Plan Review Details - Permit 20121415
Plan Review Stops For Permit 20121415
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2021-06-17 Cont ID  
Sent By jgomez Date 2021-06-17 Time 13:26 Rev Time 0.00
Received By jgomez Date 2021-06-17 Time 13:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2021-06-02 Cont ID  
Sent By jgomez Date 2021-06-02 Time 13:26 Rev Time 0.00
Received By jgomez Date 2021-06-02 Time 13:01 Sent To  
Notes
2021-06-02 13:26:11REVISED 06/10/2021
  
 RESIDENTIAL (R3)ALTERATION FIFTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121415
  
  
 1- SEE MECHANICAL REVIEW COMMENTS FOR PROPOSED
 MINI-SPLIT UNIT FOR HEATING REQUIREMENTS IN NEW
 BEDROOM.
 SEC. R303.10 FBC-RESIDENTIAL.
  
 2-REPEAT COMMENT:
 VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION IS FOR ALL WORK SHOWN ON PLANS THAT WAS DONE
 WITHOUT PERMITS. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION AS REQUIRED, INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. VALUATION WAS NOT
 UPDATED.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-04-19 Cont ID  
Sent By jgomez Date 2021-04-16 Time 16:47 Rev Time 0.00
Received By jgomez Date 2021-04-16 Time 16:21 Sent To  
Notes
2021-04-19 08:53:01RESIDENTIAL (R3)ALTERATION FOURTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121415
  
 ORIGINAL COMMENT:
 NOTE: NEED TO PROVIDE INFORMATION ABOUT THE HEAT SOURCE
 FOR NEW BEDROOM #3 AND ROOM FACING THE BEDROOM. THIS
 WAS REQUESTED BY THE MECHANICAL PLANS EXAMINER. I
 DIDN'T SEE ANY INFORMATION SHOWING COMPLIANCE WITH THIS
 REQUIREMENT. IF USING WINDOW UNITS, THEN NEED DEDICATED
 OUTLETS (220 OUTLET MAY BE REQUIRED). SEC. R303.10
 FBC-RESIDENTIAL.
 RESPONSE:
 MECHANICAL PLANS EXAMINER COMMENTS STILL HAVE NOT BEEN
 ADDRESSED. AT THIS POINT IT IS NOT KNOWN IF THE
 SPECIFIED EQUIPMENT IS ADEQUATE TO PROVIDE THE REQUIRED
 HEAT IN THE NEW HABITABLE AREAS. NEED HEATING
 CALCULATIONS AND EQUIPMENT SPECS AS REQUESTED TO THE
 ENGINEER BY THE MECHANICAL REVIEWER.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
 ORIGINAL COMMENT:
 VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION IS FOR ALL WORK SHOWN ON PLANS THAT WAS DONE
 WITHOUT PERMITS. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION AS REQUIRED, INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. VALUATION WAS NOT
 UPDATED.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-03-17 Cont ID  
Sent By jgomez Date 2021-03-09 Time 09:12 Rev Time 0.00
Received By jgomez Date 2021-03-09 Time 11:10 Sent To  
Notes
2021-03-09 12:07:1303/09/21
 EMAILED JASON MOAN. WAITING ON HEATER SPECS TO FINISH
 REVIEW. PLANS NEED TO REFLECT HEATER SPECS.
  
  
  
 03/03/21
 NOTE: COURTESY REVIEW OF PLAN EMAILED BY JASON MOAN.
  
 1) 53"X37" SINGLE HUNG WINDOW DOESN'T COMPLY WITH THE
 EMERGENCY ESCAPE REQUIREMENTS.
 2) CARBON MONOXIDE ALARMS INFORMATION IS NOT CLEAR.
 LEGEND BELOW THE FLOOR PLANS SHOW SMOKE DETECTOR
 SYMBOL. IT IS NOT CLEAR IF THIS IS AN SMOKER DETECTOR
 AND CARBON MONOXIDE ALARM COMBO. AND, THERE IS A NOTE
 STATING "CARBON WITHIN 12' OF BEDROOMS". NOT CLEAR
 ABOUT THIS NOTE. IS IT GOING TO BE CARBON MONOXIDE
 ALARM INSIDE AND OUTSIDE THE BEDROOMS AS SHOWN ON
 PLANS?. ALSO, ACCORDING TO SEC. R315.1 FBC-RESIDENTIAL
 CARBON MONOXIDE ALARMS NEED TO BE AT LEAST 10 FEET FROM
 EACH BEDROOM NOT 12 FEET. REVISE AS REQUIRED.
  
 3) NOTE: NEED TO PROVIDE INFORMATION ABOUT THE HEAT
 SOURCE FOR NEW BEDROOM #3 AND ROOM FACING THE BEDROOM.
 THIS WAS REQUESTED BY THE MECHANICAL PLANS EXAMINER. I
 DIDN'T SEE ANY INFORMATION SHOWING COMPLIANCE WITH THIS
 REQUIREMENT. IF USING WINDOW UNITS, THEN NEED DEDICATED
 OUTLETS (220 OUTLET MAY BE REQUIRED). SEC. R303.10
 FBC-RESIDENTIAL.
  
  
  
 ORIGINAL COMMENTS BELOW:
  
  
  
 RESIDENTIAL (R3)ALTERATION TO COVERT BACK HOUSE TO ONE
 SINGLE FAMILY RESIDENCE: BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121415
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- DRAWING 1 OF 1 NEEDS TO HAVE THE SEAL AND SIGNATURE
 OF THE ENGINEER OF RECORD (THOMAS J. TWOMEY, P.E.).
 NEED ORIGINAL SEAL/SIGNATURE AS REQUIRED BY SEC.
 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 2- ACCORDING TO CITY RECORDS, NEW BEDROOM #3 IS LOCATED
 WHERE THE PORCH USED TO BE. THERE ARE NO CITY RECORDS
 SHOWING PORCH ALTERATIONS. NEED TO SPECIFY SIZE AND
 TYPE OF WINDOWS TO VERIFY COMPLIANCE WITH TH EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. AT LEAST
 ONE WINDOW NEEDS TO COMPLY WITH THE EGRESS
 REQUIREMENTS.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 3- SHOW ON THE FLOOR PLAN THE LOCATION OF CARBON
 MONOXIDE ALARMS FOR ALL BEDROOMS, INCLUDING EXISTING
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 4- SHOW ON THE FLOOR PLAN THE LOCATION OF SMOKE ALARMS
 FOR ALL ALL BEDROOMS, INCLUDING EXISTING BEDROOMS AS
 REQUIRED BY SEC. R314 FBC-RESIDENTIAL.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION IS FOR ALL WORK SHOWN ON PLANS THAT WAS DONE
 WITHOUT PERMITS. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION AS REQUIRED, INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-03 Cont ID  
Sent By jgomez Date 2021-03-03 Time 09:48 Rev Time 0.00
Received By jgomez Date 2021-03-03 Time 09:48 Sent To  
Notes
2021-03-03 10:07:1803/03/21
 NOTE: COURTESY REVIEW OF PLAN EMAILED BY JASON MOAN.
  
 1) 53"X37" SINGLE HUNG WINDOW DOESN'T COMPLY WITH THE
 EMERGENCY ESCAPE REQUIREMENTS.
 2) CARBON MONOXIDE ALARMS INFORMATION IS NOT CLEAR.
 LEGEND BELOW THE FLOOR PLANS SHOW SMOKE DETECTOR
 SYMBOL. IT IS NOT CLEAR IF THIS IS AN SMOKER DETECTOR
 AND CARBON MONOXIDE ALARM COMBO. AND, THERE IS A NOTE
 STATING "CARBON WITHIN 12' OF BEDROOMS". NOT CLEAR
 ABOUT THIS NOTE. IS IT GOING TO BE CARBON MONOXIDE
 ALARM INSIDE AND OUTSIDE THE BEDROOMS AS SHOWN ON
 PLANS?. ALSO, ACCORDING TO SEC. R315.1 FBC-RESIDENTIAL
 CARBON MONOXIDE ALARMS NEED TO BE AT LEAST 10 FEET FROM
 EACH BEDROOM NOT 12 FEET. REVISE AS REQUIRED.
  
 3) NOTE: NEED TO PROVIDE INFORMATION ABOUT THE HEAT
 SOURCE FOR NEW BEDROOM #3 AND ROOM FACING THE BEDROOM.
 THIS WAS REQUESTED BY THE MECHANICAL PLANS EXAMINER. I
 DIDN'T SEE ANY INFORMATION SHOWING COMPLIANCE WITH THIS
 REQUIREMENT. IF USING WINDOW UNITS, THEN NEED DEDICATED
 OUTLETS (220 OUTLET MAY BE REQUIRED). SEC. R303.10
 FBC-RESIDENTIAL.
  
  
  
 ORIGINAL COMMENTS BELOW:
  
  
  
 RESIDENTIAL (R3)ALTERATION TO COVERT BACK HOUSE TO ONE
 SINGLE FAMILY RESIDENCE: BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121415
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- DRAWING 1 OF 1 NEEDS TO HAVE THE SEAL AND SIGNATURE
 OF THE ENGINEER OF RECORD (THOMAS J. TWOMEY, P.E.).
 NEED ORIGINAL SEAL/SIGNATURE AS REQUIRED BY SEC.
 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 2- ACCORDING TO CITY RECORDS, NEW BEDROOM #3 IS LOCATED
 WHERE THE PORCH USED TO BE. THERE ARE NO CITY RECORDS
 SHOWING PORCH ALTERATIONS. NEED TO SPECIFY SIZE AND
 TYPE OF WINDOWS TO VERIFY COMPLIANCE WITH TH EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. AT LEAST
 ONE WINDOW NEEDS TO COMPLY WITH THE EGRESS
 REQUIREMENTS.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 3- SHOW ON THE FLOOR PLAN THE LOCATION OF CARBON
 MONOXIDE ALARMS FOR ALL BEDROOMS, INCLUDING EXISTING
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 4- SHOW ON THE FLOOR PLAN THE LOCATION OF SMOKE ALARMS
 FOR ALL ALL BEDROOMS, INCLUDING EXISTING BEDROOMS AS
 REQUIRED BY SEC. R314 FBC-RESIDENTIAL.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION IS FOR ALL WORK SHOWN ON PLANS THAT WAS DONE
 WITHOUT PERMITS. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION AS REQUIRED, INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-12 Cont ID  
Sent By jgomez Date 2021-01-12 Time 13:07 Rev Time 0.00
Received By jgomez Date 2021-01-11 Time 11:13 Sent To  
Notes
2021-01-12 13:22:04RESIDENTIAL (R3)ALTERATION TO COVERT BACK HOUSE TO ONE
 SINGLE FAMILY RESIDENCE: BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121415
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- DRAWING 1 OF 1 NEEDS TO HAVE THE SEAL AND SIGNATURE
 OF THE ENGINEER OF RECORD (THOMAS J. TWOMEY, P.E.).
 NEED ORIGINAL SEAL/SIGNATURE AS REQUIRED BY SEC.
 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 2- ACCORDING TO CITY RECORDS, NEW BEDROOM #3 IS LOCATED
 WHERE THE PORCH USED TO BE. THERE ARE NO CITY RECORDS
 SHOWING PORCH ALTERATIONS. NEED TO SPECIFY SIZE AND
 TYPE OF WINDOWS TO VERIFY COMPLIANCE WITH TH EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. AT LEAST
 ONE WINDOW NEEDS TO COMPLY WITH THE EGRESS
 REQUIREMENTS.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 3- SHOW ON THE FLOOR PLAN THE LOCATION OF CARBON
 MONOXIDE ALARMS FOR ALL BEDROOMS, INCLUDING EXISTING
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 4- SHOW ON THE FLOOR PLAN THE LOCATION OF SMOKE ALARMS
 FOR ALL ALL BEDROOMS, INCLUDING EXISTING BEDROOMS AS
 REQUIRED BY SEC. R314 FBC-RESIDENTIAL.
 SEC. 504 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION IS FOR ALL WORK SHOWN ON PLANS THAT WAS DONE
 WITHOUT PERMITS. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION AS REQUIRED, INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-06-24 Cont ID  
Sent By jleahy Date 2021-06-24 Time 15:52 Rev Time 0.00
Received By jleahy Date 2021-06-24 Time 15:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-05-27 Cont ID  
Sent By jleahy Date 2021-05-27 Time 12:55 Rev Time 0.00
Received By jleahy Date 2021-05-27 Time 12:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-05-03 Cont ID  
Sent By jleahy Date 2021-05-03 Time 05:52 Rev Time 0.00
Received By jleahy Date 2021-05-03 Time 05:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-10 Cont ID  
Sent By cthroop Date 2021-03-10 Time 15:15 Rev Time 0.00
Received By cthroop Date 2021-03-10 Time 15:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By cthroop Date 2021-01-06 Time 16:14 Rev Time 0.00
Received By cthroop Date 2021-01-06 Time 14:52 Sent To  
Notes
2021-01-06 16:41:00PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
 2017 FBC EXISTING BUILDING ALTERATION LEVEL 2
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: ALL NEW ELECTRICAL SYSTEMS AND DEVICES SHALL BE
 BROUGHT UP TO CURRENT CODE REQUIREMENTS.
  
  
 1. SMOKE ALARMS SHALL BE LOCATED AS REQUIRED FOR NEW
 DWELLINGS PER R314.2.2
  
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 2. CARBON MONOXIDE DETECTORS SHALL BE LOCATED PER
 R315.1 SEE DESIGNERS NOTE ON PLAN PAGE 1 OF 1.
  
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2021-06-22 Cont ID  
Sent By lcrespo Date 2021-06-22 Time 14:27 Rev Time 0.00
Received By lcrespo Date 2021-06-22 Time 14:27 Sent To  
Notes
2021-06-22 14:27:5606/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-06-02 Cont ID  
Sent By lcrespo Date 2021-06-02 Time 13:01 Rev Time 0.00
Received By lcrespo Date 2021-06-02 Time 13:01 Sent To  
Notes
2021-06-02 13:03:1506/02/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-04-13 Cont ID  
Sent By lcrespo Date 2021-04-13 Time 11:52 Rev Time 0.00
Received By lcrespo Date 2021-04-13 Time 11:52 Sent To  
Notes
2021-04-13 11:52:4504/13/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-03-15 Cont ID  
Sent By abelisle Date 2021-03-15 Time 18:42 Rev Time 0.00
Received By abelisle Date 2021-03-15 Time 18:42 Sent To  
Notes
2021-03-15 18:49:222ND REVIEW FBC-2020 PLUMBING
 PERMIT-20121415
 3/15/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- PLEASE ADDRESS ALL OF THE PREVIOUS PLAN REVIEW
 COMMENTS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By lcrespo Date 2021-01-06 Time 14:20 Rev Time 0.00
Received By lcrespo Date 2021-01-06 Time 14:20 Sent To  
Notes
2021-01-06 14:55:03REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF A GAS
 PERMIT FOR THE HEATER OUTSIDE. THIS IS UP TO THE
 HOMEOWNER TO MAKE AN APPLICATION TO THE BUILDING
 OFFICIAL AND OBTAIN THE REQUIRED PERMIT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. TANK TYPE WATER HEATERS ARE NOT MADE FOR OUTDOOR USE
 PER THE MANUFACTURERS SPECIFICATION UNLESS IN AN
 APPROVED STRUCTURE SUPPORTED BY THE MANUFACTURER.
 PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE UNIT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 4. PLEASE SUBMIT A GAS RISER ISOMETRIC DRAWING PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS.
  
 5. SUBMIT ON THE ISOMETRIC DRAWING THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS. G2413.4.1,
 G2413.4.2.
  
 6. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 7. IS THIS THE ONLY GAS APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM? REFER TO THE 2017 FBC RES. SEC.
 G2413.
  
 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER THE 2017 FBC RES. SEC. G2413.2.
  
 9. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING
 ELEMENTS OF THE GAS VENT(S) PER THE 2017 FBC RES. SECS.
 G2426 THRU G2429.1.
  
 10. THE GAS HEATER SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 11. SUBMIT A COPY OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE PLAN LISTING
 THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD
 USED IN THIS SYSTEM'S DESIGN PER THE 2017 FBC FG. 402.3
 OR 2017 FBC RES. SEC. G2413.3.
  
 12. PLEASE SHOW THE DISTANCE FROM THE TWO PSI REGULATOR
 TO THE APPLIANCE. COMPLY WITH 2017 FBC FG RES. TABLE
 G2413.4 (12) FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 13. GAS APPLIANCES (WATER HEATER) SHALL NOT BE
 PROHIBITED UNLESS IT COMPLIES WITH PER THE 2017 FBC
 RES. SEC. G2406.2.
  
 14. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.1 GENERAL.
  
 15. HOW IS THIS GAS VENTED AND IT IT NEAR A WINDOW,
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-06-24 Cont ID  
Sent By jleahy Date 2021-06-24 Time 15:53 Rev Time 0.00
Received By jleahy Date 2021-06-16 Time 14:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-14 Cont ID  
Sent By jgomez Date 2021-06-14 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2021-05-24 Time 12:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-03 Cont ID  
Sent By jleahy Date 2021-05-03 Time 05:52 Rev Time 0.00
Received By jleahy Date 2021-04-12 Time 10:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-22 Cont ID  
Sent By pvalenti Date 2021-03-22 Time 10:19 Rev Time 0.00
Received By pvalenti Date 2021-03-05 Time 17:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-21 Cont ID  
Sent By ajones Date 2021-01-21 Time 16:25 Rev Time 0.00
Received By ajones Date 2021-01-05 Time 09:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-06-18 Cont ID  
Sent By hmoser Date 2021-06-18 Time 14:45 Rev Time 0.00
Received By hmoser Date 2021-06-18 Time 13:35 Sent To  
Notes
2021-06-18 14:45:35PASS PROVISO
 1) REFER TO SECTION 301.15 WIND RESISTANCE. PROVIDE
 CONDENSER TIE DOWN TO SLAB.2020 FBC (M)
 2) PROVIDE AHRI SHEET FOR A/C EQUIPMENT.
 3) PROVIDE EQUIPMENT SCHEDULE ON PLAN
 SECTION 107 2020 FBC.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-06-10 Cont ID  
Sent By medwards Date 2021-06-10 Time 11:08 Rev Time 0.00
Received By medwards Date 2021-06-10 Time 11:08 Sent To  
Notes
2021-06-10 11:14:00THIS LATEST SUBMITTAL HAS NOW CHANGED TO A MINI-SPLIT
 CONDITIONING THE 3RD BEDROOM AND SITTING ROOM.
 PLEASE SHOW THE LOCATION OF THE CONDENSING UNIT ON THE
 EXTERIOR AND PROVIDE THE APPLIANCE ANCHORAGE DETAILS.
 FBC RES M1307.2
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-04-16 Cont ID  
Sent By medwards Date 2021-04-16 Time 07:51 Rev Time 0.00
Received By medwards Date 2021-04-16 Time 07:42 Sent To  
Notes
2021-04-16 07:54:46PLEASE PROVIDE THE SPECIFICATION SHEETS FOR THE WINDOW
 HEATER. FBC 107.2.1
 PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE ROOMS BEING HEATED BY THE WINDOW
 UNIT. FBC EC R403.7.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-03-10 Cont ID  
Sent By medwards Date 2021-03-10 Time 10:04 Rev Time 0.00
Received By medwards Date 2021-03-10 Time 08:42 Sent To  
Notes
2021-03-10 10:05:001ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20121415
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT THE SPECIFICATIONS FOR THE MODEL OF
 HEATER USED. FBC 107.2.1
  
 2) PLEASE PROVIDE INFORMATION THAT THE MODEL OF HEATER
 INSTALLED IS UL 499 LISTED. FBC M 912.1
  
 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE HEAT SOURCE FOR THIS AREA. FBC RES
 M1401.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By medwards Date 2021-01-06 Time 17:16 Rev Time 0.00
Received By medwards Date 2021-01-06 Time 17:16 Sent To  
Notes
2021-01-06 17:20:25PLEASE PROVIDE MORE INFORMATION FOR THE CONDITIONING OF
 THIS HOME. IS THERE A HEATING SOURCE AS DEFINED IN FBC
 RES R303.10
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-06-22 Cont ID  
Sent By lcrespo Date 2021-06-22 Time 14:28 Rev Time 0.00
Received By lcrespo Date 2021-06-22 Time 14:28 Sent To  
Notes
2021-06-22 14:28:1906/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-06-02 Cont ID  
Sent By lcrespo Date 2021-06-02 Time 13:01 Rev Time 0.00
Received By lcrespo Date 2021-06-02 Time 13:01 Sent To  
Notes
2021-06-02 13:03:4506/02/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-04-13 Cont ID  
Sent By lcrespo Date 2021-04-13 Time 11:52 Rev Time 0.00
Received By lcrespo Date 2021-04-13 Time 11:52 Sent To  
Notes
2021-04-13 11:53:1904/13/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-03-15 Cont ID  
Sent By abelisle Date 2021-03-15 Time 18:49 Rev Time 0.00
Received By abelisle Date 2021-03-15 Time 18:49 Sent To  
Notes
2021-03-15 18:49:512ND REVIEW FBC-2020 PLUMBING
 PERMIT-20121415
 3/15/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- PLEASE ADDRESS ALL OF THE PREVIOUS PLAN REVIEW
 COMMENTS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By lcrespo Date 2021-01-06 Time 14:20 Rev Time 0.00
Received By lcrespo Date 2021-01-06 Time 14:13 Sent To  
Notes
2021-01-06 14:14:3501/06/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF ANY
 PERMITS THAT PERTAIN TO EXISTING PLUMBING OR GAS AT
 THIS ADDRESS. IN A CONVERSATION WITH THE BUILDING
 OFFICIAL, HE SAID THAT HE HAS SPOKEN WITH THE OWNER OF
 THIS STRUCTURE, AND HE AND I DISCUSSED THE VIOLATION.
 IT WAS NOTED THAT THIS WOULD BE TURNED BACK INTO A
 SINGLE-FAMILY HOUSE. PLEASE SHOW AND PUT A NARRATIVE ON
 THE PLANS OF THE SCOPE OF WORK. ANY PLUMBING THAT IS
 GOING TO RETURN TO ITS ORIGINAL STATE WILL HAVE TO BE
 DOCUMENTED. THE FIELD INSPECTOR MAY FIND OTHER
 VIOLATIONS, AND IN THIS REVIEW, THE EXAMINED VIOLATIONS
 FOR THIS REVIEW WILL NEED TO BE ADDRESSED.
  
 2. PLEASE REFER TO ANY PLUMBING APERTURES AS NEW, NOT
 EXISTING, AS THERE WAS NEVER PERMITTED IN THE FORM OF A
 PERMIT FOR THEM PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. THERE SEEM TO BE OTHER DRAWINGS, 01, 02, AND 03,
 SECTIONS OF THE FLOOR PLANS WITH NOTES AND WATER LINE
 AND NOT SIGNED OR SEALED BY THE ENGINEER OF RECORD IN
 ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G10-11.010 SEALS.
  
 4. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 5. THE PLANS SUBMITTED STATE AN EXISTING GAS HEATER,
 BUT THE CITY OF WEST PALM BEACH DOES NOT HAVE ANY
 RECORD OF PERMIT OR INSPECTIONS ON THE GAS HEATER. THIS
 IS UP TO THE HOMEOWNER TO MAKE AN APPLICATION TO THE
 BUILDING OFFICIAL AND OBTAIN THE REQUIRED PERMIT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
 6. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1. PLEASE REFER TO THE COMMENTS ON
 THE GAS.
  
 7. PLEASE PROVIDE A DETAILED WORK SCOPE ON SHEET 1-1
 AND REFER TO COMMENT TWO AND SUBMITTED SCOPE OF WORK
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION.
  
 8. THE WASHING MACHINE IS OUTSIDE THE RESIDENTIAL
 STRUCTURE, AND PER MANUFACTURER SPECIFICATION, THEY ARE
 NOT MADE FOR OUTSIDE USE. ARE THEY IN A STRUCTURE, AND
 IS THE STRUCTURE APPROVED? PLEASE FIND A LOCATION
 INSIDE THE HOUSE OR PROVIDE AN ENGINEERED STRUCTURE
 WITH A WIND LOAD CALCULATION ACCORDING TO PER THE 2017
 FLORIDA RESIDENTIAL CODE.
  
 9. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. RE
 403.5.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-06-22 Cont ID  
Sent By jgomez Date 2021-06-22 Time 13:59 Rev Time 0.00
Received By jgomez Date 2021-06-22 Time 13:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-02 Cont ID  
Sent By jgomez Date 2021-06-02 Time 13:26 Rev Time 0.00
Received By jgomez Date 2021-06-02 Time 13:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-16 Cont ID  
Sent By jgomez Date 2021-04-16 Time 17:06 Rev Time 0.00
Received By jgomez Date 2021-04-16 Time 17:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By cthroop Date 2021-01-06 Time 15:08 Rev Time 0.00
Received By cthroop Date 2021-01-06 Time 15:08 Sent To  
Notes
2021-01-06 15:11:57PLAN REVIEW / SIGNATURES
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD VALID DIGITALLY SIGNED DOCUMENTS OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2021-06-24 Cont ID  
Sent By ajones Date 2021-06-24 Time 12:57 Rev Time 0.00
Received By ajones Date 2021-06-24 Time 12:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2021-06-11 Cont ID  
Sent By ajones Date 2021-06-11 Time 15:23 Rev Time 0.00
Received By ajones Date 2021-06-11 Time 15:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-04-22 Cont ID  
Sent By ajones Date 2021-04-22 Time 11:01 Rev Time 0.00
Received By ajones Date 2021-04-22 Time 11:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-03-19 Cont ID  
Sent By ajones Date 2021-03-19 Time 10:10 Rev Time 0.00
Received By ajones Date 2021-03-19 Time 10:10 Sent To  
Notes
2021-03-19 10:14:513/19/21- FAILED, PROVIDE DETAILS OF WHAT IS INCLUDED IN
 THE PROPOSED WET BARS?
  
 ANGELLA VANN, AICP
 [email protected]
 561-822-1441

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-21 Cont ID  
Sent By avann Date 2021-01-21 Time 16:22 Rev Time 0.00
Received By ajones Date 2021-01-21 Time 16:22 Sent To  
Notes
2021-01-21 16:25:491/21/21- FAILED- PLEASE EXPLAIN THE LOCATION OF THE
 WASHER/DYER? IS IT OUTSIDE OR IN A BUILDING WITH NO
 DIRECT ACCESS FROM THE INSIDE?
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]