09:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-07-06 Time   Rev Time 0.00
Received By aoliver Date 2021-06-24 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-22 Cont ID  
Sent By pvalenti Date 2021-06-22 Time 07:32 Rev Time 0.00
Received By pvalenti Date 2021-04-13 Time 18:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-17 Cont ID  
Sent By shill Date 2021-02-17 Time 07:56 Rev Time 0.00
Received By shill Date 2021-01-12 Time 17:21 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2021-11-30 Cont ID  
Sent By lmarchan Date 2021-11-30 Time 08:05 Rev Time 0.00
Received By lmarchan Date 2021-11-30 Time 08:05 Sent To  
Notes
2021-11-30 08:05:37IMPACT FEES WILL BE WAIVED UNTIL VERTICAL PERMIT PER
 DERREK MOORE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-01-29 Cont ID  
Sent By rmcphers Date 2021-01-29 Time 08:50 Rev Time 0.00
Received By rmcphers Date 2021-01-29 Time 08:50 Sent To  
Notes
2021-01-29 08:51:26PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2021-09-01 Cont ID  
Sent By medwards Date 2021-09-01 Time 10:04 Rev Time 0.00
Received By medwards Date 2021-09-01 Time 08:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-08-26 Cont ID  
Sent By medwards Date 2021-08-17 Time 07:48 Rev Time 0.00
Received By medwards Date 2021-08-17 Time 07:48 Sent To  
Notes
2021-08-17 07:49:41PLEASE EITHER HAVE THE PAGES IN SIGNATURE FILE REMOVED
 OR MOVE THEM TO THE DRAWINGS FOLDER.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-07-06 Cont ID  
Sent By medwards Date 2021-07-06 Time 09:33 Rev Time 0.00
Received By medwards Date 2021-06-28 Time 16:44 Sent To  
Notes
2021-07-06 09:33:462ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21010007
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS PERMIT IS FOR A MASTER FOUNDATION BUT A
 COMPLETE SET OF MECHANICAL PLANS HAVE BEEN SUBMITTED.
 PLEASE EITHER SUBMIT PLANS FOR THE FOUNDATION ONLY OR
 RESPOND TO THE MECHANICAL PLAN REVIEW COMMENTS. PLEASE
 ALSO CONTACT SAMANTHA HILL BY EMAIL TO DISCUSS HOW
 THESE PLANS WILL BE SUBMITTED AND DISCUSS THE FEES. FBC
 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-18 Cont ID  
Sent By medwards Date 2021-05-18 Time 11:32 Rev Time 0.00
Received By medwards Date 2021-05-18 Time 11:18 Sent To  
Notes
2021-05-18 11:23:361) PLEASE PROVIDE THE ENERGY CALCULATIONS.FBC EC
 101.5.1.1.2
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-08-12 Cont ID  
Sent By ccole Date 2021-08-12 Time 13:31 Rev Time 0.00
Received By ccole Date 2021-08-12 Time 12:18 Sent To  
Notes
2021-08-12 13:34:36PLUMBING PROVISO FOR FOUNDATION ONLY PERMIT- 21010007.
  
 PLUMBING APPROVED FOR INSTALLATION OF THE UNDER SLAB
 SANITARY DRAIN.
 SEPARATE PERMITS REQUIRED FOR NEW CONSTRUCTION
 PLUMBING, GAS, AND IRRIGATION SYSTEM INSTALLATIONS.
 REFER TO NEW DUPLEX PERMIT- 21040185
  
 POTABLE WATER AND GAS SERVICE ENTRANCES HAVE BEEN
 REMOVED BY THE ENGINEER AND ARE NOT INCLUDED IN THIS
 PERMIT.

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-07-06 Cont ID  
Sent By ccole Date 2021-07-06 Time 11:20 Rev Time 0.00
Received By ccole Date 2021-07-06 Time 07:07 Sent To  
Notes
2021-07-06 11:20:463RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21010007
 7/6/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESDIENTIAL CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FOUNDATION REVIEW ONLY-
 SEPARATE PERMIT REQUIRED FOR NEW CONSTRUCTION OF THE
 VILLAS. A COMPLETE REVIEW OF THE PLUMBING SYSTEMS WILL
 NOT BE ACCOMPLISHED AT THIS TIME. PLEASE REVIEW THE
 COMMENTS BELOW AND RESUBMIT CORRECTED PLANS.
  
 1) 3RD REQUEST FOR CIVIL PLANS. SHEETS P201, P301,
 P501: REFERENCES ARE MADE FOR CIVIL PLANS THAT ARE
 SHOWING POINTS OF CONNECTIONS TO WATER, SEWER AND STORM
 DRAIN MAINS, AND LOCATIONS OF WATER METERS, PREVENTERS
 ETC.-SECTION 107.2.1 WPB.
  
 2) P201 SANITARY RISERS: VENTS MISSING FOR BATH #2
 SHOWERS- SECTION P3101.2.1 FBC P. PLEASE NOTE THAT THIS
 IS AN ADVISORY COMMENT AND THE ENTIRE PLUMBING SYSTEM
 IS NOT BEING REVIEWED AT THIS TIME.
  
 5) P101 & P201: SHOW THE WATER HEATER PAN DRAIN LINE
 RUNS AND DISCHARGE LOCATIONS. PLEASE INDICATE THE TYPE
 AND SIZE OF PIPES- SECTIONS 504.7.1 AND 504.7.2 FBC P.
  
 PLUMBING COMMENTS 4.D & 7 UNDER THE MAIN PERMIT PLANS
 FOR THE STRUCTURE (21040185) BELOW MUST BE ADDRESSED.
 ADDITIONAL NOTES IN CAPS PROVIDED.
  
 4.D. ON DETAIL A-2, BEFORE THE METER, YOU HAVE AN NRV.
 WHAT IS THIS DEVICE, AND WHAT IS THE PURPOSE. PLEASE
 REMOVE OR CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 PLEASE NOTE BACKFLOW PREVENTERS FOR THE POTABLE WATER
 SERVICES ARE REQUIRED AND SHALL BE INSTALLED UNDER
 SEPARATE PERMITS- SECTION 105.1 WPB.
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 7. THE PIPES UNDER SLAB NEED TO BE INSULATED WITH A
 MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-05-14 Cont ID  
Sent By ccole Date 2021-05-14 Time 09:23 Rev Time 0.00
Received By ccole Date 2021-05-14 Time 08:11 Sent To  
Notes
2021-05-14 09:23:382ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21010007
 5/14/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA RESDIENTIAL CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FOUNDATION REVIEW ONLY-
 SEPARATE PERMIT REQUIRED FOR NEW CONSTRUCTION OF THE
 VILLAS. A COMPLETE REVIEW OF THE PLUMBING SYSTEMS WILL
 NOT BE ACCOMPLISHED AT THIS TIME. PLEASE REVIEW THE
 COMMENTS BELOW AND RESUBMIT CORRECTED PLANS.
  
 1) SHEETS P201, P301, P501: REFERENCES ARE MADE FOR
 CIVIL PLANS THAT ARE SHOWING POINTS OF CONNECTIONS TO
 WATER, SEWER AND STORM DRAIN MAINS, AND LOCATIONS OF
 WATER METERS, PREVENTERS ETC. THIS IS THE 2ND REQUEST
 FOR THE PLANS- SECTION 107.2.1 WPB.
 2) PLEASE REVIEW ZONING AND BUILDING COMMENTS REGARDING
 SITE PLANNING, ADDRESSING AND SEPARATE PERMITTING. A
 COMPLETE PLUMBING APPROVAL FOR THE VILLA FOUNDATIONS
 CANNOT BE COMPLETED AT THIS TIME- SECTION 107.2.1 WPB.
  
 3) SHEET P201 SANITARY RISER: THE 3-INCH WASHING
 MACHINE DRAIN CANNOT CONNECT TO THE FIXTURE DRAIN OF
 THE WATER CLOSET, AND SHALL CONNECT TO THE BUILDING
 DRAIN INDEPENDENTLY AT A POINT EITHER DOWNSTREAM OF THE
 HORIZONTAL WET VENT FOR THE POWDER ROOM- SECTION 912.1
 FBC P.
  
 4) P201 SANITARY RISER: THE VENT FOR THE SHOWER IN BATH
 2 IS NOT SHOWN- SECTION 910.1 FBC P. PLEASE NOTE THAT
 THIS IS AN ADVISORY COMMENT AND THE ENTIRE PLUMBING
 SYSTEM IS NOT BEING REVIEWED AT THIS TIME.
  
 5) P101 & P201: SHOW THE WATER HEATER PAN DRAIN LINE
 RUNS AND DISCHARGE LOCATIONS. PLEASE INDICATE THE TYPE
 AND SIZE OF PIPES- SECTIONS 504.7.1 AND 504.7.2 FBC P.
  
 6) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-22 Cont ID  
Sent By ccole Date 2021-01-22 Time 13:47 Rev Time 0.00
Received By ccole Date 2021-01-22 Time 13:10 Sent To  
Notes
2021-01-22 13:47:391ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21010007
 1/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA RESDIENTIAL CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE PLUMBING RISER DRAWINGS AND A GROUND
 FLOOR PIPING PLAN SHOWING ALL UNDER SLAB PIPING-
 SANITARY, WATER SERVICE AND DISTRIBUTION, GAS,
 CONDENSATE, AND STORM- SECTIONS 107.2.1 & 107.3.5.1.3
 WPB. PLEASE INCLUDE A CIVIL PLAN SHOWING POINTS OF
 CONNECTION TO ONSITE MAIN UTILITY PIPING.
  
 2) SHEET A000: PLEASE UPDATE THE CODE EDITION TO THE
 FLORIDA BUILDING CODE- 2020 7TH EDITION WHICH WENT INTO
 EFFECT ON 12/31/2020.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2021-10-19 Cont ID  
Sent By rmcphers Date 2021-10-19 Time 09:47 Rev Time 0.00
Received By rmcphers Date 2021-10-19 Time 09:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2021-10-14 Cont ID  
Sent By rmcphers Date 2021-10-14 Time 16:24 Rev Time 0.00
Received By rmcphers Date 2021-10-14 Time 16:20 Sent To  
Notes
2021-10-14 16:24:05SIGNATURE REVIEW
  
 DRAWINGS LABELED " VILLACONDOBOUNDARY SURVEY.PDF" IN
 PROJECTDOX DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-09-20 Cont ID  
Sent By rmcphers Date 2021-09-20 Time 15:17 Rev Time 0.00
Received By rmcphers Date 2021-09-20 Time 15:11 Sent To  
Notes
2021-09-20 15:17:05SIGNATURE REVIEW
  
 DRAWINGS LABELED
 "17 S1-FOUNDATION-AND-FIRST-FLOOR-COLUMN-PLAN-REV.0.PDF
 "
 "24 SP-4 SITE PLAN.PDF"
 AND - ALL OF THE ELECTRICAL PLANS
 IN PROJECTDOX DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER
 OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  
2021-08-26 08:31:33THE ENGINEER'S SIGNATURE ON THE ONE PAPER PLAN SHEET 05
 OF 18, PAVING, DRAINAGE, WATER AND SEWER PLAN IS
 ORIGINAL. SENT TO STORAGE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-08-12 Cont ID  
Sent By rmcphers Date 2021-08-12 Time 09:57 Rev Time 0.00
Received By rmcphers Date 2021-08-12 Time 09:57 Sent To  
Notes
2021-08-12 09:57:59SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-07-02 Cont ID  
Sent By rmcphers Date 2021-07-02 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2021-07-02 Time 12:49 Sent To  
Notes
2021-07-02 12:50:19REVISED DRAWINGS ADDED TO THE "DRAWINGS" FOLDER =
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-13 Cont ID  
Sent By rmcphers Date 2021-05-13 Time 12:29 Rev Time 0.00
Received By rmcphers Date 2021-05-13 Time 12:29 Sent To  
Notes
2021-05-13 12:32:16REVISED STRUCTURAL DRAWINGS ADDED TO THE "DRAWINGS"
 FOLDER = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER
 OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-29 Cont ID  
Sent By rmcphers Date 2021-01-29 Time 08:51 Rev Time 0.00
Received By rmcphers Date 2021-01-29 Time 08:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-09-25 Cont ID  
Sent By jroach Date 2021-09-25 Time 15:01 Rev Time 0.00
Received By jroach Date 2021-09-25 Time 15:01 Sent To  
Notes
2021-09-25 15:03:00THIS REVIEW IS FOR THE MASTER FOUNDATION PERMIT ONLY!
  
 EACH VILLA SHALL BE INDIVIDUALLY PERMITTED. PERMIT
 APPLICATIONS SHALL BE ACCOMPANIED WITH A SITE PLAN A
 SITE PLAN, ETC.
  
 SEPARATE PERMITS ARE REQUIRED FOR ALL LANDSCAPING,
 FENCING AND GATES, HARDSCAPE, ETC. AND ARE NOT INCLUDED
 IN THIS PERMIT REVIEW.
  
 THE BANYAN CAY RESIDENTIAL/COMMERCIAL PLANNED
 DEVELOPMENT (RPD/CPD) SHALL BE SUBJECT TO ALL
 DEVELOPMENT ORDER CONDITIONS, AS OUTLINED IN RESOLUTION
 NO. 177-21, APPROVED ON AUGUST 23, 2021, AND AS MAY BE
 AMENDED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 2 Status P Date 2021-06-14 Cont ID  
Sent By jroach Date 2021-06-14 Time 14:28 Rev Time 0.00
Received By jroach Date 2021-06-14 Time 14:28 Sent To  
Notes
2021-06-14 14:29:17THIS REVIEW IS FOR THE MASTER FOUNDATION PERMIT ONLY!
  
 EACH VILLA SHALL BE INDIVIDUALLY PERMITTED. PERMIT
 APPLICATIONS SHALL BE ACCOMPANIED WITH A SITE PLAN A
 SITE PLAN, ETC.
  
 SEPARATE PERMITS ARE REQUIRED FOR ALL LANDSCAPING,
 FENCING AND GATES, HARDSCAPE, ETC. AND ARE NOT INCLUDED
 IN THIS PERMIT REVIEW.
  
 THE BANYAN CAY RESIDENTIAL/COMMERCIAL PLANNED
 DEVELOPMENT (RPD/CPD) SHALL BE SUBJECT TO ALL
 DEVELOPMENT ORDER CONDITIONS, AS OUTLINED IN RESOLUTION
 NO. 76-21, APPROVED ON MAY 3, 2021, AND AS MAY BE
 AMENDED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-15 Cont ID  
Sent By jroach Date 2021-01-15 Time 09:39 Rev Time 0.00
Received By jroach Date 2021-01-15 Time 09:39 Sent To  
Notes
2021-01-15 09:39:49ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 01.15.2021
 PERMIT NO.: 21010007
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. YOU WILL NEED TO CONFIRM WITH THE BUILDING DIVISION
 THAT SEPARATE PERMITS WILL BE REQUIRED FOR EACH
 INDIVIDUAL VILLA AS THEY ARE COMPLETELY INDEPENDENT
 STRUCTURES.
  
 2. IT IS STAFF?S UNDERSTANDING THAT MODIFICATIONS TO
 THE VILLAS HAVE OCCURRED FROM THAT WHICH WAS APPROVED
 AS PART OF THE PLANNED DEVELOPMENT (PD). AS SUCH AN
 AMENDMENT TO THE PLANNED DEVELOPMENT SHALL BE SUBMITTED
 AND APPROVED PRIOR TO THE ISSUANCE OF ANY BUILDING
 PERMIT.
  
 3. THE SITE PLAN SHALL CLEARLY IDENTIFY THE SCOPE OF
 THE WORK THAT IS BEING COVERED BY THIS PERMIT.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved