Plan Review Details - Permit 20121414
Plan Review Stops For Permit 20121414
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-05 Cont ID  
Sent By rmcphers Date 2021-04-05 Time 08:50 Rev Time 0.00
Received By rmcphers Date 2021-04-05 Time 08:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-01 Cont ID  
Sent By rmcphers Date 2021-03-01 Time 10:55 Rev Time 0.00
Received By rmcphers Date 2021-03-01 Time 10:48 Sent To  
Notes
2021-03-01 10:55:24GLASS FENCE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING NEEDS TO SHOW THAT THE GLAZING WILL COMPLY
 WITH FBC R308.3.1 IMPACT TEST.
 WHERE REQUIRED BY OTHER SECTIONS OF THE CODE, GLAZING
 SHALL BE TESTED IN ACCORDANCE WITH CPSC 16 CFR 1201.
 GLAZING SHALL COMPLY WITH THE TEST CRITERIA FOR
 CATEGORY II UNLESS OTHERWISE INDICATED IN TABLE
 R308.3.1(1). FBC R308.4.4 GLAZING IN GUARDS AND
 RAILINGS.
 GLAZING IN GUARDS AND RAILINGS, INCLUDING STRUCTURAL
 BALUSTER PANELS AND NONSTRUCTURAL IN-FILL PANELS,
 REGARDLESS OF AREA OR HEIGHT ABOVE A WALKING SURFACE
 SHALL BE CONSIDERED TO BE A HAZARDOUS LOCATION.
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-04-23 Cont ID  
Sent By fmittner Date 2021-04-23 Time 10:44 Rev Time 0.00
Received By fmittner Date 2021-04-23 Time 10:44 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-03-26 Cont ID  
Sent By fmittner Date 2021-03-26 Time 16:04 Rev Time 0.00
Received By fmittner Date 2021-03-26 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-23 Cont ID  
Sent By lmarchan Date 2021-04-23 Time 11:34 Rev Time 0.00
Received By lmarchan Date 2021-03-30 Time 15:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-26 Cont ID  
Sent By lmarchan Date 2021-03-26 Time 16:21 Rev Time 0.00
Received By lmarchan Date 2021-02-10 Time 20:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-04-05 Cont ID  
Sent By rmcphers Date 2021-04-05 Time 08:50 Rev Time 0.00
Received By rmcphers Date 2021-04-05 Time 08:50 Sent To  
Notes
2021-04-05 08:51:49SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-01 Cont ID  
Sent By rmcphers Date 2021-03-01 Time 10:55 Rev Time 0.00
Received By rmcphers Date 2021-03-01 Time 10:55 Sent To  
Notes
2021-03-01 10:56:25SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 2 Status P Date 2021-04-23 Cont ID  
Sent By fmittner Date 2021-04-23 Time 10:43 Rev Time 0.00
Received By fmittner Date 2021-04-23 Time 10:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-03-26 Cont ID  
Sent By fmittner Date 2021-03-26 Time 16:04 Rev Time 0.00
Received By fmittner Date 2021-03-26 Time 16:04 Sent To  
Notes
***NONE***