Plan Review Details - Permit 20121385
Plan Review Stops For Permit 20121385
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-26 Cont ID  
Sent By rmcphers Date 2021-04-26 Time 17:00 Rev Time 0.00
Received By rmcphers Date 2021-04-26 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-31 Cont ID  
Sent By rmcphers Date 2021-03-31 Time 10:45 Rev Time 0.00
Received By rmcphers Date 2021-03-31 Time 10:35 Sent To  
Notes
2021-03-31 10:38:28SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEW EXTERIOR DOORS AT EXISTING BEDROOM - PLEASE SHOW
 THE EXTERIOR LANDING TO COMPLY WITH FBC R311.3 FLOORS
 AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED
 IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR
 LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2 PERCENT).
 2) THE SITE PLAN NEEDS TO SHOW THE SETBACKS FOR THE
 ADDED ROOFED PATIO.
  
 DEFERRED SUBMITTALS: WINDOW AND DOOR PRODUCT APPROVALS,
 ROOFING SYSTEM.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-01 Cont ID  
Sent By rmcphers Date 2021-02-01 Time 14:43 Rev Time 0.00
Received By rmcphers Date 2021-02-01 Time 13:44 Sent To  
Notes
2021-02-01 14:43:03SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE
 THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN EFFECT
 FBC 2020 AND ASCE 7-16
 2) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - PLEASE PROVIDE A SIGNED CONTRACT TO
 VERIFY THE JOB COST. FBC WPB 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL
 CODE CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE
 SET BY THE BUILDING OFFICIAL.
  
 DEFERRED SUBMITTALS: WINDOW AND DOOR PRODUCT APPROVALS,
 ROOFING SYSTEM.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-23 Cont ID  
Sent By equinone Date 2021-03-23 Time 15:26 Rev Time 0.00
Received By equinone Date 2021-03-23 Time 15:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-28 Cont ID  
Sent By equinone Date 2021-01-28 Time 16:53 Rev Time 0.00
Received By equinone Date 2021-01-28 Time 16:05 Sent To  
Notes
2021-01-28 16:54:22CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) BACK AND FRONT OF UNIT. GFI/WP OUTDOOR RECEPTACLES
 REQUIRED. NEC 210.8(A)(3)
 2) LAUNDRY AREA: GFI RECEPTACLE REQUIRED. NEC
 210.8(A)(10)
 3) PANEL SCHEDULES A AND B: PLEASE PROVIDE AVAILABLE
 SHORT CIRCUIT CURRENT AT MAIN DISCONNECT AND SPECIFY
 AIC RATINGS FOR 250 AMPS DISCONNECT AND BOTH PANELS.
 4) PLEASE SPECIFY IF PANELS HAVE MCB OR IF THEY MLO.
 FBC 107
 5) PLEASE SHOW AND IDENTIFY AND SHOW LOCATION OF
 DISCONNECTING MEANS FOR BOTH PANELS. PLEASE SPECIFY IF
 DISCONNECTS HAVE OCP AND IF YES SPECIFY BREAKER SIZES.
 FBC 107
 6) RISER DIAGRAM: PLEASE SPECIFY HOW FEEDER TO PANELS A
 AND B ARE PROTECTED. PANEL A FEEDER DOES NOT COMPLY
 WITH TAP RULES. IT ALSO SEEMS THAT DISTANCE FROM
 DISCONNECT TO PANEL B IS TOO LONG TO COMPLY WITH TAP
 RULES. SEE NOTES 4 AND 5 AS THESE ITEMS ARE RELATED.
 7) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16 (A NOTE WILL
 SUFFICE)
 8) TAMPER-RESISTANT RECEPTACLES REQUIRED AS PER FBC RE
 E4002.14 (A NOTE WILL SUFFICE)
 9) NOTE 9 SPECIFIES A MINIMUM OF 50%. IT SHOULD BE 75%.
 SEE NOTE: PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT
 OF THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES
 SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT
 OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-30 Cont ID  
Sent By ccarvaja Date 2021-04-30 Time 10:54 Rev Time 0.00
Received By ccarvaja Date 2021-04-30 Time 10:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-30 Cont ID  
Sent By ccarvaja Date 2021-04-30 Time 10:30 Rev Time 0.00
Received By ccarvaja Date 2021-04-12 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-08 Cont ID  
Sent By lcrespo Date 2021-04-08 Time 09:56 Rev Time 0.00
Received By lcrespo Date 2021-03-17 Time 12:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-09 Cont ID  
Sent By lmarchan Date 2021-03-09 Time 08:35 Rev Time 0.00
Received By lmarchan Date 2021-01-15 Time 15:33 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-06-02 Cont ID  
Sent By lmarchan Date 2021-06-02 Time 16:51 Rev Time 0.00
Received By lmarchan Date 2021-04-30 Time 10:32 Sent To  
Notes
2021-05-25 14:10:55RECEIPT MU-2021-25126 - $1945.04 - PAID
2021-04-30 10:33:4704/30/21 EMAILED PBC - IMPACT FEE QUESTIONNAIRE
 UPLAODED IN PROJECTDOX. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-02-01 Cont ID  
Sent By rmcphers Date 2021-02-01 Time 14:43 Rev Time 0.00
Received By rmcphers Date 2021-02-01 Time 14:43 Sent To  
Notes
2021-02-01 14:44:14PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-29 Cont ID  
Sent By hmoser Date 2021-03-29 Time 14:01 Rev Time 0.00
Received By hmoser Date 2021-03-29 Time 13:29 Sent To  
Notes
2021-03-29 13:38:262ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20121385
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE IS NO MECHANICAL PERMIT OR MECHANICAL
 CONTRACTOR FOR THIS PROJECT. PLEASE OBTAIN A MECHANICAL
 PERMIT AND IDENTIFY THE MECHANICAL CONTRACTOR FOR THIS
 PROJECT.
  
 2) EITHER THE MECHANICAL CONTRACTOR CONTRACTED TO DO
 THIS PROJECT OR AND ENGINEER CAN DESIGN THE MECHANICAL
 SYSTEM. PLEASE HAVE THE MECHANICAL CONTRACTOR OR A
 LICENSED ENGINEER IN THE STATE OF FLORIDA WILL NEE TO
 SUBMIT THE DESIGN INCLUDING THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS. FS 471.003 (H)
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-21 Cont ID  
Sent By medwards Date 2021-01-21 Time 13:30 Rev Time 0.00
Received By medwards Date 2021-01-21 Time 13:15 Sent To  
Notes
2021-01-21 13:30:151ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20121385
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEW
 ADDITION.
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-01-21 Cont ID  
Sent By lcrespo Date 2021-01-21 Time 18:11 Rev Time 0.00
Received By lcrespo Date 2021-01-21 Time 18:11 Sent To  
Notes
2021-01-21 18:12:1201/21/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-02-01 Cont ID  
Sent By rmcphers Date 2021-02-01 Time 14:44 Rev Time 0.00
Received By rmcphers Date 2021-02-01 Time 14:44 Sent To  
Notes
2021-02-01 14:44:43DEFERRED SUBMITTAL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-26 Cont ID  
Sent By rmcphers Date 2021-04-26 Time 17:02 Rev Time 0.00
Received By rmcphers Date 2021-04-26 Time 17:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-29 Cont ID  
Sent By medwards Date 2021-03-29 Time 13:40 Rev Time 0.00
Received By medwards Date 2021-03-29 Time 13:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-21 Cont ID  
Sent By medwards Date 2021-01-21 Time 13:37 Rev Time 0.00
Received By medwards Date 2021-01-21 Time 13:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-04-30 Cont ID  
Sent By rthermid Date 2021-04-30 Time   Rev Time 0.00
Received By rthermid Date 2021-04-30 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-04-07 Cont ID  
Sent By rthermid Date 2021-04-07 Time   Rev Time 0.00
Received By rthermid Date 2021-04-07 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-03-05 Cont ID  
Sent By rthermid Date 2021-03-05 Time   Rev Time  
Received By rthermid Date 2021-03-05 Time   Sent To I
Notes
2021-03-05 12:14:16EXPANDING SINGLE FAMILY RESIDENCE.