Plan Review Details - Permit 20121397
Plan Review Stops For Permit 20121397
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-02-04 Cont ID  
Sent By cpuell Date 2021-02-04 Time 15:19 Rev Time 0.00
Received By cpuell Date 2021-02-04 Time 15:19 Sent To  
Notes
2021-02-04 15:21:46WE CURRENTLY HAVE THREE ADDRESSES FOR THE SPACE
 INDICATED, 730 730B AND 732. COULD YOU PLEASE INDICATE
 WHICH ADDRESS IS CORRECT, ALSO COULD YOU TELL US WHO
 THE TENANT WAS IN THAT SPACE BEFORE. PLEASE EMAIL
 [email protected].

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-01-19 Time 16:27 Rev Time  
Received By   Date 2021-01-19 Time 15:29 Sent To  
Notes
2021-01-19 16:22:09COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-19 Cont ID  
Sent By jwitmer Date 2021-01-19 Time 16:28 Rev Time 0.00
Received By jwitmer Date 2021-01-19 Time 15:29 Sent To  
Notes
2021-01-19 16:26:22WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20121397
 ADD: 730 BELVEDERE RD.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 19TH/ 2021
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES A VALUE OF
 $8,000.00 DOLLARS, THIS IS EXTREMELY LOW AND NEEDS TO
 BE ADDRESSED IMMEDIATELY, A 2ND REVIEW SHOULD NOT BE
 COMPLETED UNTIL A REALISTIC VALUE IS GIVEN. THE
 DESIGNER OF RECORD SHOULD BE ABLE TO PROVIDE MORE
 REALISTIC VALUE FOR THIS PROJECT. THE VALUE SHOULD
 INCLUDE FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES AND OR ENGINEERING FEES,
 MARKETING COST, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL
 ADJUSTMENTS FOR LOCATION AS PUBLISHED BY THE
 INTERNATIONAL CODE CONGRESS. 109.3 BUILDING PERMIT
 VALUATION.
  
 2) THE LIFE SAFETY PLAN IS MISSING INFORMATION NEEDED
 FOR A COMPLETE REVIEW. 2017 FLORIDA BUILDING CODE W
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 SQUARE FOOT AREA OF TENANT SPACE.
 OCCUPANT LOAD/ TAKEN GROSS OR NET
 ELEVATION VIEWS OF THE RESTROOM WITH ACCESSIBLE
 ELEMENTS GIVEN REQUIRED DIMENSIONS
 DRINKING FOUNTAINS
 RESTROOMS
 ELEVATIONS OF KIOSK & WORK SURFACES.
  
 3A) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 3B) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 3C) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 3D) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 4A) LAVATORIES AND SINKS> 2017 FBC-ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 4B) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED
 CLEAR FLOOR SPACE ON THE FLOOR PLAN.
  
 4C) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY &
 DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
  
 4D) CLEARANCES AT WATER CLOSETS. 604.3 CLEARANCE.
 CLEARANCES AROUND THE WATER CLOSETS AND IN TOILET
 COMPARTMENTS SHALL COMPLY WITH 604.3.
 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR
 WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE
 7-FOOT 1 INCH.
  
 4E) 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY CODE. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 4F) GRAB BARS/ RESTROOMS> 2017 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 4G) 2017 FBC-ACCESSIBILITY CODE SECTION 604.5.1 THE
 SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 4H) 2017 FBC-ACCESSIBILITY CODE SECTION 604.5.2 REAR
 WALL. THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915
 MM) LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND
 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 4I) TOILET PAPER DISPENSERS. 604.7. THE TOILET PAPER
 DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES
 MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER.
  
 4J) THE OUTLET OF THE DISPENSER SHALL BE 15 INCHES
 MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 AND SHALL NOT BE LOCATED BEHIND THE GRAB BARS.
  
 5A) WORK SURFACE HEIGHTS. 902.3 HEIGHT. THE TOPS OF
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5B)CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3
 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5C) SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5
 POSITION. UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR
 GROUND SPACE SHALL BE POSITIONED FOR EITHER A FORWARD
 OR PARALLEL APPROACH TO AN ELEMENT.
  
 5D) 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS
 AND SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR
 904.4.2. THE ACCESSIBLE PORTION OF THE COUNTERTOP SHALL
 EXTEND THE SAME DEPTH AS THE SALES OR SERVICE COUNTER
 TOP.
  
 6) 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION06/2020. IN RESTROOMS & SERVICE SINK
 AREAS EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH
 HARD, NON-ABSORBENT SURFACE.
  
 6A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 6B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 6C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-20 Cont ID  
Sent By equinone Date 2021-01-20 Time 13:58 Rev Time 0.00
Received By equinone Date 2021-01-20 Time 09:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-01-12 Cont ID  
Sent By pleduc Date 2021-01-12 Time   Rev Time 0.00
Received By pleduc Date 2021-01-11 Time 13:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-04 Cont ID  
Sent By cpuell Date 2021-02-04 Time 15:22 Rev Time 0.00
Received By cpuell Date 2021-01-07 Time 10:24 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-01-19 Cont ID  
Sent By jwitmer Date 2021-01-19 Time 16:27 Rev Time 0.00
Received By jwitmer Date 2021-01-19 Time 16:20 Sent To  
Notes
2021-01-19 16:24:57CHANGE OF OCCUPANCY/ IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-13 Cont ID  
Sent By medwards Date 2021-01-13 Time 17:18 Rev Time 0.00
Received By medwards Date 2021-01-13 Time 17:05 Sent To  
Notes
2021-01-13 17:20:15PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THE AHU-1. FBC EC C403.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-12 Cont ID  
Sent By jesmith Date 2021-01-12 Time 17:01 Rev Time 0.00
Received By jesmith Date 2021-01-12 Time 13:53 Sent To  
Notes
2021-01-12 17:01:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20121397 730 BELVEDERE RD
  
 1ST REVIEW
 PLUMBING COMMENTS:
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.VALUE OF JOB SEEMS LOW WHEN COMPARED TO ENTIRE SCOPE
 OF WORK. PROVIDE AN ACCURATE VALUATION OF ALL WORK AND
 COST. 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL (1)CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS FOR
 NEW TOILET ROOM INDICATING THE FOLLOWING:
 A.THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C.THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D.THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F.TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 H.LAVATORIES AND ACCESSIBLE SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND PER FBC ACC 606.3, ADDITIONALLY SHOW TOE AND
 KNEE CLEARANCE AS REQUIRED BY FBC ACC 306.2 AND 306.3
 I.PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 J.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
 K.MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 603.3.
 L.DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602 PER
 FBC ACC 602.1.
 M.REFERENCE THE DRINKING FOUNTAIN: PROTRUDING OBJECTS
 307.2 PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING
 EDGES MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES
 ABOVE THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY INTO THE CIRCULATION PATH.
 N.602.2CLEAR FLOORUNITS SHALL HAVE A CLEAR FLOOR OR
 GROUND SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER FBC
 ACC 602.2.
 O.OPERABLE PARTS SHALL COMPLY WITH 309 PER FBC ACC
 602.3.
 P.SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 602.4.
 Q.SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND PER FBC ACC 602.7
 R.THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM
 FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM
 FROM THE FRONT EDGE OF THE UNIT, INCLUDING BUMPERS PER
 FBC ACC 602.5.
 S.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE,
  
 3.PER FBC PL 403.3.1, THE ROUTE TO THE PUBLIC TOILET
 FACILITIES REQUIRED BY SECTION 403.3 SHALL NOT PASS
 THROUGH KITCHENS (FOOD PREP AREAS), STORAGE ROOMS OR
 CLOSETS. ACCESS TO THE REQUIRED FACILITIES SHALL BE
 FROM WITHIN THE BUILDING OR FROM THE EXTERIOR OF THE
 BUILDING. ROUTES SHALL COMPLY WITH THE ACCESSIBILITY
 REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO THE
 REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE
 BUILDING IS OCCUPIED.
  
 4.PER FBC PL 608.1 AND WPB CCCM A BACKFLOW PREVENTER IS
 REQUIRED FOR THE POTABLE WATER SERVICE AND SHALL BE
 INSTALLED TO COMPLY WITH THE WPB CCCM REQUIREMENTS AND
 SHALL BE LEAD FREE. PER WPB FBC 107.2.1, PROVIDE
 SPECIFICATION FOR SAID BACKFLOW PREVENTER. A SEPARATE
 PERMIT IS REQUIRED FOR THE BACKFLOW PREVENTER. IF SUCH
 A BACKFLOW PREVENTER IS EXISTING AND IN PLACE, SHOW IT
 ON THE PLAN AS EXISTING. AN UP TO DATE CERTIFICATION
 SHALL BE PROVIDED PRIOR TO FINAL INSPECTION.
  
 5.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION FOR THE WATER HEATER AT THE LAVATORY.
 IDENTIFY THE WATER HEATER ON THE WATER DISTRIBUTION
 PLANS. PROVIDE ELECTRICAL CHARACTERISTICS AND GPM
 CAPACITY. SHOW THAT THE GPM CAPACITY WILL MEET THE
 DEMAND OF THE LAVATORY AND THE TWO SINKS.
  
 6.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION FOR THE MIXING VALVE AT THE LAVATORY.
 PROVIDE ELECTRICAL CHARACTERISTICS AND GPM CAPACITY.
  
 7.PER WPB FBC PL 603.1, THE WATER SERVICE PIPE SHALL BE
 NOT LESS THAN 3/4 INCH (19.1 MM) IN DIAMETER.
  
 8.PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR SIZING
 OF WATER DISTRIBUTION SHOWING COMPLIANCE WITH THE
 PROVISIONS OF FBC PL SECTION 604.
  
 9.PER FBC PL 606.1, FULL-OPEN VALVES SHALL BE INSTALLED
 IN THE FOLLOWING LOCATIONS:
 A.ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE
 INTO THE STRUCTURE.
 B.ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN
 OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
  
 10.REGARDING THE POINT OF USE WATER HEATER DETAIL, THE
 TWO-WAY VALVE FOR COLD WATER TO SINK AND WATER HEATER
 IS NOT COMPLIANT. PER FBC PL 503.1, THE COLD WATER
 BRANCH LINE TO THE WATER HEATER SHALL BE PROVIDED WITH
 A DEDICATED VALVE. THE CORRECT DISTRIBUTION OF HOT
 WATER FROM THE HEATER TO ALL FIXTURES REQUIRING HOT
 WATER IS NOT INDICATED ON THE PLANS AS ONLY THE FIXTURE
 IN THE DETAIL SEEMS TO BE SUPPLIED WITH HOT WATER. PER
 WPB FBC 107.2.1, PROVIDE A DETAIL SHOWING SAID REQUIRED
 DISTRIBUTION. PER FBC PL 602.2, PROVIDE A SHUT OFF
 VALVE FOR THE COLD WATER SUPPLY AND THE HOT WATER
 SUPPLY TO THE FIXTURE.
  
 11.PER FBC EC C404.4, INSULATE HOT WATER PIPING FROM
 WATER HEATER TO THE FIXTURE SUPPLY IN ACCORDANCE WITH
 FBC EC 403.2.10.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20121397 730 BELVEDERE RD
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-13 Cont ID  
Sent By medwards Date 2021-01-13 Time 17:23 Rev Time 0.00
Received By medwards Date 2021-01-13 Time 17:23 Sent To  
Notes
2021-01-13 17:25:08THE MECHANICAL SHEETS MUST BE DIGITALLY SIGNED AND
 SEALED OR THE ORIGINAL SIGNED AND SEALED PAPER DRAWINGS
 CAN BE DELIVERED TO OUR OFFICE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-02-03 Cont ID  
Sent By kalexand Date 2021-02-03 Time 09:23 Rev Time 0.00
Received By kalexand Date 2021-02-03 Time 09:23 Sent To I
Notes
***NONE***